HANYOUNGNUX HD6 Скачать руководство пользователя страница 2

▍Time setting

▍Program setting

▍Control method for temperature

█ Key operation function description

[2.tyP]  

“PL.2”: 1, 2nd stage setting and 1, 2nd stage control (control 2nd stage priority)

"PL.1" : 1st stage setup and 1st stage control only.

[CLOSE Output Relay]

•Closed 1 operation

If the current temperature is lower than the set temperature (CLo.1), the CLOSE output relay is operated, 

and the output relay is “ON / OFF” according to the ON/OFF time (CL1.n / CL1.F) of the close 1 operation.

[CLOSE Output Relay ]

•Close 2 operation (However, the operation priority is higher than the closed 2 action.)

If the current temperature is lower than the set temperature (CLo.1 + CLo2), the CLOSE output relay operates.

The output relay turns "ON / OFF" according to the ON/OFF time (CL2.n/CL2.F) of the closed 2 operation.

[OPEN Output Relay]

● 2.tyP = PL.2(Stage 2 control operation)

• Open 2 operation (However, the operation priority is higher than Open 2 operation.)

If the current temperature is higher than the set temperature (oPE.1 + oPE.2), the OPEN output relay operates.

The output relay is "ON / OFF" according to the ON / OFF time (oP2.n / oP2.F) of open 2 operation.

● 2.tyP = PL.1(Stage 1 control operation)

•Open 1 operation

 When the current temperature is higher than the set temperature (OPE.1), the OPEN output relay is operated.

 The output relay is "ON/OFF" according to the ON/OFF time (oP1.n/oP1.F) setting of Open1 operation.

[OPEN Output Relay]

·Operation: oPE.1 output ON time

   

·Setting value change(      ,      ) : 1 ~ 999

·Operation: CLo.1 output ON time

·Setting value change(      ,       ) : 1 ~ 999

·Operation: CLo.1 output ON time and OFF time

·Setting value change(      ,      ) : 1 ~ 999

·Operation: oPE.2 output ON time

    

·Setting value change(      ,      ) : 1 ~ 999 

   Default : 10(Sec)

·Operation: OFF time after output ON time of oPE.2

   

·Setting value change(      ,      ) : 1 ~ 999 

   Default : (1 Min)

·Operation: CLo.2 output ON time

    

·Setting value change(      ,      ) : 1 ~ 999

   Default : (10 Sec)

Operation: CLo.2 output ON time and OFF time

    

·Setting value change(      ,      ) : 1 ~ 999 

   Default : (1 Min)

·Operation: OFF time after output ON time of oPE.1

    

·Setting value change(      ,       ) : 1 ~ 999

Default : oFF

Default : PL.1

Default : 0℃

Default : 5.0℃

Default : sec

Default : Min

Default

(10 Sec)

Default

(10 Sec)

Default

(1 Min)

Default

(1 Min)

온도설정

시간설정

프로그램설정    

Open 1 operation ON time

Open 1 operation OFF time

Closing 1 operation ON time

Closing 1 operation OFF time

Open 2 operation ON time

Open 2 operation OFF time

Closed 2 operation ON time

Closed 2 operation OFF time

Save time setting value

※ Press for more than 3 seconds. 

      (Enter the mode or save the set value)

on (lock): locks all set values in program setting mode

oFF (Release): Unlock all set values in program setting mode

Setting data lock function

·“PL.2”: 1st and 2nd stage setting and 1st and 2nd stage control (control 2nd stage priority)

·“PL.1”: 1st stage setting and 1st stage control only

Control method selection   (1st stage control operation or 2nd stage control operation)

·Temperature compensation for sensor line length or error occurrence (-10.0 ~ 10.0 ℃)

Measurement value correction setting

·Constant deviation is required during ON/OFF operation (0.1 ~ 25.0 ℃)

Hysteresis

Sec: Seconds (display lamp m: OFF)

Min: minute unit (display lamp m: ON)

Select output ON time unit

Sec: Seconds (display lamp m: OFF)

Min: minute unit (display lamp m: ON)

Select output OFF time unit

Current

temperature

Current

temperature

Default :

30.0 ℃

Default :

10.0 ℃

Default : 

10.0 ℃

Default :

-10.0 ℃

Save 

temperature

 setting value

※ 

In the program setting mode, “2. Displayed only when tyP = PL.2” is set.

※ 

※ When setting “2.tyP = PL.2” in program setting mode

      The priority of the task is "2 tasks (2 open, 2 closed)".

Open 1 operation temperature setting

(Set temperature (oPE.1) <present temperature (PV))

·Operation: Operates when the current temperature is higher than 

                           the set temperature (oPE.1)

·Setting value change(      ,        ) : -40.0 ~ 90.0 ℃

(Set temperature (CLo.1) <present temperature (PV))

Closed 1 operating temperature setting

·Operation: Operates when the current temperature is lower 

                           than the set temperature (CLo.1)

·Setting value change(       ,        ) : -40.0 ~ 90.0 ℃

Open 2 operation temperature setting

(Set temperature (oPE.1+oPE.2) <present temperature (PV))

·Operation: Operates when the current temperature is higher than

                          the set temperature (oPE.1 + oPE2)

·Setting value change(      ,       ) : 1.0 ~ 130.0 ℃

Closed 2 operating temperature setting

(Set temperature (CLo.1 + CLo.2)> Current temperature (PV))

·Operation: Operates when the current temperature is lower than 

                           the set temperature (CLo.1 + CLo.2)

·Setting value change(      ,        ) : -1.0 ~ -99.0 ℃

Current

temperature

Current

temperature

Current

temperature

※ 

Displayed only when “2.tyP=PL.2” 

is set in the program setting mode.

※ 

·Operation: oPE.1 output ON time

   

·Setting value change(      ,      ) : 1 ~ 999

·Operation: CLo.1 output ON time

·Setting value change(      ,       ) : 1 ~ 999

·Operation: CLo.1 output ON time and OFF time

·Setting value change(      ,      ) : 1 ~ 999

·Operation: oPE.2 output ON time

    

·Setting value change(      ,      ) : 1 ~ 999 

   Default : 10(Sec)

·Operation: OFF time after output ON time of oPE.2

   

·Setting value change(      ,      ) : 1 ~ 999 

   Default : (1 Min)

·Operation: CLo.2 output ON time

    

·Setting value change(      ,      ) : 1 ~ 999

   Default : (10 Sec)

Operation: CLo.2 output ON time and OFF time

    

·Setting value change(      ,      ) : 1 ~ 999 

   Default : (1 Min)

·Operation: OFF time after output ON time of oPE.1

    

·Setting value change(      ,       ) : 1 ~ 999

Default : oFF

Default : PL.1

Default : 0℃

Default : 5.0℃

Default : sec

Default : Min

Default

(10 Sec)

Default

(10 Sec)

Default

(1 Min)

Default

(1 Min)

온도설정

시간설정

프로그램설정    

Open 1 operation ON time

Open 1 operation OFF time

Closing 1 operation ON time

Closing 1 operation OFF time

Open 2 operation ON time

Open 2 operation OFF time

Closed 2 operation ON time

Closed 2 operation OFF time

Save time setting value

※ Press for more than 3 seconds. 

      (Enter the mode or save the set value)

on (lock): locks all set values in program setting mode

oFF (Release): Unlock all set values in program setting mode

Setting data lock function

·“PL.2”: 1st and 2nd stage setting and 1st and 2nd stage control (control 2nd stage priority)

·“PL.1”: 1st stage setting and 1st stage control only

Control method selection   (1st stage control operation or 2nd stage control operation)

·Temperature compensation for sensor line length or error occurrence (-10.0 ~ 10.0 ℃)

Measurement value correction setting

·Constant deviation is required during ON/OFF operation (0.1 ~ 25.0 ℃)

Hysteresis

Sec: Seconds (display lamp m: OFF)

Min: minute unit (display lamp m: ON)

Select output ON time unit

Sec: Seconds (display lamp m: OFF)

Min: minute unit (display lamp m: ON)

Select output OFF time unit

Current

temperature

Current

temperature

Default :

30.0 ℃

Default :

10.0 ℃

Default : 

10.0 ℃

Default :

-10.0 ℃

Save 

temperature

 setting value

※ 

In the program setting mode, “2. Displayed only when tyP = PL.2” is set.

※ 

※ When setting “2.tyP = PL.2” in program setting mode

      The priority of the task is "2 tasks (2 open, 2 closed)".

Open 1 operation temperature setting

(Set temperature (oPE.1) <present temperature (PV))

·Operation: Operates when the current temperature is higher than 

                           the set temperature (oPE.1)

·Setting value change(      ,        ) : -40.0 ~ 90.0 ℃

(Set temperature (CLo.1) <present temperature (PV))

Closed 1 operating temperature setting

·Operation: Operates when the current temperature is lower 

                           than the set temperature (CLo.1)

·Setting value change(       ,        ) : -40.0 ~ 90.0 ℃

Open 2 operation temperature setting

(Set temperature (oPE.1+oPE.2) <present temperature (PV))

·Operation: Operates when the current temperature is higher than

                          the set temperature (oPE.1 + oPE2)

·Setting value change(      ,       ) : 1.0 ~ 130.0 ℃

Closed 2 operating temperature setting

(Set temperature (CLo.1 + CLo.2)> Current temperature (PV))

·Operation: Operates when the current temperature is lower than 

                           the set temperature (CLo.1 + CLo.2)

·Setting value change(      ,        ) : -1.0 ~ -99.0 ℃

Current

temperature

Current

temperature

Current

temperature

※ 

Displayed only when “2.tyP=PL.2” 

is set in the program setting mode.

※ 

·Operation: oPE.1 output ON time

   

·Setting value change(      ,      ) : 1 ~ 999

·Operation: CLo.1 output ON time

·Setting value change(      ,       ) : 1 ~ 999

·Operation: CLo.1 output ON time and OFF time

·Setting value change(      ,      ) : 1 ~ 999

·Operation: oPE.2 output ON time

    

·Setting value change(      ,      ) : 1 ~ 999 

   Default : 10(Sec)

·Operation: OFF time after output ON time of oPE.2

   

·Setting value change(      ,      ) : 1 ~ 999 

   Default : (1 Min)

·Operation: CLo.2 output ON time

    

·Setting value change(      ,      ) : 1 ~ 999

   Default : (10 Sec)

Operation: CLo.2 output ON time and OFF time

    

·Setting value change(      ,      ) : 1 ~ 999 

   Default : (1 Min)

·Operation: OFF time after output ON time of oPE.1

    

·Setting value change(      ,       ) : 1 ~ 999

Default : oFF

Default : PL.1

Default : 0℃

Default : 5.0℃

Default : sec

Default : Min

Default

(10 Sec)

Default

(10 Sec)

Default

(1 Min)

Default

(1 Min)

온도설정

시간설정

프로그램설정    

Open 1 operation ON time

Open 1 operation OFF time

Closing 1 operation ON time

Closing 1 operation OFF time

Open 2 operation ON time

Open 2 operation OFF time

Closed 2 operation ON time

Closed 2 operation OFF time

Save time setting value

※ Press for more than 3 seconds. 

      (Enter the mode or save the set value)

on (lock): locks all set values in program setting mode

oFF (Release): Unlock all set values in program setting mode

Setting data lock function

·“PL.2”: 1st and 2nd stage setting and 1st and 2nd stage control (control 2nd stage priority)

·“PL.1”: 1st stage setting and 1st stage control only

Control method selection   (1st stage control operation or 2nd stage control operation)

·Temperature compensation for sensor line length or error occurrence (-10.0 ~ 10.0 ℃)

Measurement value correction setting

·Constant deviation is required during ON/OFF operation (0.1 ~ 25.0 ℃)

Hysteresis

Sec: Seconds (display lamp m: OFF)

Min: minute unit (display lamp m: ON)

Select output ON time unit

Sec: Seconds (display lamp m: OFF)

Min: minute unit (display lamp m: ON)

Select output OFF time unit

Current

temperature

Current

temperature

Default :

30.0 ℃

Default :

10.0 ℃

Default : 

10.0 ℃

Default :

-10.0 ℃

Save 

temperature

 setting value

※ 

In the program setting mode, “2. Displayed only when tyP = PL.2” is set.

※ 

※ When setting “2.tyP = PL.2” in program setting mode

      The priority of the task is "2 tasks (2 open, 2 closed)".

Open 1 operation temperature setting

(Set temperature (oPE.1) <present temperature (PV))

·Operation: Operates when the current temperature is higher than 

                           the set temperature (oPE.1)

·Setting value change(      ,        ) : -40.0 ~ 90.0 ℃

(Set temperature (CLo.1) <present temperature (PV))

Closed 1 operating temperature setting

·Operation: Operates when the current temperature is lower 

                           than the set temperature (CLo.1)

·Setting value change(       ,        ) : -40.0 ~ 90.0 ℃

Open 2 operation temperature setting

(Set temperature (oPE.1+oPE.2) <present temperature (PV))

·Operation: Operates when the current temperature is higher than

                          the set temperature (oPE.1 + oPE2)

·Setting value change(      ,       ) : 1.0 ~ 130.0 ℃

Closed 2 operating temperature setting

(Set temperature (CLo.1 + CLo.2)> Current temperature (PV))

·Operation: Operates when the current temperature is lower than 

                           the set temperature (CLo.1 + CLo.2)

·Setting value change(      ,        ) : -1.0 ~ -99.0 ℃

Current

temperature

Current

temperature

Current

temperature

※ 

Displayed only when “2.tyP=PL.2” 

is set in the program setting mode.

※ 

▍Temperature setting