HANYOUNGNUX TPR-2SL Скачать руководство пользователя страница 2

3

4

 

 

Signal and 

alarm terminals

LED display

Overcurrent 

setting volume
Soft start or 

UP/DOWN setting volume

Output limit volume

Internal dip switch

Input signal and 

power terminal (control unit)

Load terminal

LOAD

Fast acting fuse

Noise filter

100 - 240 V a.c

Time delay

fuse

R U

▒ Recommended connection diagram

· In case of low voltage model, we suggest connect it as following picture. (90/110/130A have fuse).
· If the product is used in a place where there is an excessive amount of noise from power then make sure to use 
    a noise filter satisfied its specification as shown in the picture below. If not, it can be a cause of malfunction.

· When the voltage is used higher than 380 V AC, please make sure that the input power for the control unit is 
   separately connected to 100 - 240 V AC.
· Please use a 2 A fuse for the time delay fuse.
· Please select a fuse that satisfied with operating current/voltage for the fast acting fuse.
   (example) actual operating current 40 A : BUSSMANN FWH-40 (please use 40 A r.m.s min)

Part name and function

▒ Internal dip switch operation

Number

ON

OFF

Default mode

No. 1

-

1. input mode : 4 – 20 mA DC
2. control mode : phase control
3. others : Restart mode ON, 
partial load break function OFF        

No. 2

-

Partial load break function

No. 3

-

Restart mode ON

No. 4

Fixed cycle control

Phase control (Linear output)

No. 5

Variable cycle control

No. 4, 5

Phase control

No. 6

Limit mode

-

No. 7

1 - 5 V DC

Use external and internal

V.R simultaneously

No. 8

External V.R

No. 7, 8

4 - 20 ㎃ DC

 

 

Function description

▒ Phase control

▒ Phase control (Linear output)

Phase control is to control the AC power supply applied to the load proportionally according to the control 
input signal as changing phase angle (0 ~ 180 degree) in a each half cycle, 8.33 ms.

The control method is the same as the phase control but it outputs more linearly than the phase control.

<Ordinary phase control>

<Phase control (Linear output)>

25 % control

Output

Output

contact

signal

Contact

signal

Output

contact signal

Output

contact signal

50 % control

75 % control

100 % control

Output

control input (mA)

100 %

80 %

60 %

40 %

20 %

6 8 10 12 14 16 18 20

Output

control input (mA)

100 %

80 %

60 %

40 %

20 %

6 8 10 12 14 16 18 20

▒ Restart function

▒ V.R Explanation

When a warning or caution alarm occurs, TPR gives alarm 1 or 2 or stop the output. This function is used 
to return to normal operation mode when factors caused errors are eliminated.
This function can be used in power failure, frequency variation and SCR short of EMG and OT1, 2 of 
overheated heat sink. (This function is not applicable to when overcurrent occurs.)

1. O.C (overcurrent setting function)
   When overcurrent occurs, protection function for TPR and load (Only for phase control)

 

V.R gradation for overcurrent setting position.

•Depending on load type and VR error, overcurrent setting 
   position can be different.
•The overcurrent setting can be different depending on the types 
   of load or VR tolerance. In order to set an accurate position of 
   the overcurrent setting, adjust the control signal that TPR can have the current that needs to be alarmed. Turn 
   the O.C VR until the O.C indicator is ON. The position of the O.C VR is the overcurrent setting value.
•If OC V.R turning to the right of the maximum, overcurrent function does not work.
2. SOFT
   This volume is to set time for Soft start or Soft up/down. (only applicable to phase control, ON/OFF control)
- Soft start : Protection functions against big load of start current (inrush current). It increases output softly.
                  When control input is applied and power is on, Soft start operates when rung signal is applied. 
                 In case of maximum VR, it set 60 second. (Example : 20 mA : 60 sec, 12 mA : 30 sec)
- Soft up / down : When run signal and power are applied and if 
                         control input is applied, it will operate. It 
                         case of maximum VR, it set 15 second.
- If VR turn up to the right, the function does not work. And if VR turn 
   right, time will be reduced.
3. POWER (output limit function)
This function is to limit the output regardless of the control input amount. 
Even though the control input is 100 %, the output will decrease as 
turning POWER volume counterclockwise.

▒ ON/OFF control

If ON/OFF contact is ON, then the output is 100 %. ON/OFF always operates near zero point.

•Even though the control input signal is 
   ON, the output is 100 % when ON/OFF 
   control is used.

25 % control

Output

Output

contact

signal

Contact

signal

Output

contact signal

Output

contact signal

50 % control

75 % control

100 % control

Output

current

Time

Time

Input

signal

output voltage(%)

VR setting value (%)

Control input (%)

100

80

60

40

20

0

100

80

60

40

20

0

20

40

60

80

100

1. Please install it perpendicularly. If the product is installed vertically in   
   unavoidable circumstances, please use 50 % of rated current.
2. When multiple products are closely installed, please install them with 
   keeping a distance of more than a width of 5 cm and a length of 
   10 cm as shown in the picture.
3. In order to not block the air flow, please install the wiring duct less 
   than the half of the heat sink height.
4. Please consider whether the air flow is good enough when installing 
   the product. If the ambient temperature is as low as possible in the 
   inside then the life span of the product is increasing as the durability 
   and reliability of the product are improving. The operating ambient 
   temperature is 0 ℃ ~ 40 ℃. Please refer to the following graph.
   However, if the ambient temperature is higher than 40 ℃, the 
   maximum load current is decreasing like the below.

5. When connecting R and U, please securely fasten them with 
   using crimp connectors since high current flows into these 
   terminals. If the contact surface of the connectors and 
   terminals are poor, it may lead to a fire since the wires and 
   terminal gets overheated.
6. Before applying power, this model need more than the third class grounding to prevent electric shock.
   This model does not have separate grounding terminal so we suggest using grounding terminal and 
   bracket together when install this model to a panel.

•Characteristic of current 
   and temperature

Installation

Airflow

Perpendicular installation

Load curren

t

Ambient temperature (℃)

▒ LED indicator and explanation

LED indicator 

name

Description

POWER

POWER indicator is ON when the power is being supplied to the control unit

FIRE

Fire indicator is ON proportionally to the control input. It lights longer if the output amount is 
large and it is continuously ON if it outputs 100 % continuously.

SOFT

To use Soft start, Soft up/down function, turn Soft VR clockwise and SOFT indicator will be ON.

O.C

If the current flows higher than set value of O.C volume when there is overcurrent then O.C indicator 
is ON, the TPR stops the output to protect the product and the load and alarm 1 is activated.

L.L

This is partial heater break alarm. If heaters are connected in parallel 2~4 and one or more of heater is 
broken, alarm 2 will be activated. But in this case, alarm is activated and regulator operates properly.
(But in case of heater break, LL led will be displayed when total load current is more than 7A or falling load 
current more than 3A)

0.T1

While TPR is operating, the temperature of the heat sink is higher than 65 ℃, OT1 indicator is ON 
and alarm 2 is activated but the output of TPR is normally operating. If the temperature of the heat 
sink is below approximately 55 ℃, alarm 2 is deactivated.

0.T2

While TPR is operating, the temperature of the heat sink is higher than 85 ℃, OT2 indicator is 
ON and alarm 1 is activated but TPR stops the output.

EMG

The following situation when EMG LED indicator is ON. (This situation is for when alarm 1 (warning) outputs)
1. Power failure : when the power (100 – 240 V AC) of the control unit is being supplied, EMG LED is ON 
                      if the power for the load is not being supplied or the heater is broken.
2. SCR short : If SCR is short-circuited then the heater gets overheated since the power is being supplied 
         to the load regardless of the output of TPR. EMG is ON if the current flows without the control input.
3. Frequency variation : EMG is ON when the frequency other than 50/60 Hz that TPR cannot control.

▒ Variable cycle control

Without setting a constant cycle, variable cycle control 

is to control AC power supply with using the number of 
cycle.

TPR-2SL040/055/070 TPR-2SL090/110/130

O.C

17 A

37 A

58 A

O.C

26 A

57 A

87 A

O.C

17 A

37 A

58 A

O.C

26 A

57 A

87 A

▒ Fixed cycle control

As setting the constant cycle of the output, (1 sec), 
fixed cycle control is to control the AC power 
supply repeatedly with a constant rate of ON/OFF 
according to the control input.

60 ㎜ min

100 ㎜ min

30 ㎜ min

50 ㎜ min

Air flow

Wiring duct

Air in

Air out (FAN)

Wiring duct

Wiring duct