Constellation™
2002 June 20
4-4
Circuit Breakers
The values in
are for the Constellation
terminal radio only.
Grounding Recommendations
Grounding in accordance with the R56 installation standard is necessary for
proper operation of the equipment as well as protection of the personnel and
equipment.
•
Connect the ground between the radio rack and halo, or ground window
of the site.
•
Do not connect the ground through any other radio or rack.
•
Do not daisy chain the grounds. A surge through a daisy chain ground
will go through all the radios.
•
The return bus bar should be grounded using 6-AWG wire as a
minimum.
Some operators require the same gauge wire for the return buss bar and the
battery cables. This may help avoid DC power surges when the on-site
generator switches between on or off.
Table 4-3: Recommended circuit breaker sizes for
Constellation radio terminal only
6, 7/8 GHz
10/11 GHz
Configuration
24 V
48 V
24 V
48 V
Fully protected
25 A
15 A
30 A
15 A
Содержание Constellation
Страница 1: ...Point to Point Digital Radio Constellation Installation Maintenance next level solutions ...
Страница 2: ......
Страница 3: ...Constellation Microwave Radio INSTALLATION AND MAINTENANCE MANUAL June 20 2002 IMN 112871 E07 ...
Страница 16: ...Constellation 2002 June 20 TOC 12 ...
Страница 20: ...Constellation 2002 June 20 2 ...
Страница 76: ...Constellation 2002 June 20 4 34 ...
Страница 100: ...Constellation 2002 June 20 6 12 NETWORK MANAGEMENT For NEWORK MANGEMENT configuration refer to Chapter 8 ...
Страница 136: ...Constellation 2002 June 20 10 12 ...
Страница 150: ...Constellation 2002 June 20 11 14 ...
Страница 186: ...Constellation 2002 June 20 12 36 ...
Страница 210: ...Constellation 2002 June 20 A 16 ...
Страница 236: ...Constellation 2002 June 10 F 2 ...
Страница 240: ......
Страница 242: ......
Страница 248: ...Constellation 2002 June 20 G 6 ...
Страница 262: ...Constellation 2002 June 20 I 14 ...
Страница 263: ......