27
B
ef
or
e staring
Installation
Op
er
ation
Sp
ecifications
No.
0
Description
+100
+200
+300
+400
Description by channel
93
-
-
-
-
-
-
-
94
-
-
-
-
-
-
-
95
ADDR
Switch address
-
-
-
-
-
96
MAX_CH
Number of channels
-
-
-
-
-
97
R_SYS
System data
-
-
-
-
-
98
R_OPT
Option data
-
-
-
-
-
99
ROMVER
Version
-
-
-
-
-
3.2.4 ML-D4register description
Register address (HEX)
Description
4
0001(0) ~
4
0099(63)
CH1~4 PV, SV, MV, TSV, CHSTS, EVSTS and common channel setting
※ Please use address
4
0000 for Modbus
communication
4
0101(65) ~
4
0199(C7)
CH1 related setting
4
0201(C9) ~
4
0299(12B)
CH2 related setting
4
0301(12D) ~
4
0399(18F)
CH3 related setting
4
0401(191) ~
4
0499(1F3)
CH4 related setting
Register address (HEX)
Symbol
Description
Property
(R/W)
Setting range
Unit
Initial
value
CH1 CH2 CH3 CH4 n : Number
of channel
1(1)
2(2)
3(3)
4(4)
PV
Process value
R
EU(0 ~ 100%)
℃
-
6(6)
7(7)
8(8)
9(9)
SV
Set value
R/W EU (0 ~ 100%)
℃ EU (0%)
11(B) 12(C) 13(D) 14(E)
MV
Manipulated
Value
R
0.0 ~ 100.0
%
-
16(10) 17(11) 18(12) 19(13)
CHSTS
Channel
status
R
OR run for situation occurrence
15 Bit: Set “1” at System Data error
14 Bit: Set “1” at Calibration Data error
13 Bit: Set “1” at input circuit error
12 Bit: Set “1” at EEPROM error
11 Bit: Set “1” after 24 hours of auto toning (AT)
10 Bit: Set “1” at standard contact point
correction (RCJ) error
9 Bit: Set “1” when exceeding ±5% input range
8 Bit: Set “1” at input sensor error (B. OUT)
2 Bit: Set “1” at auto tuning (AT) run
1 Bit: Set “1” at monitor mode
0 Bit: Set “1” at run start
ABS
-
21(15) 22(16) 23(17) 24(18)
TSV
Current target
set value
R
EU (0 ~ 100%)
℃ EU (0%)
26(1A)
EVT_STS
Event status
R
Indication of occurrence to all events
previously set
0: no event occurred
1: event occurred
ABS
-
27(1B)
EVBUS_STS Event bus output
status
R
Event bus output OR run
7 Bit(128): Set “1” at event bus8 output occurrence
6 Bit(64): Set “1” at event bus7 output occurrence
5 Bit(32): Set “1” at event bus6 output occurrence
4 Bit(16): Set “1” at event bus5 output occurrence
3 Bit(8): Set “1” at event bus4 output occurrence
2 Bit(4): Set “1” at event bus3 output occurrence
1 Bit(2): Set “1” at event bus2 output occurrence
0 Bit(1): Set “1” at event bus1 output occurrence
ABS
-
31(1F)
LOCK
Parameter
setting lock
R/W
0: possible to edit all parameters
1: possible to edit only SV, R/S, AT, CHEN
parameters
2. impossible to edit all parameters
ABS
0
32(20)
COMCHK
Time setting for
RS485
communication
disconnection
detection time
R/W 0: OFF
1 ~ 3,600
second 0 (OFF)
33(21)
PARA_SAVE
Save parameter
when
communication
R/W
0: Automatic parameter save
1: save manually using PARA_COPY
parameter
ABS
0
Содержание ML-D2H