Installation

Only For Qualified Installers

Making The Connection

The gas inlet is located on the bottom right side 

of the fireplace. The inlet fitting is 1/2” male flare fitting 

designed for 1/2” stainless flex pipe. This fitting can be 

removed to provide 3/8” female pipe thread.

A  separate  gas  shut-off  valve  and  a  1/8”  N.P.T. 

plugged  tapping  should  be  installed  immediately  up-

stream of the connection to the appliance.

The ShadowLight XL Direct Vent Gas Heater must 

be disconnected from the gas supply piping during any 

pressure testing of that system at pressures in excess 

of 1/2 psig (3.5 kPa).

The  ShadowLight  XL  gas  control  valve  must  be 

in the OFF position during any pressure testing of the 

gas supply system at pressures equal to or less than 

1/2 psig (3.5 kPa).

WARNING: To avoid pipe compounds from enter-

ing into the gas train, apply compounds only to male 

pipe  threads  and  do  not  apply  compound  to  the  first 

two threads.

CAUTION: TEST ALL JOINTS FOR LEAKS BE-

FORE OPERATING.

 

Gas Pressure Requirements:

Correct  gas  pressure  and  the  use  of  a  properly 

sized gas supply line are essential for the safe and ef-

ficient performance of this appliance. Make sure that 

the plumber or gas supplier checks the gas supply line 

and gas pressure at installation.

 NOTE: Improper gas pressure can affect heater 

performance, flame color, or cause pilot outage.

Natural Gas:

 

Maximum inlet pressure 7.0” w.c. (1.74 kPa)   

Minimum inlet pressure 5.0” w.c. (1.25 kPa)  

Gas manifold pressure 3.5” w.c. (0.87 kPa)

LP Gas:

 

Maximum inlet pressure 13” w.c. (3.24 kPa)   

Minimum inlet pressure 11” w.c. (2.74 kPa)  

Gas manifold pressure 10” w.c. (2.49 kPa)

DO NOT USE THIS HEATER IF ANY PART HAS 

BEEN  UNDER  WATER,  EXPOSED  TO  MOISTURE, 

OR SHOWS SIGNS OF CORROSION. IMMEDIATELY 

CALL A QUALlFlED SERVICE TECHNICIAN TO IN-

SPECT THE HEATER AND REPLACE ANY PART OF 

THE CONTROL SYSTEM AND ANY GAS CONTROL 

WHICH HAS BEEN UNDER WATER.

Gas Line

CONNECTING THE SHADOWLIGHT XL 

FIREPLACE INSERT TO A GAS SUPPLY

Test Class 

Note:  Stove  is  built  for  propane. A  conversion 

must be done to accomodate natural gas.

Do  not  connect  the  venting  to  the  flue  of  a 

chimney  that  serves  a  separate  solid-fuel 

burning appliance.

13

Содержание XL

Страница 1: ...ne respect pas la lettre les instructions dans le pr sent manuel risque de d clencher un incendie ou une explosion entra ant des dommages mat rials des l sions corporelles ou la perte de vies humaine...

Страница 2: ...oisinage de cet appareil ou de tout autre appareil In the Commonwealth of Massachusetts this product must be installed by a licensed Massachusetts Plumber or Gas Fitter IMPORTANT The Shadowlight XL is...

Страница 3: ...3 Converting to Natural Gas 15 Converting to High Altitude 17 Venting 18 Installing into a Fireplace 20 Options 24 MAINTENANCE 25 Removing the Glass 25 Replacing the Gasket 25 Cleaning the Glass 25 Cl...

Страница 4: ...plied by the manufacturer shall be used to convert this room heater to the alternate fuel Pour utilisation avec le gaz naturel et le propane Une trousse de conversion fournie par le fabricant doit etr...

Страница 5: ...Speci cations 40 30 Front View Minimum Opening Size 29 Inlet Outlet Top View Side View Front View 14 13 5...

Страница 6: ...Low Knob On Off Pilot Knob Igniter Blower Speed Switch On Off Thermostat Switch Pilot Glass Door Latch Handle Leveling Bolt Leveling Bolt Burner Plate Burner Lighting Instructions Safety Label Face B...

Страница 7: ...Btu hr 2000 4500ft 610 1375m 34 000 BTU 34 500 BTU Min Input Rating Btu hr 21 600 BTU 20 900 BTU Ori ces DMS 0 2000 ft 0 610m 31 50 Ori ces DMS 2000 4500ft 610 1375m 33 51 Manifold Pressure in w c kP...

Страница 8: ...he Handles Lift bottom grill with index nger and fold down to access controls ON OFF THERMOSTAT Switch UP ON MIDDLE OFF DOWN THERMOSTAT ON OFF THERMOSTAT Pilot Location Shown Above Pull lighting instr...

Страница 9: ...al times before the pilot ignites Continue to hold the control knob in for about one 1 minute after the pilot is lit Release the knob and it will pop back up Pilot should remain lit If it goes out rep...

Страница 10: ...R SHUTTER ADJUSTMENT The adjuster can be accessed with a phillips screw driver just above the valve Turn the adjuster clockwise to increase ame height and counterclockwise to de crease See above left...

Страница 11: ...ly For Quali ed Installers Packing List Inside the Insert Box ShadowLight XL Insert Log set Bag of rock wool Owners Manual Restrictor Plates Inside Face Box ShadowLight XL Face Right Door Left Door Ha...

Страница 12: ...near the ShadowLight XL Surveiller les enfants Garder les v tements les meubles l essence ou autres liquides vapeur in ammables lin de l appareil CLEARANCES The following clearances to combustibles mu...

Страница 13: ...ING Gas Pressure Requirements Correct gas pressure and the use of a properly sized gas supply line are essential for the safe and ef cient performance of this appliance Make sure that the plumber or g...

Страница 14: ...ence quali ee de service conformement aux instruc tions du fabricant et toutes exigencies et codes appli cables de l autorises avoir la jurisdiction Si l information dans cette Instruction n est pas s...

Страница 15: ...Using one hand gently push the side brick relief door open slightly and using the other pull the top of the rear brick panel forward and remove it Remove the screws mounting the intake air de ector an...

Страница 16: ...r box on the fuel label with a permanent marker Note If no conversion is made the box for propane must still be marked 7 Safety Label Use soap and water and or a gas detector to check for leaks before...

Страница 17: ...the rear brick panel Using one hand gently push the side brick relief door open slightly and using the other pull the top of the rear brick panel forward and remove it Remove the screws mounting the i...

Страница 18: ...proved Venting Observe local codes when venting the ShadowLight XL If no local codes exist follow ANSI Z21 88 2002 installation code Do not connect the venting to the ue of a chimney that serves a sep...

Страница 19: ...ns exactly The Simpson Duravent venting components listed below are approved for use with the ShadowLight XL Direct Vent Gas Insert Flashing Chimney Liner Termination Kit Includes ashing Stock 923GK H...

Страница 20: ...ag of rock wool packaging materials and log set from inside the rebox Skip steps 3 thru 5 if intake exhaust adapter does not need removed for installation Feed chimney liners down the chimney and thro...

Страница 21: ...side stove while it is installed you may want to remove the gas line from the valve assembly and connect it to your supply line inside the replace rst then reconnect to the gas valve Set stove into re...

Страница 22: ...he notches on the left side of the stove body and secure the cord to the front bottom section of the stove using wire ties 11 12 Back out the 4 face clamping bolts far enough to install the face Slide...

Страница 23: ...mponents that were removed if the pipe adapter was removed from the stove body 10 Connect Gas line to the unit Check for leaks using an approved method 11 Change power cord to opposite side of unit if...

Страница 24: ...ver time When properly installed and maintained a millivolt control system should give many years of trouble free service It is important to use the proper gauge wire for the length used RECOMMENDED W...

Страница 25: ...ppointment They must have no blockage and be in good condition The vent manufacturer s instructions may provide speci c suggestions or details on vent inspection Any sections that are taken apart for...

Страница 26: ...ower motor 11 Remove screws mounting blower to blower mount 12 Replace blower 13 Assemble in reverse order Air Flow To prevent damage to the heater it is essential that air ows freely into the bottom...

Страница 27: ...MAGENTA MAGENTA MAGENTA MAGENT A Wiring Diagrams High Voltage DIagram Low Voltage DIagram Blower Power Cord Variable Speed Switch Blower Switch External Thermostat Remote Terminals 27...

Страница 28: ...ors 2 00 384321 2 2 00 384323 1 75 13 Tail pipe Gasket 3 44 384328 14 J Bolt 15 Flue Clamp Weldment 1 10 384343 16 Body Weldment 1 89 384300 17 Flue Access Cover 2 00 384307 18 AIr Plate Assembly 1 10...

Страница 29: ...3 30 1252005014 8 5 12 x 18 x 6 Pan Headbolt 3 30 631186001 9 5 16 x 18 nuts 3 30 80311813 10 Adjuster Disc 2 00 384142 11 Gas Tube 2 00 384128 12 Control Valve 3 40 820653 13 Burner Floor 2 00 38432...

Страница 30: ...Adjuster Pilot Adjuster If pressures are not according to specification contact your Authorized Harman Dealer If pressures are not according to specification contact your Authorized Harman Dealer To c...

Страница 31: ...Yes No Bad OK OK Bad No Yes Turn on gas valve Is gas turned on Yes OK Purge gas line to stove No Replenish supply Bad OK Replace Piezo Igniter Check Piezo Igniter to make sure the small wire on the m...

Страница 32: ...output of thermocouple Should be 10 or more MV Check inlet pressure Bad Adjust pilot adjustment to achieve proper ame Replace Thermocouple Bad Replace Valve Pilot does not stay lit Check size of pilo...

Страница 33: ...lit no Light pilot Yes Check Thermopile voltage at terminals marked TP on valve Should be approximately 200 mv with switch on and approximately 400 mv with switch off too low Replace Thermopile Check...

Страница 34: ...t covered Damage and or repairs including but not limited to remote controls lters fuses knobs glass ceramic brick panels ceramic ber afterburners door packing tile ceramic log sets paint batteries or...

Отзывы: