HANBAY Inc
User Manual MDx-xxxDT-10.31
Page 4 of 8
www.hanbayinc.com
Rev: 2
– July, 2019
1 800 315 4461
DIP 3
Reserved for custom function.
DIP 4
Sets direction of offset. (Offset only available in MD
H
and MD
F
series)
DIP 5
Sets the highest amount of offset, typically 12°.
NOTE:
To set maximum offset DIP’s 5,6 and 7 will
need to be high for a total of 21°. The max. offset can also be set differently upon customer request.
DIP 6
Sets medium offset, typically 6°.
DIP 7
Sets the lowest amount of offset, typically 3°.
DIP 8
With DIP switch 8 in the ON position, the actuator will move to 4 positions. When switch 8 is off, the
actuator is limited to three positions. Switch 8 also changes the function of the output signals.
DIP 9
Run / Calibrate
Putting DIP switch 9 into the off position will disable the actuator positioning control, and the motor
will not move regardless of the input signals.
When DIP 9 is moved back into the on position, the actuator will perform its homing routine, and then
move to the position commanded by the input signals.
DIP 10 DIP 11
Description
Approximate stall current
Off
Off
Low torque 16%
0.75A
Off
On
Medium-low 33%
1A
On
Off
Medium-high 66%
2A
On
On
High torque 100%
3A
Approximate stall torque
DIP 10
DIP 11
MDL
MDM
MDH
MDF
Off
Off
55 in-lbs.
120 in-lbs.
405 in-lbs.
756 in-lbs.
Off
On
82 in-lbs.
160 in-lbs.
540 in-lbs.
1008 in-lbs.
On
Off
88 in-lbs.
180 in-lbs.
608 in-lbs.
1134 in-lbs.
On
On
94 in-lbs.
195 in-lbs.
657 in-lbs.
1241 in-lbs.
DIP 12
DIP 12 sets the direction of rotation
Functionality of the MDx-xxxDT:
The MDx can operate as a 3-position or 4-position actuator. The 4
th
position is enabled by turning DIP 8 ON.
3-pos Functionality (DIP 8 OFF)
Input#1
(Pin 1)
Input#2
(Pin 2)
Action taken
High
High
Moves to or remains in center position
Low
High
Moves to or remains in right position
High
Low
Moves to or remains in left position
Low
Low
Moves to or remains in left position (Input#2 has precedence
over Input #1)
The feedback from the MDx-xxxDT is as follows:
Output#1
(Pin 3)
Output#2
(Pin 4)
Meaning
High = 4.5vDC Low = 0.8vDC
High
High
Actuator output is in center position
High
Low
In Right position
Low
High
In Left position
Low
Low
Actuator is moving, or has stalled and given up trying to reach
a requested position.
You may retry to reach any position by cycling alternate inputs
and trying the original again. Repeated failures to reach
position will require troubleshooting.
Top View
onto valve or
other
appliance
Center
Right
Left