Haws 5874SS Скачать руководство пользователя страница 2

02/10                                

Model

 

5874SS/5874PB/5874PBF/VRK5874/PBA6/PBA6HPB/PBA7

                      Page 2 of 5 

Note: 

 
1.  Before removing valve, strainer or cartridge assembly, shut off water     

supply line. 

2.  This valve is pressure compensating.  Be sure to remove any existing flow 

control devices. 

3.  When retrofitting an existing fountain with a 5874SS series assembly: 

a)  Remove any in-line strainer that may be present in the supply line, 
b)  Reconnect tubing to new valve using supplied or existing fittings. 

     4.  Valve is directional.  Verify flow direction indicated on valve when installing. 

Caution:

 Valve must be protected by the 60-mesh strainer LOCATED INSIDE 

VALVE BODY.   
Warranty void if 60-mesh strainer IS REMOVED FROM VALVE BODY.  

 

 

OPERATION & MAINTENANCE OF FRONT ACCESS FEATURES 

 

FLOW ADJUSTMENT:

  A 3/16” hole in the center of this button is provided for front access to 

the adjustment screw found on the cartridge assembly. While pushing the button in and using a 
slotted narrow blade screwdriver, the flow may be adjusted by inserting it into the hole and 
turning clockwise for increased flow, and counterclockwise for decreased flow. 

STRAINER CLEANING:  

Periodically clean the strainer 

located inside valve body

. Remove 

front push-button and retaining nut with the universal spanner wrench provided. Pull cartridge 
assembly out. Gently remove strainer off of cartridge.  Thoroughly flush away any debris from 
strainer. While keeping bottom of cartridge clean of debris, re-attach strainer by aligning larger 
hole opening on gasket over the larger water inlet opening on the cartridge. Insert cartridge 
assembly back into valve body, by aligning screen into large opening inside bottom of valve 
body. Ensure cartridge has bottomed out, by slightly turning into place.  Retighten retaining nut 
and check for leaks. 

CARTRIDGE ASSEMBLY REPLACEMENT:

 Remove front push-button and retaining nut with 

the universal spanner wrench provided. Pull cartridge assembly out. Gently remove strainer off 
of old cartridge and reassemble on new cartridge (see strainer reattachment instructions 
above). Insert cartridge assembly into valve body by aligning screen into large opening inside 
bottom of valve body. Ensure cartridge has bottomed out, by turning slightly into place.  
Retighten retaining nut and check for leaks. 

CAUTION: When replacing strainer or cartridge assembly, damage can occur if 
not properly re-installed.  Read instructions carefully. 

PUSH BUTTON ASSEMBLY/REASSEMBLY 

Must apply 1 Dot of Loctite 222MS Threadlocker on female threads of push-
button. See page 5 of 5 for proper application procedure. 

 
 
 
 
 
 