background image

Exception TL200 W ood Stove

17

The Harman Exception may be installed with a

minimum  of  (150  mm)  24  gauge  chimney  connector
pipe.  Size of the connector should correspond to the
size  of the  flue collar  opening.  Do  not use makeshift
compromises. No part of the chimney connector may pass
through an attic or roof space, closet or other concealed
space, or through a floor or ceiling.  Whenever possible,
avoid passing the connector through a combustible wall; if
you must, use an approved wall pass-through, described
later in this section.

Assemble the connector beginning at the flue col-

lar, with the crimped ends pointing towards the stove (to
keep debris and creosote flakes inside the system).  Each

joint, including the one to the stove’s flue collar and the

one to the chimney itself should be secured with at least
three sheet metal screws.  Screws may be a maximum of
3 inches apart.  A 1-1/4" (30 mm) overlap is required at
each joint, including the flue collar attachment.  No more
than two 90 degree elbows should be used, and the total
length of connector should not exceed 10 feet (3 m).  All
horizontal  runs of  connector must  have  a minimum  up-
ward slope of 1/4"(6 mm) per foot (20 mm per meter).

Wall Pass-throughs

Occasionally it is necessary to pass the chimney

connector through a combustible wall to reach the chim-
ney.  Depending on your local building codes, and the per-
tinent provincial or national codes, there are several choices
for accomplishing this safely.  Before beginning your in-
stallation, contact local officials, and also the chimney con-
nector and chimney manufacturer for specific requirements.

Canada.  

Three methods are approved by the Cana-

dian Standards Association.  The diagram shows one method
requiring an 18"(450 mm) air space between the connector
and the wall.  It allows use of one or two covers as described
in the diagram.  The two  other methods are described in
detail in the current issue of CAN/CSA B365, the national
standard.

United States 

 In the U.S., the national code is NFPA

211.  While many localities adopt this standard, be sure to
check with local authorities before beginning your installa-
tion.

The NFPA (National Fire Protection Association) per-

mits four methods for passing through a combustible wall.  A
commonly used method to pass through a wall directly to a
masonry chimney is to clear a minimum 12"(300 mm) around
the entire chimney connector, and fill it with brick masonry
which is at least 3.5"(90 mm) thick.  A fireclay liner, mini-
mum 3/8" (9 mm) wall thickness must run through the brick
wall to the chimney liner (but not beyond the inner surface of
the liner).  It must be cemented in place with refractory ce-
ment.  This method is illustrated.  For details on the other
three options, refer to the most recent edition of the NFPA
211 code.

Venting

Chimney  Connectors and  Chimneys

Draft

Draft is widely misunderstood.  It is important that

you, the stove operator, realize that draft is a variable 

ef-

fect

, not a  given quantity. Stoves and  chimneys do not

have

 draft, yet draft is the key to your stove’s performance.

Draft is a 

force

, produced by an operating stove

and the chimney to which it is attached.  It is created by
hot gases rising up the chimney, creating a pressure dif-
ference between the inside of your home and the outside
air.  It continually moves fresh combustion air into the stove,
and hot exhaust gases out of the stove; without this con-
stant flow, the fire will go out.

Other factors, such as barometric pressure, winds,

the air tightness  of the home, the total  inside chim-
ney volume, chimney height and the presence of vent-
ing devices such as exhaust fans also play a role in
maintaining an adequate draft.  Low barometric pres-
sures, super insulated homes and exhaust fans can
reduce draft;  winds can play havoc wi th draft; and
too large or too small a chimney volume can cause
reduced  draft   due  to the  excessive  co oling  or  not
e no u gh  r o o m  t o   v e n t   e xha us t   ga s e s   qui c kly.
Introducing outside air  directly to the stove may help
remedy a low draft prblem.  Some signs of inadequate
draft are smoking, odor, difficulty in maintaining the
fire, and low heat output.   Overdraft can be caused
by a very tall chimney even if it is the recommended
size, and can cause overfiring of your stove.  Signs
of an overdraft include rapid fuel consumption, inabil-
ity to slow the fire, and parts of the stove or chimney
connector  glowing red.  It is important that  you fol-
low the chimney guidelines in this manual, including
size, type, and height to avoid draft problems.

Other causes of poor ventilation or draft are icing,

exhaust  fans, a  blocked  outside air  inlet,  and room  air
starvation.  If your stove is sluggish and you get occa-
sional odor, check these possibilities and increase the air
flow in your home.

When installed and operated according to this

manual, the Exception will produce enough hot gases to
keep the chimney warm so that adequate draft is
maintained throughout the burn cycle.

Chimney  Connectors

In general, following these guidelines will en-

sure compliance with all national and provincial codes;
prior to beginning your installation, check with your lo-
cal building code official to  check  on additional  local
regulations which may influence the design and place-
ment of your venting system.

Содержание TL200

Страница 1: ...ALLED AHOUSEFIREMAYRESULT FORYOURSAFETY FOLLOW INSTALLATIONDIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATIONINSPECTION REQUIREMENTS INYOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILDING DEPARTMENT FIRE DEPARTMENT FIRE PREVENTION BUREAU ETC TO DETERMINE THENEED FORA PERMIT CETTEGUIDE D UTILISATIONEST DISPONIBLEENFRANCAIS CHEZ VOTRECONCESSIONNAIRE DE...

Страница 2: ... temperatures The Harman Exception was designed to make burning wood easier by adding a top load door which allows more wood to fit into the large firebox The Exception s smoke free designdraws smoke down throughthe stove not into your room The top load door also comes in handy when cooking on the optional cooking grill Simply place the grill in the top load opening and grill great tasting meats a...

Страница 3: ...ght 440 lbs Flue Size 6 inch Log Length Recommended 18 with 20 Max Heating Capacity 1500 to 2800 sq ft Average Emissions 4 4 Grams Per Hr Emissions on Low 2 25 Grams Per Hr Blower Size optional 105 cfm variable speed Outside Air size 3 inch 3 5 3 75 ...

Страница 4: ...xception TL200 Wood Stove 4 Andirons Grates Top Load Opening FrontLoad Door Combination Top Load Doorand Damper Arm Ash Door Ash Door Latch Front Load Door Latch Side Shield Specifications Top Load Door ...

Страница 5: ...larattention to the explanation of draft and its effect on stove performance in the venting section By following the installation and operating guidelines you will ensure proper draft and gain maximumefficiency and en joyment fromyour stove Fuel Your Exceptionburns wood very efficiently Here are some guidelines concerning firewood that willhelp you obtain the best performance Select hardwoods if p...

Страница 6: ... or more of these stages are generally occur ring at once Operation Controls Two important controls the top loading door handle and the air controllever regulate the operationand output of the stove Top loading door handle damperinterlock The top loading door handle is linked to the bypass damper and serves two purposes Move the handle forward one position approximately 3 and the handle automatica...

Страница 7: ...arcoal bed 2 3 50 mm 80 mm is formed close the bypass damper by pushing the top loading handle all the way back until it locks closed You may needto leave the load door open a crack to get the blaze going properly but neverleave the stove unattended withdoor open Addmore woodto cre ate a deeper charcoal base 3 4 or 80 mm 100 mm thick remember to open the bypass damper if you are loading fromthe fr...

Страница 8: ... following guidelines for air settings can be used for woodburning as you become familiar with your stove you will know which settings best heat your home Minimum burn rate air control fully to left Medium low burn rate air control moved 1 to right High burn rate air control fully to the right Note At minimum burn rates the glass may get dirty but will clean off again at higher burn rates Afterbur...

Страница 9: ...Reinstall door on stove Glass Cleaning Sometimes it will be necessary to clean ac cumulated ash from the glass surface allowing this ash to remain on the glass for long periods can result in etching due to the acidity of the ash Thecreosote whichaccumulates onthe glass should burn off during yourhot fires Never clean the glass while it is hot and do not use abrasive substances Wash the surface wit...

Страница 10: ... your chimney system and have it repairedif necessary Gaskets Gaskets are used at strategic positions when build ing the Harman Exception for controlling the path that in coming andoutgoing airand gases take throughthe stove You must check these gaskets from time to time and replace themwhen necessary The gaskets are made of fiberglass of different sizes obtainable fromHarman Stove Company and are...

Страница 11: ...tion by certain localbuilding codes Checkwith your local building inspector to find out requirements Some signs to watch for that indicate a possible need for outside air poor performance of other heaters or of the Exception including smoke roll out and odor the disappearance of the same symptoms when a window is opened near the stove and condensation on windows in the winter Mod ern homes with ti...

Страница 12: ...ed here Parallel versus Corner Installations A parallel installation is one in which the back and sides of the stove are parallel to the walls behind and to the side of the stove A corner installation is one in which the back of the stove is positioneddiagonally across a corner of the room Each installation requires its own set of clearances For parallel installations the required clearance distan...

Страница 13: ...WOOD HANDLE SET SCREW 4 GLASS RETAINER CLIPS 4 GLASS RETAINER BOLTS GLASS GLASS GASKET DOOR HINGE PINS PAW BOLT The paw bolt should be turned into the door from the inside approximately 14 turns Withthe set screw removed turn the brass elbowonto the paw bolt approximately 5 turns or until a 1 16 clearance is achieved between the elbow and the door face make sure to stop on the flat spot of the paw...

Страница 14: ...sy Lift up on the side shield then pull out Drive ArmAssembly Heavy Washer 1 4 x 20 x 1 2 Bolt Figure 2 With left hand slide new drive armthrough hole in side of stove With right hand take 1 4 x 20 grade 8 bolt along with washer and insert through hole from inside of stove Tighten snugly using a 7 16 wrench Shown in Fig 2 Step 2 Install the drive arm slots for side shield tabs Before side shield i...

Страница 15: ...e lift lug Fig 7 can get bent Check to see that it is 90o fromthe lid If adjustment is necessary the lugcan be straightened witha large adjustable wrench slots for side shield tabs Before side shield is in place Side Shield After side shield is in place Figure 4 Step 3 Install the top lift arm Tighten the 1 4 20 x 5 8 button head allen bolt Bolt into the tab on the underside of the top lid This bo...

Страница 16: ...on TL200 Wood Stove 16 Exception Linkage Installation cont d Figure 7 Top Lift Arm Lift Lug 1 4 x 20 Self Locking Nut 1 4 x 20 Button head Allenbolt Drive Arm Assembly Outside Damper Arm Pivot Arm Shoulder Pin ...

Страница 17: ... the chimney liner but not beyondthe innersurface of the liner It must be cemented in place with refractory ce ment This method is illustrated For details on the other three options refer to the most recent edition of the NFPA 211 code Venting Chimney Connectors and Chimneys Draft Draft is widely misunderstood It is important that you the stove operator realize that draft is a variable ef fect not...

Страница 18: ...r non mobile home installations a round flue either masonry or approved prefabricated of either6 150 mm 7 180 mm or 8 200 mm may be used For square or rectangular masonry chimneys nominal sizes of 8 x 8 or 8 x 12 200 mm x 200 mm 200 mm x 300 mm may be used Codes require that solid fuel chimneys extend 3 ft 0 9 m above the point at which they exit from the roof provided that no part of any structur...

Страница 19: ... at least 2 50 mm into the room so the connector can be attached with sheetmetal screws Venting to a Masonry Fireplace Chimney In some situations a code compliant chimney originally used for a masonry fireplace may be used to install your Exception In additionto the requirements found inthe previous paragraphs it is important to be aware that all clearances must be met including those fromthe chim...

Страница 20: ...uidelines in the Installation section when installing your Harman Exception in your mobile home Other important Mobile Home guidelines The stove must be securely attached to the mobile home floor All stoves installed in mobile homes must have a direct outside air connection See Assembly Instructions Avapor barrier must be in place where the approved chimney system exits the mobile home Caution The...

Страница 21: ...7 Damper weldment 20 1 10 08057 Damper frame assy 21 1 10 08059 Right side plate assy 22 1 10 08200 Afterburner hood weldment 23 1 10 08111 Ramp assy 24 3 40 05174 IR glass 25 3 44 11862 1 4 OD rope 60 not shown 26 3 44 53500 1 2 door rope 66 per not shown 27 4 00 05165 Cast door machined 28 2 00 05202 Glass retainer clips 4 per 29 3 00 05165 4 Gold plated cast door optional same as 27 30 2 00 052...

Страница 22: ...Exception TL200 Wood Stove 22 1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 18 19 20 21 22 23 24 27 28 30 31 32 33 34 35 36 37 38 39 40 41 Exception TL200 Parts ...

Страница 23: ...ONS Failure due but not limited to fire lightning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filters fuses knobs glass ceramic brick panels ceramic fiber afterburners door packing tile ceramic log sets paint batteries or battery back up and related duct work are not covered Also exc...

Отзывы: