background image

ACCESSORIES:

Before cable gland assembly or stripping of the cable gland 
assembly, consideration should be given to any cable gland 
accessories that may be required, such as: -

  Shroud, to offer additional corrosion protection.

  Locknut, to secure cable glands into position.

  Sealing washer, to offer additional ingress protection of the 

enclosure at the cable gland entry.

  Earthtag, to provide an external armour/braid bonding point.

  Serrated washer, to dampen any vibrations that may loosen the 

locknut or cable gland assembly.

SCHEDULE OF LIMITATIONS:

1.  The cable glands when used with braided cable types are only 

suitable for use with fixed apparatus, the cable for which must 
be effectively clamped and cleated elsewhere.

2.  This cable gland has an operating temperature range of -60°C 

to +80°C.

3.  A seal must be formed between the equipment and the cable 

gland to maintain the appropriate degree of protection against 
ingress of dust, solid objects and water.

AI 312 - Issue R / Page 2 of 2

EU Declaration of Conformity in accordance with  European Directive 2014/34/EU

Manufacturer: Hawke International
Address: Oxford Street West, Ashton-under-Lyne, OL7 0NA, United Kingdom.

Equipment: Group II Compression Cable Glands Type: PSG 553/RAC

Provisions of the Directive fulfilled by the Equipment:

Group II Category 2GD Exeb IIC Gb, Exdb IIC Gb, Extb IIIC Db – IP66

Notified Body for EU-Type Examination:

 SGS-Baseefa 1180 Buxton UK

EU-type Examination Certificate: 

Baseefa06ATEX0056X 

Notified Body for production:

 SGS-Baseefa 1180 Buxton UK

Harmonised Standards used:

EN60079-0:2012+A11:2013, EN60079-1:2014, EN60079-7:2015, EN60079-31:2014.

On behalf of the above named company, I declare that, on the date the 
equipment accompanied by this declaration is placed on the market, the 
equipment conforms with all technical and regulatory requirements of the above 
listed directives.

………………………………….

A. Tindall
Technical Manager

………

……

……

…………

F

Select the correct punch tool to suit the 
conductors sizes (see table) and cut out the 
required number of holes in the seal 

 using the 

indented positions as a guide. Remove the entry 

 and pass the individual  conductors through 

the appropriately sized punched holes in the seal 

 ensuring they are not twisted or kinked, and 

slide the seal 

 down to the spigot 

Replace entry 

 and re-assemble middle nut 

 

onto the entry component 

.

Tighten up the middle nut 

 until hand tight, 

then using a wrench/spanner turn the nut 
through a minimum of one full turn. 

Hand tighten the backnut 

 to form a seal 

around the cable, then tighten a further full turn 
using a wrench/spanner. Ensure that the middle 
nut 

 does not rotate when tightening the 

backnut 

. Ensure that the deluge seal is pulled 

down into position, if fitted.

Locate the shroud over the cable gland, if 
applicable.

E

Unscrew the middle nut 

 and visually inspect that

the armour/braid has been successfully clamped
between the armour spigot 

 and the armour

clamping ring 

. If armour/braid not clamped, repeat

assembly.

Note :

 

If the equipment has a threaded entry, it may be

advisable to screw the cable gland into the equipment to
prevent twisting of the cable after Step E 

D

Hold the entry 

 in position with a spanner/wrench to 

prevent rotation. Hand tighten the middle nut 

 to the 

entry 

 and turn a further ½ to ¾ of a turn with a 

spanner/wrench.

IMPORTANT

:

 Support the cable to prevent it from 

twisting.

12.5

16.9

22.0

20.5

26.0

33.0

Outer Sheath

Min.

Max.

0.8/1.25

1.25/1.6

1.6/2.0

0/0.8

0/0.7

0/0.7

Steel Wire Armour/

Tape/Braid

Orientation

2

Orientation

 1

 CABLE GLAND SELECTION TABLE

Male Entry

Thread Size

Metric

Size

Ref.

NPT

Across

Flats

Across

Corners

Hexagon

Dimensions

A

B

C

M20

M25

M32

30.0

36.0

46.0

32.5

39.5

50.5

53.0

69.5

64.0

80

88

95

½" - ¾"

¾" - 1"

1" - 1¼"

C

ompr

essed

Length

M

aximum

Length

CABLE GLAND SIZE FOR CONDUCTOR 

Maximum No.

of Cores

A & B

7

4

3

1.5

2.5

Cores Cross Sectional Area mm²

4.0

6.0

10.0

---

---

---

---

---

---

---

---

A & B

B & C

B

PUNCH TOOL SIZE DETAILS

Punch Ref.

Core C.S.A. mm²

No.1

No.2

No.3

1.5   -   2.5

4.0   -   6.0

10.0

6

2

1

6

3

2

1

1

2

6

5

4

Отзывы: