11-1/4"
286mm
14-1/2"
368mm
32-1/2"
826mm
6X Ø3/16" 3
4.8mm
MOUNTING
HOLE
REMOVABLE
ACCESS PANEL
(NOT SHOWN)
3-3/4"
95mm
18-1/2"
470mm
20-5/8"
524mm
FLOOR LINE
15/16"
24mm
SUPPLY
CL
1/2" IPS SUPPLY
23"
584mm
(47-1/2")
(1207mm)
6-9/16"
167mm
2" NPT
FEMALE OUTLET
1-11/16"
43mm
3"
76mm
6-11/16"
170mm
CL
11-1/2"
292mm
(34-5/8")
(879mm)
5"
127mm
(29-5/8")
(752mm)
BALL
DETENT
2X
IN-LINE
STRAINER
HOUSING
APPROVED:
DRAWN:
PART NUMBER
SCALE:
SHEET
OF
REVISION
DRAWING TYPE:
SIZE: A
BY:
ECN NO.
PA
G
E
DATE:
DATE:
ECN:
REVISED PER
CHK'D.:
Haws Corporation - All Rights Reserved. HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
C
R
MODEL(S)
1455 KLEPPE LANE
SPARKS, NEVADA 89431
(775) 359-4712 FAX (775) 359-7424
E-MAIL: [email protected]
WEBSITE: WWW.HAWSCO.COM
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
I.ROBERTS
7/13/10
4
0002080083.D
7656WCSM
NA
1
1
FV
11/23/17
4520
VWC
5 O
F
5
INSTALLATION
5240
2017
VWC
PULL DOWN
TO OPEN
EYE/FACE WASH
33"- 53"
838mm-1346mm
FLOW PATTERN
NOTES:
1. WHEN INSTALLING THIS UNIT, LOCAL , STATE, OR FEDERAL CODES SHOULD BE ADHERED TO FOR
INSTALLATION DIMENSIONS (LOCATIONS), WASTE AND SUPPLY REQUIREMENTS OTHER THAN SHOWN.
2. TO COMPLY WITH ANSI Z358.1-2014 FOR EMERGENCY EYEWASH OR EYE/FACE WASH:
EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED SUCH THAT FLUSHING FLUID PATTERN IS
NOT LESS THAN 33" (838mm) AND NO GREATER THAN 53" (1346mm) FROM SURFACE ON WHICH
USER STANDS; AND 6.0" (153mm) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
3 MOUNTING HARDWARE NOT SUPPLIED.
4. DIMENSIONS MAY VARY BY ±1/2" (13 mm).