Table A: Guide to maximum stabilised tem-

peratures  recorded  during  site  tests 

 

Application 

Mixed water

 

temperature

Shower 

43°C

Washbasin 

43°C 

Bath (44°C fill) 

46°C

Bath (46°C fill) 

48°C

 

 

The mixed water temperature at terminal fitting should 
never exceed 46ºC.

If  there  is  a  residual  flow  during  the  commissioning  or 
the annual verification (cold water supply isolation test), 
then this is acceptable providing the temperature of the 
water seeping from the valve is no more than 2°C above 
the designated maximum mixed water outlet temperature 
setting of the valve.
Temperature readings should be taken at the normal flow 
rate after allowing for the system to stabilise. 
The sensing part of the thermometer probe must be fully 
submerged in the water that is to be tested.
Any  TMV  that  has  been  adjusted  or  serviced  must  be 
re-commissioned  and  re-tested  in  accordance  with  the 
manufacturers' instructions.

Commissioning  and  in-service 

tests

Commissioning

Purpose

Since the installed supply conditions are likely to be diffe-
rent from those applied in the laboratory tests it is appro-
priate, at commissioning, to carry out some simple checks 
and tests on each mixing valve to provide a performance 
reference point for future in-service tests.

Procedure

1. 

Check that:

a) the designation of the thermostatic mixing valve 

matches the intended application

b)  the supply pressures are within the range of ope-

rating pressures for the designation of the valve

c)  the supply temperatures are within the range per-

mitted for the valve and by guidance information 
on the prevention of legionella etc.

2. 

Adjust the temperature of the mixed water in accor-
dance with the manufacturer’s instructions (page 62) 
and the requirement of the application and then carry 
out the following sequence:

a)  record the temperature of the hot and cold water 

supplies

b)  record the temperature of the mixed water at the 

largest draw-off flow rate

c)  record the temperature of the mixed water at a 

smaller draw-off flow rate, which shall be measu-
red

d)  isolate the cold water supply to the mixing valve 

and monitor the mixed water temperature

e)  record the maximum temperature achieved as a 

result of (d) and the final stabilised temperature

 

NOTE: The final stabilised mixed water temperature 
should not exceed the values in Table A.

f)  record the equipment, thermometer etc. used for 

the measurements

Содержание Ecomax 14243000

Страница 1: ...EN Instructions for use assembly instructions 2 DE Gebrauchsanleitung Montageanleitung 4 Ecomax 14243000...

Страница 2: ...utting injuries The shower system may only be used for bathing hygienic and body cleansing purposes Children as well as adults with physical mental and or sensoric impairments must not use this shower...

Страница 3: ...necessary Spout temperature does not cor respond with temperature set Thermostat has not been adjusted Hot water temperature too low Adjust thermostat Increase hot water temperature to 42 C to 65 C T...

Страница 4: ...r Trinkwasser konzi piert Sicherheitshinweise Bei der Montage m ssen zur Vermeidung von Quetsch und Schnittverletzungen Handschuhe getragen werden Das Produkt darf nur zu Bade Hygiene und K rper reini...

Страница 5: ...r stimmt nicht mit der eingestellten Temperatur berein Thermostat wurde nicht justiert Zu niedrige Warmwassertempe ratur Thermostat justieren Warmwassertemperatur erh hen auf 42 C bis 65 C Temperaturr...

Страница 6: ...6 SW 30 mm 17 Nm SW 30 mm 17 Nm 2b 1 2a...

Страница 7: ...7 SW 3 mm 2 Nm SW 3 mm 42 40 1 2 3 4 5 6...

Страница 8: ...8 1 2 3...

Страница 9: ...9 close schlie en 90 open ffnen 1 2 cold kalt 40 C hot warm 90...

Страница 10: ...10 SW 30 mm SW 12 mm 2 1 2 3 4 1...

Страница 11: ...11 Ecomax 14243000...

Страница 12: ...12 96922000 97210000 97163000 97164000 98870000 95589000 92929000 96488000 97211000 98163000 15x2 98194000 28x2 96644000 A 96633000 Ecomax 14243000 PA IX DVGW SVGW ACS WRAS ETA KIWA 14243000 X...

Страница 13: ...g recommendation www hansgrohe com cleaning recommendation www hansgrohe com cleaning recommendation www hansgrohe com cleaning recommendation EN Cleaning recommendation Warranty Contact DE Reinigungs...

Страница 14: ...waterproofed wall surface usually tiles If you are using power tools e g to drill holes wear sa fety glasses and always disconnect tools from the power supply after use Do not operate the shower unit...

Страница 15: ...allowable temperature tolerances inherent in thermo static mixing valves and temperature losses in metal baths It is not a safe bathing temperature for adults or children The British Burns Association...

Страница 16: ...16 KEY Isolating valve Reducing valve Mixer Valve Pump Gas Combination Boiler multi point Unvented System pressure balanced Pumped System...

Страница 17: ...priate at commissioning to carry out some simple checks and tests on each mixing valve to provide a performance reference point for future in service tests Procedure 1 Check that a the designation of...

Страница 18: ...ce of any other instruction or guidance on the means of determining the appropriate frequency of in service testing the following procedure may be used 1 6 to 8 weeks after commissioning carry out the...

Страница 19: ...after correct installation the outlet temperature of the water can never exceed 43 C To guarantee a smooth running of the thermostatic element it is necessary from time to time to turn the thermostat...

Страница 20: ...20 Hansgrohe Auestra e 5 9 D 77761 Schiltach Telefon 49 0 78 36 51 1282 Telefax 49 0 7836 511440 E Mail info hansgrohe com Internet www hansgrohe com 08 2018 9 04410 04...

Отзывы: