GU320a Controller Manual

 

10

 

Gen. 

KVArh

 

 

As the frequency measuring is from L1 phase of the generator, ensure no fault with this part before use. 

6.2

 

Other measuring data 

Oil pressure(

KPa

 

Obtain the data from an external sensor

Coolant temperature

(℃)

 

Obtain the data from an external sensor

Rotating speed 

RPM

 

Obtain the data from speed sensor 

Total running time of the oil engine

h

   

Battery voltage

 (V)

 

 

 

7

 

Fault signal 

7.1

 

 Warning 

 (NOTE: warning is a very serious alarm state, it won’t affect the generator system operation, only 

remind the operator of the improper condition. When warning occurs, the state indicator light illuminate, but 

the buzzer won’t alarm and the fault won’t lock. Once the fault has been eliminated, the warning light off 

automatically.

 

Charge failure 

The controller detect the voltage lower than the “LOW battery pre-alarm setting” from the aux AC 

charger, “CHARGE FAILURE” indicator light illuminate, and the buzzer alarm. 

Battery low    

 

The controller detect the battery voltage lower than the “Low battery pre-alarm value”, the state LCD 

will display “

WARNING

 BATTERY  LOW

, and the buzzer warn. 

Low pressure   

 

After the safety-on delay timeout, and the controller detect the output pressure of the engine lower than 

the low pressure alarm value preset, the buzzer warn. The state LCD will display 

WARNING

LOW OILPRESS

  

H temperature     

The controller detect the coolant temperature of the engine higher than the high temperature preset alarm 

value, and then the buzzer warn, the state screen display

WARNING

COOLANT TEMP

 

the buzzer warn. 

Overspeed            

If the running speed of the engine over the preset alarm value, the LCD will display 

WARNING

OVER SPEED

”,

and the buzzer warn. 

Underspeed          

If the running speed of the engine descend to alarm level preset, then the state LCD display 

WARNING

UNDER SPEED

”,

and the buzzer warn. 

High voltage         

 If the controller detects the output voltage of the generator over the alarm value preset, the state LCD 

will display 

WARNING

 V HIGH

”,

and the buzzer warn. 

Low voltage          

 

If the controller detects output voltage lower than the alarm value preset, then the state LCD will display 

WARNING

V LOW

”,

and the buzzer warn. 

Overcurrent          

 

If the controller detects the output current over the alarm value preset, then the state LCD display  

WARNING

 I HIGH

”,

and the buzzer warn. 

Standby input       

 

If set the aux input to a warning input, then if the signal at the input is valid, the LCD will display 

WARNING

EXT. ALARM

”,

and the buzzer warn. 

7.2

 

Stop Fault 

Note: “Stop fault” can lock the control system and stop the generator running. After the fault is 

eliminated, by  pressing the “reset” key unlocking the fault lock, then you can operate the controller again.

 

Fail to Start          

If the engine starting times over the preset value, the engine still does not run, namely it occurs “

Fail to 

Start

.” The LCD will display

ALARM

START  FAILURE

”,

 The indicator light 

Fail to Start  

illuminate, and the 

buzzer warns. 

Fail to Stop           

If the generator fail to stop after the stop delay timeout, then the buzzer warn and the LCD display 

ALARM

 STOP  FAILURE

”。

 

Emergency stop   

When the emergency stop input signal is valid, the controller stop all output of the relay except the alarm, 

the LCD display 

ALARM

E.STOP

”,“

EMERGENCY STOP

” indicator light illuminate, and the buzzer warn. 

Содержание GU320a

Страница 1: ...uction 2 2 Shape and connection 2 3 Operation panel 5 4 Installation 6 5 Control and operation 7 6 Measuring 9 7 Fault signal 10 8 Parameters configuration 11 9 LCD and menu system 13 10 Communication 15 11 Preparations 20 12 Troubleshooting 21 ...

Страница 2: ...d modify the running protection parameters The LED indicates the operating mode of the controller and the running state of the generator sets LCD display each measured parameter and state The controller is integrated closely by aluminum alloy panel and steel shell which has been spurt powder All connection of the controller are connected by pin like terminal with lock such device can be connected ...

Страница 3: ...no use 1mm line C13 Gen Set running output N O dry contact 3A 30VDC 1mm line C14 Fault alarm output N O dry contact 3A 30VDC 1mm line C15 Pre alarm output N O dry contact 3A 30VDC 1mm line C16 Idle output N O dry contact 3A 30VDC 1mm line D17 Pressure detection P sensor 1mm line D18 Temperature detection T sensor 1mm line D19 standby Measure 0 5Vdc 1mm line D20 Pressure signal Low potential valid ...

Страница 4: ...uel 起动 10 充电机 12 14 13 11 T sensor Pressure Temperature E stop Remote start P sensor 16 15 20 17 23 21 22 Speed sensor PICK UP 26 25 19 18 8 6 7 3 2 5 4 F2 F3 IDLE RUNNING 1 Generator F1 FAULT PRE ALARM RS CONNECTOR Standby 0 5Vdc 24 standby Note cathode of the battery and shell of the contoller must be grounded to earth properly ...

Страница 5: ...O key LED The key is used for auto operate mode Running in this mode the LED above the button will illuminate According to the remote control startup input signal the controller determines whether the generator startup or not MAN Key Indicator Light The key is used for manual operation mode Running in this mode the LED above the button will illuminate By pressing START and STOP key the controller ...

Страница 6: ...ault alarm occur press this key can mute the buzzer At the same time the light above the key illuminate Press it again will cancel mute If the controller still in fault the buzzer will keep alarm 4 Installation 4 1 Hatch size for panel installation as the figure attached Four special screws fix the controller If the shell of the controller is installed on the body of a generator directly or other ...

Страница 7: ...d control process Operation Description When the controller run in TEST or the remote control start signal able in Auto or press START in MAN the controller begin to delay the start procedure the light above the key will bicker The LCD display the count for start delay not in MAN START 00 09 Fuel relay action the fuel electromagnetic valve of the engine open After delay for 200 milliseconds the st...

Страница 8: ...NK 2 The phenomena above repeat again and again until the engine reach the normal running parameters While starting if any stop fault occurs the controller will stop controlling output instantly until the fault eliminated and reset then it can be operated again 5 4 Fail to start condition Operation Description When the phenomena above repeat again and again the starting attempts exceed preset the ...

Страница 9: ...s the same to the engine of normal closed oil electromagnetic valve 5 8 Idle and Hotstart function Select Idle or Hotstart according to the IDLE DELAY setting While set to above 0 the Idle delay is selected and set to 0 to release Idle delay and to select Hotstart function The operating principle is when Ready for Idle READY status the Idle relay open The controller runs the start procedure The st...

Страница 10: ... the buzzer warn Overspeed If the running speed of the engine over the preset alarm value the LCD will display WARNING OVER SPEED and the buzzer warn Underspeed If the running speed of the engine descend to alarm level preset then the state LCD display WARNING UNDER SPEED and the buzzer warn High voltage If the controller detects the output voltage of the generator over the alarm value preset the ...

Страница 11: ...after confirming the delay and the LCD display ALARM I HIGH the buzzer warn Standby Output If set the aux input to fault stop then when the signal at the input is valid the engine will stop instantaneously and the LCD display ALARM EXT ALARM the buzzer warn NOTE The data of low oil pressure pre alarm is from the measuring of the oil pressure sensor and the data of low pressure stop fault is from t...

Страница 12: ... 3 16 Stop delay 20s 0 60s 3 17 Under SP Alarm 0 RPM 0 9999 RPM 0 no setting 3 18 Under SP preALM 1440 RPM 0 9999 RPM 0 no setting 3 19 Over SP preALM 1600 RPM 0 9999 RPM 9999 no setting 3 20 Over SP Alarm 1710 RPM 0 9999 RPM 9999 no setting 3 21 Oil P low Alarm 140KPa 50 300Kpa 0 no setting 3 22 Oil P low preALM 220KPa 50 300Kpa 0 no setting 3 23 Coolant preALM 95 70 160 9999 no setting 3 24 Cool...

Страница 13: ...et and adjust the parameter When press the increase or decrease key for a while the ones digit changes one by one and then the tens digit change after ten changes the rest may be deduced by analogy Press in the main page two seconds to enter setting state then press and to look over in the menu of the same level and press to enter next submenu to select and adjust the item press to adjust When ind...

Страница 14: ...transformer the CT should be 200 Operation Description Press for two seconds to enter the configure menu and then the LCD display SETTING 参数设定 0 QUIT Press and key then press the LCD will display 1 CT 1000 Press and then press will indicate to enter the password 1 CT Password Press or to vary the parameters set to 200 at this time and the LCD then Indicate 1 CT 200 After the configuration press to...

Страница 15: ...e LCD display 6 Firmware update Press key will indicate you to enter password 3132 enter the password 6 Firmware update Password Then press to enter program mode You should make sure the power supply is normal in this mode The program will reset for use after correctly burn to record according to the program software or it won t exit and you should remove the working source Then the LCD display Fi...

Страница 16: ...ry more details please refer to the following wiring diagram The communication interface provides users a method to make the users fetch more information that cannot obtain from the panel The relative software can display the whole parameters measured and state information it also can set various parameters RS CONNECTOR G U320a C ontroller C I485A DB9 A S B RS485 Transform term inal RS CONNECTOR G...

Страница 17: ...m as below Note Communication cable use high quality twisted pair cable with shielded and its total length of cable less than 1000m Each anode and cathode of RS485 interface must be connected properly and the cable shield only can be connected to the earth at one side GU320a Controller DB9 RS CONNECTOR CI485A A B S Computer GU320a Controller RS CONNECTOR DB9 CI485A GU320a Controller RS CONNECTOR D...

Страница 18: ...7 1 L2 Current ph B phase current unit A 1008 1 L1 Current ph A phase current unit A 1009 1 L3 PF ph c PF 100A 1 L2 PF ph B PF 100B 1 L1 PF ph C PF 100C 1 Frequency Generator frequency unit 0 1HZ 100D 1 L3 VA Ph C real power unit KVA 100E 1 L2 VA Ph B real power unit KVA 100F 1 L1 VA Ph A real power unit KVA 1010 1 L3 W Ph C active power unit KW 1011 1 L2 W Ph B active power unit KW 1012 1 L1 W Ph...

Страница 19: ... Kwh 2014 2 KVArH unit KVArh 2016 1 VT 2018 1 Nominal speed unit RPM 2019 1 Pickup frequency unit RPM 201A 1 Fuel mode 201B 1 T sensor mode 201C 1 P sensor mode 201D 1 H sensor mode 201E 1 Start delay unit S 201F 1 Crank attempt 2020 1 Crank time unit S 2021 1 Crank reset unit S 2022 1 Crank disconnect unit RPM 2023 1 Idle delay unit S 2024 1 Safety on delay unit S 2025 1 Cooling delay unit S 2026...

Страница 20: ... OPEN 14 5 LOW OILPRESS 15 6 T SENSOR OPEN 16 I HIGH 7 COOLANT TEMP 17 8 START FAIL 18 9 STOP FAIL 19 11 Preparations 11 1 To confirm that the controller has installed and fixed properly and the installation ambient must accord with installation demand 11 2 To confirm the whole connecting of control lines accord to the electric norm and confirm to the typical connecting diagram of 1 3 Especially t...

Страница 21: ...ler is in ready state READY Press for two seconds to enter the configure menu then the LCD display SETTING 参数设定 0 QUIT Press three times and then press the LCD will display 3 ENGINE 0 QUIT Press three times again then the LCD display 3 ENGINE 3 Set pickup now With the engine running press after it is steady then the controller compared the rotating speed of the speed sensor with the voltage freque...

Страница 22: ...up the belt of fan to know about whether it is loosen 5 Checking up the outside temperature to confirm that it is in accord with the designing range of generator 6 Once the diesel cooling down you need to check up the cooling water level Remember that do not add a great deal of water into the cooling diesel If you do the diesel will suffer from serious destruction 7 Please refer to the Diesel Manu...

Страница 23: ...he load adding to the AC generator After the generator stop you need to eliminate the fault and reset the Genset again 2 Checking up the high voltage fault setting value of Main confirming that the data is right 3 Checking up the measuring voltage of controller if it is in normal mode please check up the load so as to confirm that whether it is non capacitive 4 If the voltage high you need to set ...

Отзывы: