DIP 3

 

Reserved for custom function.   

DIP 4

 

Sets direction of offset. (Offset only available in MD

H

 and MD

F

 series)

 

DIP 5

 

Sets the highest amount of offset, typically 12°. 

NOTE:

 

To set maximum offset DIP’s 5,6 and 7 will 

need to be high for a total of 21°. The max. offset can also be set differently upon customer request.

 

DIP 6

 

Sets medium offset, typically 6°.

 

DIP 7

 

Sets the lowest amount of offset, typically 3°.

 

DIP 8 

With DIP switch 8 in the ON position, the actuator will move to 4 positions.  When switch 8 is off, the 
actuator is limited to three positions.  Switch 8 also changes the function of the output signals. 

DIP 9 

Run / Calibrate 
Putting DIP switch 9 into the off position will disable the actuator positioning control, and the motor 
will not move regardless of the input signals. 
When DIP 9 is moved back into the on position, the actuator will perform its homing routine, and then 
move to the position commanded by the input signals.

 

DIP 10  DIP 11

 

Description 

Approximate stall current 

Off 

Off 

Low torque           16% 

0.75A 

Off 

On 

Medium-low         33% 

1A 

On 

Off 

Medium-high        66% 

2A 

On 

On 

High torque          100% 

3A 

Approximate stall torque 

DIP 10

 

DIP 11

 

MDL 

MDM 

MDH 

MDF 

Off

 

Off 

55 in-lbs. 

120 in-lbs. 

405 in-lbs. 

756 in-lbs. 

Off

 

On 

82 in-lbs. 

160 in-lbs. 

540 in-lbs. 

1008 in-lbs. 

On

 

Off 

88 in-lbs. 

180 in-lbs. 

608 in-lbs. 

1134 in-lbs. 

On

 

On 

94 in-lbs. 

195 in-lbs. 

657 in-lbs. 

1241 in-lbs. 

DIP 12 

DIP 12 sets the direction of rotation 

 

Functionality of the MDx-xxxDT: 
 

The MDx can operate as a 3-position or 4-position actuator. The 4

th

 position is enabled by turning DIP 8 ON. 

 

3-pos Functionality (DIP 8 OFF) 

 

Input#1 

(Pin 1) 

Input#2 

(Pin 2) 

Action taken 

High 

High 

Moves to or remains in center position 

Low 

High 

Moves to or remains in right position 

High 

Low 

Moves to or remains in left position 

Low 

Low 

Moves to or remains in left position (Input#2 has precedence 
                                                                 over Input #1) 

 

The feedback from the MDx-xxxDT is as follows: 

Output#1 

(Pin 3) 

Output#2 

(Pin 4) 

Meaning     

High = 4.5vDC   Low = 0.8vDC 

High 

High 

Actuator output is in center position 

High 

Low 

In Right position  

Low 

High 

In Left position  

Low 

Low 

Actuator is moving, or has stalled and given up trying to reach 
a requested position. 
You may retry to reach any position by cycling alternate inputs 
and trying the original again. Repeated failures to reach 
position will require troubleshooting. 

 

 
 

Top View 

onto valve or 

other 

appliance 

Center 

 

Right 

Left 

Содержание MD DT-10.31 Series

Страница 1: ...ting the type of actuator pg 6 Calibration pg 6 Troubleshooting pg 6 Appendix pg 6 7 Dimensions pg 7 Cable Installation pg 7 Part Number Breakdown pg 8 Installation Mounting Usually the actuator has t...

Страница 2: ...color schematic for Turck6 cable Otherwise if the Turck cable is not included in your actuator see pg 8 for more detailed wiring instructions Pin Colour Function 6 White 24VDC 5 Black Power Gnd 4 Pin...

Страница 3: ...to use a fast settling setting on a high torque valve will increase current consumption when holding position and cause heating of the motor DIP 1 DIP 2 Off Off Fastest settling Use only for low torq...

Страница 4: ...Off On Medium low 33 1A On Off Medium high 66 2A On On High torque 100 3A Approximate stall torque DIP 10 DIP 11 MDL MDM MDH MDF Off Off 55 in lbs 120 in lbs 405 in lbs 756 in lbs Off On 82 in lbs 16...

Страница 5: ...e input is used to operate the valve When the actuator is operated using input 1 an automatic calibration is done every time the valve is actuated This does not happen on input 2 Torque Settings Effec...

Страница 6: ...he actuators output gear gets manually rotated while the actuator is powered down and can t properly realign to the center by itself Troubleshooting Upon noticing a problem your first step should almo...

Страница 7: ...ight fitting from the actuator casing and insert the cable into it 4 Carefully insert the cable into the actuator base Mind the red motor cable and its plug into the board Moving the plug out of its f...

Страница 8: ...HANBAY Inc User Manual MDx xxxDT 10 31 Page 8 of 8 www hanbayinc com Rev 2 July 2019 1 800 315 4461 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Отзывы: