2.4.2.4 Natural Ventilation Openings
to Enclosures for Flued Heaters
The table below provides specific data for
each heater model as -
Where the heater(s) is in an enclosure and
in flue only mode (ie without a positive
connection to atmosphere of combustion air
ductwork ) the minimum free area of
ventilation opening needs to be
•
At high level 5 cm
2
for each kW of
rated heat input.
•
At low level 10 cm
2
for each kW of
rated heat input.
The high level ventilation opening should be
sited on an external wall and positioned as
high as is practical and always within the top
15% of the wall height
The low level natural ventilation opening
should be situated on an external wall and
be within 1000 mm of floor level for natural
gas and ideally at floor level for l.p.g gas
installations but in any event no higher than
250 mm.
2.4.2.5 Mechanical Ventilation to a
Plant Room or Enclosure
The table below provides specific data for
each heater model as -
In the event that the installer prefers to
mechanically ventilate the plant room or
enclosure rather than provide ventilation
openings then -
•
The plant room or enclosure needs to
be mechanically ventilated at the rate
of 4.14 m
3
/h of fresh air per kW or
rated heat input.
•
It is a requirement that the mechanical
ventilation shall be of the ’input’ type
with either natural or mechanical
extraction. Where mechanical
extraction is selected then the
extraction rate should be 5%-10% less
than the input rate.
•
Systems of mechanical extraction with
a natural inlet shall not be used
•
It is necessary to provide an automatic
means to safely inhibit heater(s)
operation should mechanical air
supply fail for any reason.
MODEL
Minimum Free Area Of
Ventilation Opening
High Level
Low Level
cm
2
cm
2
72
394
394
95
527
527
120
656
656
145
787
787
MODEL
Minimum Free Area Of
Ventilation Opening
High Level
Low Level
cm
2
cm
2
72
394
788
95
527
1053
120
656
1312
145
787
1574
Содержание HT2000
Страница 2: ...2...
Страница 31: ...31 T T WARNING NEUTRAL RESET 6 0 Wiring Diagram 33 67 162 VRBD 72 95 Auto ignition On Off SEQUENCE CONTROLLER...
Страница 33: ...33 T T WARNING NEUTRAL RESET Wiring Diagram 33 67 566 VRBD 72 95 Auto ignition Hi Low SEQUENCE CONTROLLER...
Страница 34: ...34 T T WARNING NEUTRAL RESET Wiring Diagram 33 67 579 VRBD 120 145 Auto ignition Hi Low SEQUENCE CONTROLLER...
Страница 35: ...35 T T WARNING NEUTRAL RESET Wiring Diagram 33 67 567 VRBD 72 95 Auto Ignition Modulation SEQUENCE CONTROLLER...
Страница 36: ...36 T T WARNING NEUTRAL RESET Wiring Diagram 33 67 582 VRBD 120 145 Auto ignition Modulation SEQUENCE CONTROLLER...
Страница 47: ...47 Motes...