CURRENT MONITORING
INSTALLATION GUIDE
Z203256-0C
PAGE 1
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]
09081
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Split-Core Low Current 4-20mA & 0-5VDC
DC Current Transducer
quick install
Installer's Specifications
)";"3%0'&-&$53*$4)0$,&91-04*0/03"3$'-"4)
t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT
4FF/'1"&JOUIF64"PSBQQMJDBCMFMPDBMDPEFT
t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBEVOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
%0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST
'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ
%"/(&3
Wiring ExamplE
H970HCA
H970HCA
DimEnsions
/05*$&
t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT
t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT
t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT
t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF
Technology
Open loop Hall effect
Amperage Range
0 to 50/100/200 ADC (slide switch selectable)
Sensor Supply Voltage
12 to 30VAC/DC
Supply Current
35mA max.
Isolation
600VAC rms
Temperature Range
-15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Output
4-20mA and/or 0-5VDC
Accuracy
±3% F.S. combined linearity, hysteresis, and repeatability
The product design provides for basic insulation only.
Disconnect and lock out power to the conductor to be monitored.
1.
Choose a location for the sensor. The monitored conductor must pass through the
2.
iris, and the sensor must be at least 1/2" from any uninsulated conductors.
Install the adjustable mounting bracket to the back of the enclosure using the
3.
included screws.
Connect 12-30VAC/DC to the terminals marked Power (+) and Gnd (-).
4.
Wire the output (mA or VDC) connections between the sensor and the controller.
5.
Snap the sensor over the conductor to be monitored and clip the assembly to the
6.
mounting bracket.
Set the field-selectable switch to the desired amperage level (see page 2).
7.
CONTROLLER
+
–
4-20mA
DC
Load
CONTACTOR