• The contents of this manual may be changed without 

  prior notification.

• Before using the product you purchased, make sure that 

  is is exactly what you ordered.

• Make sure that there is no damage or abnormality of the

  product during the delivery.

• Make sure that there is no damage or abnormality of the 

  product during the delivery.

• Use this product within the range of the operating 

  ambient temperature, 0~50°C(When it is closely installed 

  max 40°C)and ambient humidty, 35~85%R.H(No 

  condensation).

• Do not use this product at any place with occuring 

  corrosive(especially noxious gas or ammonia)or 

  flammable gas.

• Do not use this product at any place with direct 

  vibration or impact.

• Do not use this product at any place with liquid, oil, 

  medical substances, dust, salt or iron contents.(use at 

  pollution level 1 or 2)

• Do not polish this product with substances such as 

  alchol or benzene.(use neutral detergent.)

• Do not use this product at any place with a large 

  inductive difficulty or occurring static electrictly or 

  magnetic noise.

• Do not use this product at any place with possible 

  thermal accumulation due to direct sunlight or heat 

  radiation.

• Install this product at place under 2,000m in altitude.

• When the product gets wet, the inspection is essential 

  because there is danger of an electric leakage or fire

• In case of inputting thermocouple, use a compensating 

  cable.(if using a normal wire, there is a possibility of 

  occurring temperature error.)

• For R.T.D input, use a cable which is a lead wire has 

  small resistances and resistances of there wires shall be 

  the same.(if the there wires have different resistances 

  then there will be a temperature error.)

• To avoid an effect of inductive noise to input signal 

  cables, use the product after separating the input signal 

  cables from power, output and load cables.

• Separate an input signal cable from an output signal 

  cable. if separating is not possible, please use the input 

  siganal cable after sheilding it.

• Use non-each sensor with thermocouple.(in case of 

  using earth sensor, there is a possibility of occurring 

  malfunction caused by a short circuit.)

• If there is excessive noise from the power supply, using 

  insulating transformer ans noise filter is recommended. 

  the noise filter must be attached to a panel which is 

  already connected to a ground and the wire between the 

  filter output side and power supply terminal must be 

  short as possible.

• If twisting the power cables closely together then it is 

  effective against noise.

• If the alarm functions are not properly set then it will not 

  be output when the product is malfunctiong. therefore, 

  maek sure its movements are properly working before 

  the operation.

• Turn the power OFF when replacing a sensor.

• Use an auxiliary relay in case of high frequent operation 

  such as proportional operation or etc. ist life span will 

  be shorter if connecting a load without permissible 

  rating of output relay. in this case. using SSR output type 

  is recommended.

 ◦Using electromagnetic switch : proportional cycle : set 

    it avobe 20sec

 ◦Using SSR : proportional cycle : set it above 1sec.

 ◦Life span of contact point output : mechanical life span 

     : avobe 10million times(with no load) electrical life 

    span : 100thousand times(250Va.c.3A : with the rated load)

• Do not connect anything to the unsed terminals.

• After checking the polarity of termanal, connect wires at 

  the correct position.

• When this product is connected onto a panel, use a 

  circuit breaker or switch approved with IEC60947-1 or 

  IEC60947-3.

• Install a circuit breaker or switch at near place for 

  convient use.

• Write down on a label that if the circuit breaker or switch 

  is operating then the power will be disconnected since 

  the circuit breaker or switch is installed.

• For the continuous and safe use of this product, the 

  periodical maintenance is recommened.

• Some parts of this product have limited life span, and 

  others are changed by their usage.

• The warranty period for this product including parts is 

  one year if this product is properly used.

• When the power is on, the preparation period of contact 

  output is required. in case of using signals of external 

  interlock circuit or etc., use it with a delay relay.

• In case of replacing this unit with a spare unit, make sure 

  its compatibility because its operation cna be different 

  by different parameter settings even thought the model 

  name is the same.

• Before using a temperature controller, there could be a 

  temperature difference between PV of the temperature 

  controller and the actual temperature so please operate 

  the temperature controller after compensating the 

  temperature difference appropriately.

• If there is a concern about a serious accident caused by 

  a malfunction or abnormality of this product, please 

  install an external protection circuit and device a 

  scheme for preventing an accident.

• Thisd product does not contain an electric switch or 

  fuse, so the user needs to install a separate electric 

  switch or fuse externally.(Fuse rating : 250V 0.5A)

• To prevent defection or malfunction of this product, 

  apply a proper power voltage in accordance with the rating.

• To prevent electric shock or malfunction of product, do 

  not supply the power until the wiring is conpleted.

• Since this product is not designed with explosion-

  protective structure, do not use it any place with 

  flammable or explosive gas

• Do not decompose, modify, revise or repair this product.

  this may be a cause of malfunction, electric shock or fire.

• Reassemble this product while the power is OFF, 

  otherwise, it may be a cause of malfunction or electric shock.

• If you use the product with methods other than 

  specified by the manufacturer, there may be bodily 

  injuries or property damages.

• There is a possibility of occurring electric shock so 

  please use this product after installing it on to a panel 

  while it is operating.

• There is a danger of occurring electric shock in the input/output terminals so please never let you body or conductive

   substance is touched  

Digital temperature controller

HY 

series

Thank you for purchasing HANYOUNG product. please check whether 

the product is the exactly same as you ordered. before using the 

product, please read this instruction manual carefully. please keep this 

manual where you can view at any time. 

MK2101KE191120

INSTRYCTION MANUAL

▍Suffix code

▍Range and input code

Model

Code

Description

HY-

Digital temperature controller

Dimension

8000S

96(W) X 96(H)

8200S

96(W) X 96(H) (Alarm setting general specification)

72D

72(W) X 72(H)

48D

48(W) X 48(H)

800S

96(W) X 96(H)

72I

72(W) X 72(H)

48I

48(W) X 48(H)

Control type

F

ON/OFF control

P

Proportional control

Input

K

K thermocouple

J

J thermocouple

R

R thermocouple

D

RTD, KPt100Ω

P

RTD, Pt100Ω(IEC)

V

1-5Vd.c.

C

4-20mAd.c.

Control output

M

Relay

C

Current coutput(4-20mAd.c.)

S

SSR(12Vd.c., Voltage pulse output)

Alarm output

N

None

O

High alarm(HY-8200S)

Control action(Internal selection)

R

Reverse action(Heating control)

D

Direct action(Cooling control)

Range code

Refer to the range and input code

Classification Code

HY-8000S, 8200S

HY-72D

HY-48D

Input type

Range(°C)

Input type

Range(°C)

Input type

Range(°C)

Thermocouple

4

K.J

0~299

5

0~399

6

K.J

0~199

K,J

0~199

7

0~299

0~299

8

0~399

0~399

9

0~599

10

0~599

K

0~799

11

K

0~799

12

0~1199

13

0~1199

R

600~1699

14

R

600~1699

RTD

1

-49~49

2

Pt100Ω

-99~99

Pt100Ω

-99~99

-99~99

3

-99~199

-99~199

0~199

4

0~99

0~99

0~299

5

0~399

6

0~199

0~199

7

0~299

0~299

8

0~399

0~399

Voltage/

current(DC)

1-5V

0~99

1-5V

0~99

1-5V

0~99

4-20mA

0~99

4-20mA

0~99

4-20mA

0~99

Code

HY-800S

HY-72I

HY-48I

Input type

Range(°C)

Input type

Range(°C)

Input type

Range(°C)

1

Pt100Ω

-49~199

2

Pt100Ω

0~399

Pt100Ω

-99~99

Pt100Ω

-99~99

K,J

3

K

0~1199

4

R

600~1699

5

Pt100Ω

0~399

K,J

8

Pt100Ω

0~399

K,J

K

0~1199

R

599~1699

※ Mark the range code for temperature display(HY-800S, HY-72I, HY-48I) when composing the model name and suffix code.

※ Alarm output can not be specified other than model name HY-8200S.

28, Gilpa-ro 71 beon-gil, Nam-gu, Incheon, Korea

Tel : (82-32)876-4697               Fax :(82-32)876-4696

http://www.hynux.com

HANYOUNGNUX CO.,LTD

▍Safety information

Before using the product, please read the safety information throughly and use it properly.

Alerts declared in the manual are classified to danger, warning and caution by their criticality

Danger indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
Warning indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
Caution indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury

DANGER
WARNING
CAUTION

WARNING

DANGER

CAUTION

▍Specification

Model

HY-8000S, HY-8200S

HY-72D, HY-48D

HY-800S

HY-72I, HY-48I

Power supply voltage

100-240Va.c.(±10%),

50/60㎐

110Va.c./220Va.c.

50/60㎐(Universal)

But, HY-48D, 

48I are selected by the 

internal Dip S/W

(Default : 220Va.c.)

100-240Va.c.(±10%),

50/60㎐

110Va.c./220Va.c.

50/60㎐(Universal)

But, HY-48D, 

48I are selected by the 

internal Dip S/W

(Default : 220Va.c.)

Voltage fluctuation

±10% of the power voltage

Power consumption

Approx 3Va max

Input

Thermocouple, Resistive, 

DC Current, DC Voltage

Thermocouple, Resistive

Adjusting sensitivity

Approx 0.2%FS(Fixed)

Control method

HY-8000, 72D, 48D - Time proportion ON/OFF

HY-8200S                - Time proportion ON/OFF

                                                             -  ON/OFF+ON/OFF

Setting method

Set by BCD switch

Display method

LED 7 Segment all display

LED 7 Segment all display

Control output

Relay output : capacity 250Va.c.3A

(resistive load) contact : 1c

SSR output : 12Vd.c.(constant voltage pulse)

(Resistive load : avobe 800Ω)

Current output : 4-20mAd.c.

(Resistive load : below 600Ω)

Setting accuracy

±0.5%FS max

Display accuracy

±1.0% of FS ±1digit

Proportional band

HY-8000S, HY-8200S, HY-72D

Approx.1%~10% of max. range(variable)

HY-48D : approx 3% of max. range(fixed)

Proportional cycle

Relay : 25~30sec, SSR : 2~4sec

External input esistance

Thermocouple : below 100Ω, Resistive : below 10Ω

(But, the 2 wires should have the same resistance.)

Resolution

1°C

Dielectric strength

2000Va.c.50/60㎐ 1minute(between terminals after charging 2 polar)

Ambient temperature

/humidity

0~50°C/35~85%RH(whithout condensation)

■ HY

800S

▍Connection diagram

Unit : mm

■ HY

8000S

POWER

100-240Va.c.

50/60Hz 3Va

4-20mAd.c.

12Vd.c.

POWER

100-240Va.c.

50/60Hz 3Va

POWER

100-240Va.c.

50/60Hz 3Va

4-20mAd.c.

12Vd.c.

50/60Hz(Universal)

220Va.c.

110Va.c.

4-20mAd.c.

12Vd.c.

CURRENT/SSR

OUTPUT

50/60Hz(Universal)

220Va.c.

110Va.c.

4-20mAd.c.

12Vd.c.

CURRENT/SSR

OUTPUT

110Va.c./220Va.c.

50/60Hz(Universal)

110Va.c./220Va.c.

50/60Hz(Universal)

POWER

100-240Va.c.

50/60Hz 3Va

4-20mAd.c.

12Vd.c.

POWER

100-240Va.c.

50/60Hz 3Va

POWER

100-240Va.c.

50/60Hz 3Va

4-20mAd.c.

12Vd.c.

50/60Hz(Universal)

220Va.c.

110Va.c.

4-20mAd.c.

12Vd.c.

CURRENT/SSR

OUTPUT

50/60Hz(Universal)

220Va.c.

110Va.c.

4-20mAd.c.

12Vd.c.

CURRENT/SSR

OUTPUT

110Va.c./220Va.c.

50/60Hz(Universal)

110Va.c./220Va.c.

50/60Hz(Universal)