13
P61A Pellet Stove
3-90-05822R29_10/13
#8 installing through the ceiling
Through the ceiling vent, follow PL vent manufacturers
recommendations when using wall and ceiling pass through.
note:
do not place joints within wall pass-throughs.
Fig. 14
PL vent manufacturer's
firestop spacer and support
(See Page 7 for
corner installation
clearances)
Minimum flue vent configuration
It is recommended that outside
air be installed with this venting
configuration to reduce smoke
and creosote smell in the room in
the event of power failure.
Min. above ground level
12"
Storm collar
Flashing
1" min.
1" min.
12" min.
1" min.
venting
Fig. 15
1" min.
No insulation or
other combustible
materials are
allowed within
1" of the pellet
vent pipe. Unless
specified by the
pipe manufacturer
Fig. 16