PRIMARY AIR ADJUSTER
Your FireLuxe gas stove was shipped from the factory
equipped for the fuel type indicated on the rating
plate that is attached to the rear of the stove and the
primary burner air adjuster was set at the factory at the
recommended position for that fuel. If you will be using
the alternate fuel please see the instructions included
with the optional fuel conversion kit. This includes
instructions for the proper setting for the primary air
adjuster.
The recommended setting for propane is the fully-open
position. This corresponds to the adjuster screw fully
backed out. The recommended setting for natural gas
is the fully-closed position. This corresponds to the
adjuster screw fully screwed in.
Making small adjustments to the primary air setting will
let you adjust the way the flames look for your particular
installation. See the reference to primary air adjustment
in the section below that discusses the air inlet and
exhaust outlet restrictors.
AIR INLET AND EXHAUST OUTLET RESTRICTORS
The FireLuxe is equipped with externally adjustable restrictors for both the inlet air and the exhaust outlet.
This makes it possible to fine tune the direct vent system for the specific conditions of your installation.
The recommended settings are keyed to the specific details of your venting configuration.
To access the restrictor adjustment guide plates, you must first remove the access plate. Looking at the
stove from the front, this plate is located on the upper left rear of the stove. If you have the optional blower,
the access plate also contains the blower speed control. Remove the single fastener that secures the
access plate. Set the plate aside (or if the blower is installed, let the plate hang on the wiring). Next remove
the heat shield. This is held in place with a single fastener located at the lower front corner of the shield. With
the fastener removed, tilt the heat shield as needed and remove. Refer to the illustrations below.