Hawle 490K Скачать руководство пользователя страница 1

05/2016

Subject to change

Page 1 of 2

Operating instructions for 

Hydrant shortening set

Order No. 490K

1.  Intended use
With the hydrant shortening set, Hawle freeflow underground hydrants can be adapted to the desired pipe cover 

depth on site. In addition to the operating instructions, the applicable standards and regulations, accident pre-

vention regulations and the regulations of the employers‘ liability insurance associations must be observed and 

adhered to in both installations.

2.  Machine description
The shortening set, consisting of grip ring, seal carrier and coupling plate, enables the hydrant to be shortened later, 

even when installed. By screwing to the coupling plate, the grip ring is friction-locked to the standpipe.

3.  Assembly

Initial situation! Bring the hydrant in-

to a depressurized operating state. 

The lowest shortening height is 20 

cm above the upper edge of the gear 

unit housing (see dimension arrow).

Remove dog clutch and dirt seal. Loosen the clamping screw on 

the operation square cap. Remo-

ve operation square cap and pro-

tection cap.

Shorten and deburr the standpi-

pe, PP pipe and square pipe by 

the same amount.

Remove coupling plate.

Slide the new coupling plate onto 

the standpipe and PP pipe.

Spread the grip ring open and 

slide it onto the standpipe.

Press the seal carrier onto the 

standpipe as far as it will go using 

manual pressure.

Push the grip ring back onto the 

seal carrier as far as it will go.

Insert the dirt seal into the seal 

carrier

Pull the coupling plate upwards 

and screw it together with the dog 

clutch. The tightening torque of 

100 Nm must be observed.

Mount the protection cap in the 

PP pipe.

Place operating square on square 

pipe and fix with clamping screw.

1

2

3

4

5

6

7

8

9

10

11

12

Отзывы: