• The contents of this manual may be changed without
prior notification.
• Before using the product you purchased, make sure that
is is exactly what you ordered.
• Make sure that there is no damage or abnormality of the
product during the delivery.
• Make sure that there is no damage or abnormality of the
product during the delivery.
• Use this product within the range of the operating
ambient temperature, 0~50°C(When it is closely installed
max 40°C)and ambient humidty, 35~85%R.H(No
condensation).
• Do not use this product at any place with occuring
corrosive(especially noxious gas or ammonia)or
flammable gas.
• Do not use this product at any place with direct
vibration or impact.
• Do not use this product at any place with liquid, oil,
medical substances, dust, salt or iron contents.(use at
pollution level 1 or 2)
• Do not polish this product with substances such as
alchol or benzene.(use neutral detergent.)
• Do not use this product at any place with a large
inductive difficulty or occurring static electrictly or
magnetic noise.
• Do not use this product at any place with possible
thermal accumulation due to direct sunlight or heat
radiation.
• Install this product at place under 2,000m in altitude.
• When the product gets wet, the inspection is essential
because there is danger of an electric leakage or fire
• In case of inputting thermocouple, use a compensating
cable.(if using a normal wire, there is a possibility of
occurring temperature error.)
• For R.T.D input, use a cable which is a lead wire has
small resistances and resistances of there wires shall be
the same.(if the there wires have different resistances
then there will be a temperature error.)
• To avoid an effect of inductive noise to input signal
cables, use the product after separating the input signal
cables from power, output and load cables.
• Separate an input signal cable from an output signal
cable. if separating is not possible, please use the input
siganal cable after sheilding it.
• Use non-each sensor with thermocouple.(in case of
using earth sensor, there is a possibility of occurring
malfunction caused by a short circuit.)
• If there is excessive noise from the power supply, using
insulating transformer ans noise filter is recommended.
the noise filter must be attached to a panel which is
already connected to a ground and the wire between the
filter output side and power supply terminal must be
short as possible.
• If twisting the power cables closely together then it is
effective against noise.
• If the alarm functions are not properly set then it will not
be output when the product is malfunctiong. therefore,
maek sure its movements are properly working before
the operation.
• Turn the power OFF when replacing a sensor.
• Use an auxiliary relay in case of high frequent operation
such as proportional operation or etc. ist life span will
be shorter if connecting a load without permissible
rating of output relay. in this case. using SSR output type
is recommended.
◦Using electromagnetic switch : proportional cycle : set
it avobe 20sec
◦Using SSR : proportional cycle : set it above 1sec.
◦Life span of contact point output : mechanical life span
: avobe 10million times(with no load) electrical life
span : 100thousand times(250Va.c.3A : with the rated load)
• Do not connect anything to the unsed terminals.
• After checking the polarity of termanal, connect wires at
the correct position.
• When this product is connected onto a panel, use a
circuit breaker or switch approved with IEC60947-1 or
IEC60947-3.
• Install a circuit breaker or switch at near place for
convient use.
• Write down on a label that if the circuit breaker or switch
is operating then the power will be disconnected since
the circuit breaker or switch is installed.
• For the continuous and safe use of this product, the
periodical maintenance is recommened.
• Some parts of this product have limited life span, and
others are changed by their usage.
• The warranty period for this product including parts is
one year if this product is properly used.
• When the power is on, the preparation period of contact
output is required. in case of using signals of external
interlock circuit or etc., use it with a delay relay.
• In case of replacing this unit with a spare unit, make sure
its compatibility because its operation cna be different
by different parameter settings even thought the model
name is the same.
• Before using a temperature controller, there could be a
temperature difference between PV of the temperature
controller and the actual temperature so please operate
the temperature controller after compensating the
temperature difference appropriately.
• If there is a concern about a serious accident caused by
a malfunction or abnormality of this product, please
install an external protection circuit and device a
scheme for preventing an accident.
• Thisd product does not contain an electric switch or
fuse, so the user needs to install a separate electric
switch or fuse externally.(Fuse rating : 250V 0.5A)
• To prevent defection or malfunction of this product,
apply a proper power voltage in accordance with the rating.
• To prevent electric shock or malfunction of product, do
not supply the power until the wiring is conpleted.
• Since this product is not designed with explosion-
protective structure, do not use it any place with
flammable or explosive gas
• Do not decompose, modify, revise or repair this product.
this may be a cause of malfunction, electric shock or fire.
• Reassemble this product while the power is OFF,
otherwise, it may be a cause of malfunction or electric shock.
• If you use the product with methods other than
specified by the manufacturer, there may be bodily
injuries or property damages.
• There is a possibility of occurring electric shock so
please use this product after installing it on to a panel
while it is operating.
• There is a danger of occurring electric shock in the input/output terminals so please never let you body or conductive
substance is touched
Digital temperature controller
HY
series
Thank you for purchasing HANYOUNG product. please check whether
the product is the exactly same as you ordered. before using the
product, please read this instruction manual carefully. please keep this
manual where you can view at any time.
MK2101KE191120
INSTRYCTION MANUAL
▍Suffix code
▍Range and input code
Model
Code
Description
HY-
⃞
⃞
⃞
⃞
⃞
⃞
⃞
Digital temperature controller
Dimension
8000S
96(W) X 96(H)
8200S
96(W) X 96(H) (Alarm setting general specification)
72D
72(W) X 72(H)
48D
48(W) X 48(H)
800S
96(W) X 96(H)
72I
72(W) X 72(H)
48I
48(W) X 48(H)
Control type
F
ON/OFF control
P
Proportional control
Input
K
K thermocouple
J
J thermocouple
R
R thermocouple
D
RTD, KPt100Ω
P
RTD, Pt100Ω(IEC)
V
1-5Vd.c.
C
4-20mAd.c.
Control output
M
Relay
C
Current coutput(4-20mAd.c.)
S
SSR(12Vd.c., Voltage pulse output)
Alarm output
N
None
O
High alarm(HY-8200S)
Control action(Internal selection)
R
Reverse action(Heating control)
D
Direct action(Cooling control)
Range code
Refer to the range and input code
Classification Code
HY-8000S, 8200S
HY-72D
HY-48D
Input type
Range(°C)
Input type
Range(°C)
Input type
Range(°C)
Thermocouple
4
-
-
-
-
K.J
0~299
5
-
-
-
-
0~399
6
K.J
0~199
K,J
0~199
-
-
7
0~299
0~299
8
0~399
0~399
9
-
0~599
10
0~599
K
0~799
11
K
0~799
-
12
-
0~1199
13
0~1199
R
600~1699
14
R
600~1699
-
-
RTD
1
-
-
-
-
-
-49~49
2
Pt100Ω
-99~99
Pt100Ω
-99~99
-99~99
3
-99~199
-99~199
0~199
4
0~99
0~99
0~299
5
-
-
0~399
6
0~199
0~199
-
-
7
0~299
0~299
8
0~399
0~399
Voltage/
current(DC)
-
1-5V
0~99
1-5V
0~99
1-5V
0~99
-
4-20mA
0~99
4-20mA
0~99
4-20mA
0~99
Code
HY-800S
HY-72I
HY-48I
Input type
Range(°C)
Input type
Range(°C)
Input type
Range(°C)
1
Pt100Ω
-49~199
-
-
-
-
2
Pt100Ω
0~399
Pt100Ω
-99~99
Pt100Ω
-99~99
K,J
3
K
0~1199
-
-
-
-
4
R
600~1699
-
-
-
-
5
-
-
-
-
Pt100Ω
0~399
K,J
8
-
-
Pt100Ω
0~399
-
-
K,J
-
-
-
K
0~1199
-
-
-
-
-
R
599~1699
-
-
※ Mark the range code for temperature display(HY-800S, HY-72I, HY-48I) when composing the model name and suffix code.
※ Alarm output can not be specified other than model name HY-8200S.
28, Gilpa-ro 71 beon-gil, Nam-gu, Incheon, Korea
Tel : (82-32)876-4697 Fax :(82-32)876-4696
http://www.hynux.com
HANYOUNGNUX CO.,LTD
▍Safety information
Before using the product, please read the safety information throughly and use it properly.
Alerts declared in the manual are classified to danger, warning and caution by their criticality
Danger indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
Warning indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
Caution indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury
DANGER
WARNING
CAUTION
WARNING
DANGER
CAUTION
▍Specification
Model
HY-8000S, HY-8200S
HY-72D, HY-48D
HY-800S
HY-72I, HY-48I
Power supply voltage
100-240Va.c.(±10%),
50/60㎐
110Va.c./220Va.c.
50/60㎐(Universal)
But, HY-48D,
48I are selected by the
internal Dip S/W
(Default : 220Va.c.)
100-240Va.c.(±10%),
50/60㎐
110Va.c./220Va.c.
50/60㎐(Universal)
But, HY-48D,
48I are selected by the
internal Dip S/W
(Default : 220Va.c.)
Voltage fluctuation
±10% of the power voltage
Power consumption
Approx 3Va max
Input
Thermocouple, Resistive,
DC Current, DC Voltage
Thermocouple, Resistive
Adjusting sensitivity
Approx 0.2%FS(Fixed)
-
Control method
HY-8000, 72D, 48D - Time proportion ON/OFF
HY-8200S - Time proportion ON/OFF
- ON/OFF+ON/OFF
-
Setting method
Set by BCD switch
-
Display method
LED 7 Segment all display
LED 7 Segment all display
Control output
Relay output : capacity 250Va.c.3A
(resistive load) contact : 1c
SSR output : 12Vd.c.(constant voltage pulse)
(Resistive load : avobe 800Ω)
Current output : 4-20mAd.c.
(Resistive load : below 600Ω)
-
Setting accuracy
±0.5%FS max
-
Display accuracy
±1.0% of FS ±1digit
Proportional band
HY-8000S, HY-8200S, HY-72D
Approx.1%~10% of max. range(variable)
HY-48D : approx 3% of max. range(fixed)
-
Proportional cycle
Relay : 25~30sec, SSR : 2~4sec
-
External input esistance
Thermocouple : below 100Ω, Resistive : below 10Ω
(But, the 2 wires should have the same resistance.)
Resolution
1°C
Dielectric strength
2000Va.c.50/60㎐ 1minute(between terminals after charging 2 polar)
Ambient temperature
/humidity
0~50°C/35~85%RH(whithout condensation)
■ HY
-
800S
▍Connection diagram
Unit : mm
■ HY
-
8000S
POWER
100-240Va.c.
50/60Hz 3Va
4-20mAd.c.
12Vd.c.
POWER
100-240Va.c.
50/60Hz 3Va
POWER
100-240Va.c.
50/60Hz 3Va
4-20mAd.c.
12Vd.c.
50/60Hz(Universal)
220Va.c.
110Va.c.
4-20mAd.c.
12Vd.c.
CURRENT/SSR
OUTPUT
50/60Hz(Universal)
220Va.c.
110Va.c.
4-20mAd.c.
12Vd.c.
CURRENT/SSR
OUTPUT
110Va.c./220Va.c.
50/60Hz(Universal)
110Va.c./220Va.c.
50/60Hz(Universal)
POWER
100-240Va.c.
50/60Hz 3Va
4-20mAd.c.
12Vd.c.
POWER
100-240Va.c.
50/60Hz 3Va
POWER
100-240Va.c.
50/60Hz 3Va
4-20mAd.c.
12Vd.c.
50/60Hz(Universal)
220Va.c.
110Va.c.
4-20mAd.c.
12Vd.c.
CURRENT/SSR
OUTPUT
50/60Hz(Universal)
220Va.c.
110Va.c.
4-20mAd.c.
12Vd.c.
CURRENT/SSR
OUTPUT
110Va.c./220Va.c.
50/60Hz(Universal)
110Va.c./220Va.c.
50/60Hz(Universal)