Puma 20/40
Trouble shooting | 113
Possible cause
Remedy
Joystick Displaced at
Power-up
The most common cause of this trip is if the joystick is de
fl
ected away from the center when the
control system is being switched on. When the control system is switched on, the battery gauge
will blink for a short time. Check that the user is not de
fl
ecting the joystick before the blink
fi
nishes.
If the problem persists, refer to section .37.
Communication Error
The most likely cause of a communication error is a defective cable between the Power Module
and the Joystick Module. The cable should be checked for damage, and replaced if found to
have a fault. The Joystick Cable can only be replaced by a person authorized by the wheelchair
manufacturer. Refer to Section 1.3 for the replacement procedure.
If the problem persists then either the Power Module or the Joystick Module could be defective.
Refer to Section 5.
Inhibit 2 Active
This occurs when the Inhibit 2 Input is active. The Inhibit 2 input is via the INH-2 way connector
and is normally associated with speed limit or actuator functions. The operation of Inhibit 2 will
depend upon the programmed settings and the wheelchair on which it is being used. Check all
wiring and switches connected to Inhibit 2. If these appear to be in working order, then the Power
Module may be defective. Refer to Section 5.
Inhibit 3 Active
This occurs when the Inhibit 3 Input is active. The Inhibit 3 input is via the 3 way on-board charger
(OBC) and is normally associated with this function. The operation of Inhibit 3 will depend upon
the programmed settings and the wheelchair on which it is being used. Check all wiring, switches
and OBC (if
fi
tted) connected to Inhibit 3. If these appear to be in working order, then the Power
Module may be defective. Refer to Section 5.
Actuator Motor Wiring Trip
This occurs when the control system detects a fault in the wiring to either actuator motor. Check
the motor connectors and wiring. If the trip is still present after the above checks have been made,
then the Power Module may be defective. Refer to Section 5.
Current Limit Active
This occurs when the control system operates above the Current Limit Threshold for a periode of
time greater than the Current Limit Time. It has been designed to notify the Healthcare Technician
that the control system has operated outside of its programmed range.
High Temperature
This occurs when the control system reaches its Temperature Threshold and thus becomes to
hot. The controller will not allow drive until the controller to cooled down. An entry is made in the
system log each time the controller gets too hot and goes out of drive.
Содержание Puma 20
Страница 1: ...SERVICE MANUAL EN VERSION 2 2015...
Страница 36: ...36 Service instructions Puma 20 40 36 Service instructions 4 1 3 3 2 110648 03 008 5 6...
Страница 41: ...Service instructions 41 Puma 20 40 Service instructions 41 4 5 1 3 2 110648 03 028 6...
Страница 44: ...44 Service instructions Puma 20 40 44 Service instructions 5...
Страница 46: ...46 Service instructions Puma 20 40 46 Service instructions 3 4 5 6 7 8...
Страница 50: ...50 Service instructions Puma 20 40 50 Service instructions 3 17 4 Loctite 270 25Nm 17...
Страница 53: ...Service instructions 53 Puma 20 40 Service instructions 53 8 9...
Страница 57: ...Service instructions 57 Puma 20 40 Service instructions 57 11...
Страница 71: ...Service instructions 71 Puma 20 40 Service instructions 71 11 12...
Страница 75: ...Service instructions 75 Puma 20 40 Service instructions 75 5 6...
Страница 77: ...Service instructions 77 Puma 20 40 Service instructions 77 5 6 7...
Страница 83: ...Service instructions 83 Puma 20 40 Service instructions 83 14 3 1 2 15...
Страница 85: ...Service instructions 85 Puma 20 40 Service instructions 85 5 6 7...
Страница 86: ...86 Service instructions Puma 20 40 86 Service instructions 8...
Страница 90: ...90 Service instructions Puma 20 40 90 Service instructions 5...
Страница 118: ...Puma 20 40 118 Technical product information Shark drive and lights...
Страница 132: ......