background image

10/16 

      Model 7603 

Page 4 of 6 

 

NOTE:  

Acanthamoeba survive mild chlorination and are commonly found in tap 

water. Sterile Antimicrobial Preservative Model 9082 will prevent the growth of 
Acanthamoeba.  Hot water, 158

F (70

C) or hotter will destroy Acanthamoeba but 

must be allowed to cool prior to use in eyewash units. 

 

 

STEP 4: 

If tank pressure drops below 70 psi, ensure the following steps are implemented: 

 

A. 

Ensure that the tank is filled with 10 gallons of clean, potable water.

 

B. 

Recharge with clean air to 75 psi, if applicable.  

Regulate compressed air 

source to 165 psi or less. 

C. 

Follow Procedure A or Procedure B of Step 3 above to ensure that water quality 
is maintained. 

 

TROUBLESHOOTING 

 

PROBLEM 

 

 

REPAIR CHECKLIST 

1.  No flow. 

1.  a.  Tank empty. Refill tank. 

 

 

 

b.  Obstruction in line of fitting. Clean 

obstruction. 

2.  Poor flow. 

2.  a.  Tighten head assembly. 

 

 

 

b.  Check for obstructions.  If necessary, 

remove eyewash head(s) and clean 
flow control. 

3.  Eyewash flows for less than 15 

minutes. 

3.  a.  Fill tank with 10 gallons of water.  

 

 

b.  Fill tank with pressurized air to 75 psi. 

For more information about Haws products, see our website: 

www.hawsco.com

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

© 2016 Haws

®

 Corporation – All Rights Reserved 

HAWS

® 

and other trademarks used

 

in these materials are the exclusive property of Haws Corporation. 

Содержание 7603

Страница 1: ...able for any damages caused by defective materials or poor workmanship except for replacements as provided above Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general special or consequential damages claimed t...

Страница 2: ...ply a small bead of Dow Corning 832 sealant around the threaded end of the dip tube approximately at the second thread from the end of the tube Thread and hand tighten the dip tube into the bottom of the eyewash plumbing STEP 3 Fill the tank with 10 gallons of clean potable water note fill line on main label If desired add Sterile Antimicrobial Preservative Model 9082 as directed see Step 3 under ...

Страница 3: ...yewash and allow unit to drain normally Note that air will continue to escape after the water supply has been exhausted NOTE Customer must use the supplied inspection tag to maintain a record of inspection dates and type of maintenance performed e g adding Sterile Antimicrobial Preservative Model 9082 cleaning tank STEP 1 When the unit is filled with 10 gallons of water it weighs approximately 123...

Страница 4: ...late compressed air source to 165 psi or less C Follow Procedure A or Procedure B of Step 3 above to ensure that water quality is maintained TROUBLESHOOTING PROBLEM REPAIR CHECKLIST 1 No flow 1 a Tank empty Refill tank b Obstruction in line of fitting Clean obstruction 2 Poor flow 2 a Tighten head assembly b Check for obstructions If necessary remove eyewash head s and clean flow control 3 Eyewash...

Страница 5: ......

Страница 6: ...Z358 1 2014 FOR EMERGENCY EYEWASH OR EYEWASH UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES EYE FACE WASH SHALL BE POSITIONED SUCH THAT STREAMS ARE 15 3 CM 6 IN MINIMUM FROM WALL OR NEAREST OBSTRUCTION 2 DIMENSIONS MAY VARY BY 1 2 12 7mm 3 EYEWASH HEAD ASSEMBLY MUST BE PARALLEL TO WALL OR OBSTRUCTION TO MEET CRITERIA STATED IN ACCORDANCE TO...

Отзывы: