Hansen AUTO-PURGER M Скачать руководство пользователя страница 4

4

APM-001e 
AUG 2015

PURGE POINT CONNECTIONS

Foul gas lines from condensers should be purged at points 
recommended by the condenser manufacturer.  Usually, this 
is at the top of each circuit’s outlet header which drains 
down through a P-trap to the receiver.  In some cases, a 
small high pressure auxiliary receiver is located at the 
outlet of one or more condensers. This receiver should 
have a purge point at the top, preferably at a “dead” area 
away from condenser drain pipes. Below is a typical valve 
arrangement for a purge point (Figure 3). 

Regardless of 

the purge point location, it is absolutely necessary to 

ensure that liquid is not drawn into the foul gas line.

WATER LINE

The APM has an automatic water bubbler to eliminate any 

water bottle attention.  Connect the water supply to the 
purger water shut-off valve (See Figure 1).  Water pressure 
should be between 30 and 80 psig (2 and 5 bar).  The 
factory-installed flow controller limits the amount of water 
going into the bubbler. 

The transparent tube of the water bubbler may become 

coated with mineral deposits after a period of time.  These 
deposits can be removed by adding a cup of vinegar to the 
water in the bubbler and cleaning the clear tube through 
the top plastic fitting with the brush supplied.  A water 
conditioning filter cartridge and housing are available for 
abnormally hard water.

DRAIN LINE

A 1” PVC socket water drain connection is located at the 

bottom of the bubbler (an alternate 1” FPT threaded adapter 
is also supplied).  The water should flow to a suitable drain.  
Initially, fill the water bubbler with water via the threaded 
plug located at the top of the bubbler.  Keep the plug 
lubricated and hand tight.  A circular, thin, plastic “stick-

on” acts as a bubbler relief device in case of water drain 
plugging.  The drain line should be supported to prevent 
undue stress on the water bubbler.

OIL DRAINS

There are two 3/8” valve oil drain connections near the 

bottom of purger (see Figure 1) from which oil can be 

drained. These valves are fitted with 5/16” (8 mm) hex 
socket plugs. Before draining oil, first close the liquid and 
foul gas lines to prevent additional liquid from entering the 
purger.  Wait approximately one half hour and then turn 
the purger off. Allow the purger to pump out, then close 
the suction line shut-off valve.  Use normal refrigerant oil 
draining precautions to prevent human or property damage. 
In general, oil will not be a problem unless the liquid line 

is connected to a vessel or line where oil can enter the 
purger.  See also the Caution section on page 14. Escaping 
refrigerant may cause personal injury, particularly to the 

eyes and lungs.

LEAK TEST

Use standard refrigeration procedures to check the APM 
for leaks before placing it into service.  See also the 
Caution section on page 14.  Manually open one purge 
point solenoid valve.  Open the foul gas line shut-off valve 
and wait a few moments for the flooded evaporator to 
pressurize through the metering orifice. Allow pressure to 
build to condensing pressure, as shown on the high side 
pressure gauge.  Close the foul gas line shut-off valve and 
check the purger for leaks.

Where a high-pressure float regulator is used to drain one 
or more condensers, the top of the float valve chamber 
should also be a purge point.

Horizontal shell and tube water-cooled condensers, and 
heat exchangers should be purged at the top, usually at 
the point(s) furthest from the compressor discharge main 
inlet.

Vertical condensers should be purged near the top of the 
vessel if possible.

For certain types of oil separators where very low velocities 
may exist near the top of the vessel, purging may be 
advisable from a top fitting.

It is normally not advisable to purge controlled pressure 
receivers, high-pressure thermosyphon vessels, or vessels 
located on the low side of the system.

SUCTION LINE

The ¾” suction line from the purger should be connected 

to a protected main suction line or a suction accumulator.  
Install a suction line isolation shut-off valve near purger.  
Excess amounts of liquid from the purger evaporator may 
occasionally be transmitted through the suction line.  The 
suction temperature must be 40°F (4.4°C) or less to satisfy 
the APM temperature sensor before purging will occur.

LIQUID LINE

A high-pressure ½” liquid line is required for the APM.  The 

connection to the high-pressure liquid source should be 
a location where oil will not be directed into the purger.  
Install liquid line shut-off valve near the purger.  The liquid 

line supplies refrigerant during start-up and feeds make-
up liquid as required. The only requirement is the liquid 

supply pressure must be sufficiently above the purger 
evaporator pressure, usually greater than 60 psi (4.1 bar).  
During operation, only 5% of the liquid refrigerant required 
for cooling comes from the liquid line.  The remainder of 
the refrigerant is condensate from the foul gas line, which 
is collected in the drain, condensed in the coil, and into 
the evaporator.

SECTION 1  MOUNTING & PIPING INSTALLATION

Содержание AUTO-PURGER M

Страница 1: ...ore or after the purge point solenoid valves See Figure 2 The foul gas line should not pass through cold areas where INTRODUCTION The AUTO PURGER M is a compact and totally automatic electronically co...

Страница 2: ...ndenser piping design Hansen Technologies can provide copies of these articles Also consult the condenser manufacturers installation instructions for additional piping and sizing information On evapor...

Страница 3: ...E CLOSE COUPLED ISOLATION TO PURGER 1 2 13 MM PORT SHUT OFF VALVE REMOTE PURGE POINT SOLENOID VALVE ISOLATION SHUT OFF VALVE STRAINER GLOBE VALVE STEM HORIZONTAL IS PREFERRED LEVEL OR PITCH DOWN SECTI...

Страница 4: ...oil will not be a problem unless the liquid line is connected to a vessel or line where oil can enter the purger See also the Caution section on page 14 Escaping refrigerant may cause personal injury...

Страница 5: ...il voltage is different simply remove and discard the factory installed jumpers between terminals 13 14 and 15 16 Bring the purge point solenoid line L1 connection to terminal 14 and neutral L2 to ter...

Страница 6: ...e gases that may have collected MANUAL OPERATION Manual Operation mode allows the operator to select one purge point continuously This is usually the case if a large volume of noncondensible gas is su...

Страница 7: ...t will display the diagnostic code related to the occurrence which first put the APM into this mode exception 6666 will override 7777 Also see the troubleshooting guide on page 10 for detailed explana...

Страница 8: ...d valves are required one for each enabled purge point These are not included with the APM The Hansen type HS8 solenoid valve having a 13mm port and a stainless steel piston is recommended Below is a...

Страница 9: ...er diagnostic code 2222 flashes on the APM digital readout No purging of air will occur until foul gas pressure is restored OPERATION The foul gas may carry a certain amount of condensed refrigerant w...

Страница 10: ...flooded evaporator is cooled down REASON 1 Suction temperature too high Check Verify the pressure at the purger suction line connection Action Connect to a lower temperature suction REASON 2 Restrict...

Страница 11: ...ressure liquid available to maintain an adequate level in the flooded evaporator of the purger The purger will not purge air until this is corrected REASON 1 Liquid line solenoid valve B is not openin...

Страница 12: ...to Piping Instructions in Section I of this bulletin Action Correct condenser and foul gas piping REASON 4 High side level sensor not detecting drop in liquid level due to oil Action Run recalibratio...

Страница 13: ...QUID LINE SUCTION LINE 1 4 NPT 1 4 NPT SOCKET WELD SOCKET WELD SOCKET WELD VIEW ROTATED PIPE THREAD PIPE THREAD GAUGE VALVE GAUGE VALVE PURGER FRAME SHUT OFF VALVE VPM FOR CLARITY OPTIONAL VALVE PACKA...

Страница 14: ...TIONAL VALVE PACKAGE VPMF The special construction for APMF AUTO PURGERs includes a filter dryer conditioning system for the foul gas and liquid line Water vapor as well as noncondensible gas may be p...

Страница 15: ...20 1857 Temperature sensor 20 2303 High side level sensor 77 0796 Drainer and low side level sensor 77 0794 Solenoid coil kit 230V with DIN plug 70 1093 Solenoid coil kit 115V with DIN plug 70 1092 M...

Страница 16: ...and the Nonelectrical AUTO PURGER NEAP Use the following descriptions to help select the best AUTO PURGER for your needs For additional assistance contact the factory AUTO PURGER AP This is the origin...

Отзывы: