background image

8

+

-

L1

1 2 3 5

7

1
3

21 V AC

3

2

1

N

PE

GLR 9/ ..

LAD 9.1

1 2 3 4 5 6 7

9

8

}

}

}

+

GND

+24 V DC

27 V AC

+27,6 V DC

2

1

6

5

4

3

LED

T 2,5 A / 

250 V

J1

J2

R.SP

PTC

L.SP

Supply 

27 V AC; 1,5 A

Charging voltage  

27,6 V DC (at 10K instead of  

setting 

battery pack with jumper J1 

5

 set)

Fuse 

1

 

T 2,5 A / 250 V

Monitoring 

yes, cyclically approx. every 25 minutes

Space requirements 

55 mm

Overview of the major components and modules (cont.)

Load module LAD 9.1

Is used to create the charging voltage and for monitoring the 

battery pack connection. 

The load module is fed by a separate transformer coil via a 

fuse 

1

 located on the module. A potentiometer 

2

 is used to set 

the charging voltage. The load module monitors the battery pack 

and mains connection and issues an error in case of a disruption. 

The yellow LED on the load module will come on as soon as the 

mains and battery pack connection is not in order. The module 

will switch off the voltage supply to the ventilation control system 

in case of a mains voltage failure. The sensor at the end of the 

PTC cable is positioned close to the battery back (see image), 

while the other end is connected to the PTC plug 

3

 on the load 

module. If the PTC sensor measures a temperature above 0 °C 

in the area of the battery pack, the charging voltage is 27,6 V. 

Temperatures below 0 °C will increase the charging voltage 

to 30 V. Jumper J2 

4

 is used to enable/disable the charging 

 function, while the potentiometer 

6

 is used to set the minimum 

discharge voltage (pre-set at the factory). This requires that a 

voltage of 19,2 V be applied between GND and pin 7 and that the 

potentiometer 

6

 be set to the level where the LED is barely on/

goes out.

Description of the jumpers (plug-in jumpers) 

4

 + 

5

J1 charging voltage

J1 set: Charging voltage setting

J1 not set: Operating status

J2 minimum discharge voltage

J2 set: Minimum discharge voltage setting 

J2 not set: Operating status

Technical specifications

Trafo

PTC cable

Sensor

Connection to 

screw plate

Mounting rail

Error mains/

battery pack 

connection

Malfunction

Mains

Battery pack

Содержание LZ 908

Страница 1: ...stage of the groups is identified by the designation RAZ 908 Its basic configuration consists of a housing with screw plate as well as a top hat rail a transformer a rectifier module with filter capa...

Страница 2: ...e live During service maintenance work at the unit the supply voltage has to be disconnected via isolating link at all poles Protect the system against unintentional re starting The isolating link mus...

Страница 3: ...electric power lines follow VDE regu lations In any case the wiring type must be coordinated with the responsible authority fire department T V fire protection authority etc All maximum wire lengths...

Страница 4: ...functions for SHEV and ventilation 4 Wind transmitter WG H 10 rain sensor REM H 10 WREM H 10 for automatic closing of windows top hung windows and light domes in case of rain and or wind 5 Conduit box...

Страница 5: ...000 1000 300 1196 2 7 956 3 56 7 3 1000 1000 300 1118 3 7 956 4 56 7 4 1000 1000 300 1040 4 7 956 5 56 7 5 1000 1000 300 962 5 7 956 6 56 7 6 1000 1000 300 884 6 7 956 7 56 7 7 1000 1000 300 806 7 7 9...

Страница 6: ...ety equipment for smoke removal or smoke control perform wiring in accor dance with the functional integrity classes E30 or E90 of the Model Wiring Guideline MLAR Security systems need line monitoring...

Страница 7: ...l diagram The transformer connector is slipped on via cable lugs The central unit is overload and reverse battery protected A short circuit at the and terminals of the 24 V DC feed lines in the contro...

Страница 8: ...age supply to the ventilation control system in case of a mains voltage failure The sensor at the end of the PTC cable is positioned close to the battery back see image while the other end is connecte...

Страница 9: ...The group control module is used to control the motors monitor the motor lines for cable break and include an EMERGENCY STOP function for power controlled windows in the event of an emergency Technic...

Страница 10: ...ese EMERGENCY STOP pushbuttons must comply with standard DIN EN 60204 The devices used to protect against crushing hazards and the EMERGENCY STOP button used as an opener are connect ed in series and...

Страница 11: ...in the area of the fire pushbutton In case of emergency power operation the yellow ERROR LED 8 will flash The red ALARM LED 9 will be lit when the OPEN signal is active on the smoke and heat exhaust v...

Страница 12: ...nitored for disruptions and short circuits Another option is to connect a central fire alarm system which however requires that only smoke detectors or only one central fire alarm system be connected...

Страница 13: ...wind rain alarm is reset after a certain switch off delay The signal issued by the rain sensor is transferred to the internal bus To adjust the set point of the wind rain module slip on the jumper 3 a...

Страница 14: ...r external devices The fuse 4 is used to protect the voltage supply circuit which is switched off in the event of a mains failure The module output is connected via 3 pin connectors 5 6 Jumpers 2 can...

Страница 15: ...ange over module PFW 9 Works in the same way as PFA 9 but its output contacts are designed for 230 V AC Technical specifications Overview of the major components and modules cont Description The poten...

Страница 16: ...TA 3 1 24 V DC Synchronous drives with exter nal synchronisation SYN 2K Sync drives Sync drives Sync drives Sync drives Synchronous drives with additional locking and external synchronous sequence SF...

Страница 17: ...g Follow the terminal diagram to connect the battery pack wire To prevent dangerous gases from developing and to ensure the central control unit remains operational for 72 hrs in case of a mains failu...

Страница 18: ...of the motor lines EMERGENCY STOP button pressed Fuse on module defective Display in wind rain module red LED is lit Error source The wind sensor has triggered a wind alarm The rain sensor was trigger...

Страница 19: ...reversal of polarity yes approx 2 s Pulsing according to prEN 12101 9 yes every 2 min Automatic clearing no Line monitoring yes up to the last conduit box by monitoring diodes with 3rd line Connection...

Страница 20: ...HAUTAU GmbH Wilhelm Hautau Str 2 31689 Helpsen Germany Tel 49 5724 393 0 info hautau de www hautau de...

Отзывы: