48
• Using the arrow keys, set the
controller address. To exit setup,
press CFM key and then LCD key.
Note
In an RS 485 network, each device must have a different
address.
• Select the desired baud rate with the up and down keys
and press the CFM key to store the new settings. Available
baud rates are: 1200, 2400, 4800 and 9600 Bps.
The PC software to communicate with the controllers is
HI92500. Please refer to this product specifications for fur-
ther informations.
RS485 PROTOCOL
The commands sent to the controller must have the follow-
ing format:
• 2-digit process ID number
• 3-character command name
• Parameters (variable length, may be null)
• End of command (always the CR character, Hex 0D)
A maximum time interval of 20 ms is allowed between two
consecutive characters of a command. It is possible to send
commands to change the controller settings or to simply
ask information on the controller status. Following is the
complete list of commands available:
Command
Command
Command
Command
Command
Parameter
Parameter
Parameter
Parameter
Parameter
Description
Description
Description
Description
Description
CAR
null
Request calibration data
GET
NN
Request setup item NN
K01
null
Same as CFM+CAL keys
K02
null
Same as LCD+CAL+SETUP keys
KCD
null
Same as CAL DATA key
KCF
null
Same as CFM key
KCL
null
Same as CAL key
Содержание HI 23 Series
Страница 9: ...9 MECHANICAL DIMENSIONS...