Verify that the available electrical power supply and the network
frequency correspond to the required operating current taking into
account the appliance's specific location, and the current required to
supply any other appliance connected to the same circuit.
ENPI7M 230V
+/- 10 % 50 Hz 1 Phase
ENPI9M 230V
+/- 10 % 50 Hz 1 Phase
ENPI11M 230V
+/- 10 % 50 Hz 1 Phase
ENPI13T 400V
+/- 10 % 50 Hz 3 Phases
See the corresponding wiring diagram in the appendix.
The connection box is located on the right side of the unit. Three
connections are designed for the power supply and two are for
controlling the filter pump (Enslavement).
3. INSTALLATION AND CONNECTION (continued)
3.4 Electrical connection
F
NF C15-100
GB
BS7671:1992
D
DIN VDE 0100-702
EW EVHS-HD 384-7-702
A
ÖVE 8001-4-702
H
MSZ 2364-702/1994/MSZ 10-553 1/1990
E
UNE 20460-7-702 1993,
RECBT ITC-BT-31 2002
M
MSA HD 384-7-702.S2
IRL Wiring Rules + IS HD 384-7-702
PL
PN-IEC 60364-7-702:1999
I
CEI 64-8/7
CZ
CSN 33 2000 7-702
LUX 384-7.702 S2
SK
STN 33 2000-7-702
NL
NEN 1010-7-702
SLO SIST HD 384-7-702.S2
P
RSIUEE
TR
TS IEC 60364-7-702
Electrical installation and wiring for this equipment must be in
conformity with local installation standards.
Check that the phases
balance does not
exceed 2%
Power supply
400V 3N
50Hz
R S
T N
= = = =
1 2
=
=
Dry contact 16 A max
potential free.
Priority heating function
Dry contact 16 A max
potential free.
Priority heating function
L N
1 2
= =
= =
Power supply
230V
/ 50Hz
OUT2
OUT2
Содержание ENERGYLINE PRO INVERTER