background image

R1

SAFETY NOTICE

PlEASE rEAd ThIS ENTIrE mANuAl bEFOrE YOu INSTAll ANd uSE YOur NEw rOOm hEATEr.  FAIlurE 

TO FOllOw INSTruCTIONS mAY rESulT IN PrOPErTY dAmAgE, bOdIlY INjurY, Or EvEN dEATh.
FOr uSE IN ThE u.S. ANd CANAdA.  SuITAblE FOr INSTAllATION IN mObIlE hOmES
IF ThIS hArmAN STOvE IS NOT PrOPErlY INSTAllEd, A hOuSE FIrE mAY rESulT.  FOr YOur SAFETY, 

FOllOw INSTAllATION dIrECTIONS.  
CONTACT lOCAl buIldINg Or FIrE OFFICIAlS AbOuT rESTrICTIONS ANd INSTAllATION INSPECTION 

rEQuIrEmENTS IN YOur ArEA.
CONTACT YOur lOCAl AuThOrITY (SuCh AS muNICIPAl buIldINg dEPArTmENT, FIrE dEPArTmENT, FIrE 

PrEvENTION burEAu, ETC.) TO dETErmINE ThE NEEd FOr A PErmIT.
CETTE guIdE d'uTIlISATION EST dISPONIblE EN FrANCAIS. ChEz vOTrE CONCESSIONNAIrE dE hArmAN 

hOmE hEATINg.

SAvE ThESE INSTruCTIONS.

The harman dvC-500 Coal Stoker

Installation & Operating manual

r13

Содержание DVC-500

Страница 1: ...FIRE MAY RESULT FOR YOUR SAFETY FOLLOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your localautho...

Страница 2: ...This appliance is also approved for installation into a shop...

Страница 3: ...Sensors 27 Parts 28 Specifications 29 Troubleshooting 30 Please read this entire manual before you install and use your new room heater Failure to follow instructions may result in property damage bod...

Страница 4: ...ndcorrosionanditistotally the operator s fault Usually after the coal dries for three or four days depending on conditions it will flow very well and feed properly Feed rate will be the same as with d...

Страница 5: ...g The DVC 500 is the most advanced coal stove ever put into production However there are places where it should not be installed If the end of the flue pipe is 1 Less than 8 feet from an air intake 2...

Страница 6: ...as shown at left 2 Install 3 firebricks on the cast iron angle behind the grate as shown 3 Cement in grates as shown below This may already be done at the factory 4 Install the front door and latch it...

Страница 7: ...pplied Paw Bolt The paw bolt should be turned into the door from the inside approximately 14 turns With the set screw removed turn the brass elbow onto the paw bolt approximately 5 turns or until a 1...

Страница 8: ...Cut at least a 9 x 9 hole through the wall 3 Remove the side doors rear cover assembly 6 black screws 5 16 socket or straight screw driver 4 Place the unit in front of the hole approximately 1 2 close...

Страница 9: ...pipe Using the black pop rivets fasten together then slide it against the wall and fasten it to the wall 10 Replace the side door rear cover assembly with 6 black screws 11 Complete the unit assembly...

Страница 10: ...10 Installation...

Страница 11: ...o Page 14 for all of the sec tions available Never use venting other than Harman DVC venting inside the building It is the only vent certified for this appliance Refer to page 12 14 to calculate which...

Страница 12: ...12 Installation...

Страница 13: ...13 Installation...

Страница 14: ...ickness up to 16 inches Exterior Termination for wall thickness up to 12 inches 3 44 06256 1 10 08313 1 10 08314 1 10 08321 1 10 08317 1 10 08315 1 10 08316 1 10 08320 1 10 08319 1 10 08318 1 10 08322...

Страница 15: ...not installed If a Room Sensing Probe is then installed the status light will automatically reset 5 Blinks Indicates a lack of communication between the circuit board and the TCP Temperature Control P...

Страница 16: ...16 ESP Control Hopper Lid Latch Ash Door Latch Handle Glass Door Latch Handle Side Panel Latch...

Страница 17: ...emp Dial to the desired setting 8 Light the fire and make sure that all doors and the hopper lid are closed As the ESP senses the correct temperature the Feed Motor will start Shutdown Procedure To ki...

Страница 18: ...n RoomTempMode heatoutputiscontrolled automatically by use of the Room Sensing Probe When the Room Sensing Probe calls for heat the stove will increase output When the Room Sens ing Probe is getting c...

Страница 19: ...ter is left in the Ash Out position the fire will burn out DAILY MAINTENANCE Ash Removal Witheachhopperofcoalthatisburned approxi mately one ashpan full of ashes must be removed fig 19 It may take fro...

Страница 20: ...eDraftMotor Now the viewing door can be opened with minimal exhaust leakage Use a safety razor in handle and scrape the inside of the glass with the blade almost flat to the surface Fig 21 The window...

Страница 21: ...and Exhaust Outlet fig 25 4 The blower wheel blower housing and exhaust outlet can now be cleaned with a brush and vac uum cleaner NOTE The ESP probe is located at the rear of the exhaust outlet show...

Страница 22: ...pipe over the summer to block out rodents and birds Place a note inside the unit to remind yourself or others not to forget to uncover the flue pipe before lighting a fire Prevent Rust Summertime moi...

Страница 23: ...ture rises too much This prevents the fire from reaching the coal in the hopper RedAsh Coal may form klinkers fused together ash which may cause grate blockage in severe cases Anthracite Coal can be p...

Страница 24: ...ar end will be locked in place by the flange Before tightening the bolt be sure the grate holder is back as far as possible and centered side to side on the feeder opening Install grate inserts as sho...

Страница 25: ...25 Maintenance Schedule It is recommended that End of Season Cleaning and the Annual Service are coordinated to happen at the same time for best results...

Страница 26: ...26 Wiring Diagram...

Страница 27: ...Room Sensor works with the ESP and the Control to provide the right size fire FSS The FSS Firebox Static Switch is an electronic pressure switch that senses firebox pressure The FSS works with the ESP...

Страница 28: ...13 1 10 08208 pusher assembly 1 14 3 31 06238 pillow block bearing 1 15 3 30 437161252 carriage bolt 2 16 2 00 06239 bearing spacer 1 17 3 20 60906 feed motor 1 18 3 30 1252007514 grade 8 1 4x20 1 19...

Страница 29: ...ange 7000 to 75 000 Heating Capacity 2200 Square Feet Fuel Anthracite Rice Coal Hopper Capacity 93 Pounds Distribution Blower Size 135 cfm Flue 4 Harman DVC Vent Wattage 295 Watts Control ESP with Mic...

Страница 30: ...ig 26 7 Grate inserts are extremely loose or out of align ment fig 30 8 Coal ash building up behind the ash pan to a point where the ash door is sprung and not seating when latched 9 Transparenttubing...

Страница 31: ...cool down period After five minutes the unit will restart at a reduced feed rate 30 seconds max for 72 minutes After 72 minutes if the safety switch has not sensed another pressure loss the unit will...

Страница 32: ...32...

Страница 33: ...33...

Страница 34: ...34 Service Maintenance Log Date Of Service Performed By Description Of Service...

Страница 35: ...35 Service Maintenance Log Date Of Service Performed By Description Of Service...

Страница 36: ......

Отзывы: