background image

 

User Manual MCx-xxxAS-1.05 

 

 

 

Page 6 of 18

                                                                                                                         

www.hanbayinc.com | 1 800 315 4461      

Rev.2021.8                                                                                                                                                                              [email protected] 

Modbus Protocol 

 

Actuator parameters can be set by using the MODBUS (RTU) protocol. 
 
Standard supported function codes: 
02 (0x02) Read Discrete Inputs 
03 (0x03) Read Holding Registers. 
04 (0x04) Read Input Registers. 
06 (0x06) Write Single Register. 
 
Hanbay function codes: (see p.13 for examples) 
100 (0x64) Re-zero the actuator. 
101 (0x65) Close the valve. 
102 (0x66) Open the valve. 
 

 
If you try to use any other function code, the actuator will answer with the exception code 

0x01

 

indicating that the attempted function code is not supported. 
 

 
 

Actuator memory map: 
 

Address (DEC)

 

Address (HEX)

 

Offset

 

Register Name

 

Type

 

0x0000 

4001 

MaximumSpeed 

Holding registers.  

READ

 and 

WRITE

 

0x0001 

4002 

MaximumPower 

0x0002 

4003 

NumberOfTurns 

0x0003 

4004 

TargetFromRS485Flag 

0x0004 

4005 

InputRangeLow 

0x0005 

4006 

InputRangeHigh 

0x0006 

4007 

OutputRangeLow 

0x0007 

4008 

OutputRangeHigh 

0x0008 

4009 

TargetPosition 

0x0009 

4010 

SignalLostPosition 

10 

0x000A 

4011 

Reserved 

11 

0x000B 

4012 

Reserved 

12 

0x000C 

4013 

Reserved 

13 

0x000D 

4014 

Reserved 

14 

0x000E 

4015 

Reserved 

15 

0x000F 

4016 

Reserved 

16 

0x0010 

4017 

Reserved 

17 

0x0011 

4018 

Reserved 

18 

0x0012 

4019 

Reserved 

19 

0x0013 

4020 

Reserved 

20 

0x0014 

4021 

CurrentPosition 

Input registers. 

READ

 only

 

21 

0x0015 

4022 

StatusRegister 

 

IMPORTANT:   All the values sent to t

he actuator are “HEX” values 

 

 

Содержание MC-AS-1.05 Series

Страница 1: ...ignal and Feedback 3 Serial Port Connection 3 OPERATION 4 DIP switches 4 Set the communication parameters 4 Set the actuator address 5 Modbus Protocol 6 Speed and Torque Settings 7 Speed and Torque De...

Страница 2: ...standard with a Turck 6 position connector and a 20 cable with plug Cut the cable to the length required and then connect according to the following wire color schematic Pins indicate the connection...

Страница 3: ...Signal and Feedback Locate the correct connection terminals as shown in the picture on p 2 then connect your communication wires to PIN 3 and PIN 4 grey and pink wires as shown below Serial Port Conn...

Страница 4: ...n the signal is decreased with DIP 12 in the OFF position Putting DIP 12 in the ON position will cause counter clockwise turning for a decrease in signal For changes in DIP 12 position to take effect...

Страница 5: ...0 1 1 0 1 14 0 0 1 1 1 0 15 0 0 1 1 1 1 16 0 1 0 0 0 0 17 0 1 0 0 0 1 18 0 1 0 0 1 0 19 0 1 0 0 1 1 20 0 1 0 1 0 0 21 0 1 0 1 0 1 22 0 1 0 1 1 0 23 0 1 0 1 1 1 24 0 1 1 0 0 0 25 0 1 1 0 0 1 26 0 1 1...

Страница 6: ...e is not supported Actuator memory map Address DEC Address HEX Offset Register Name Type 0 0x0000 4001 MaximumSpeed Holding registers READ and WRITE 1 0x0001 4002 MaximumPower 2 0x0002 4003 NumberOfTu...

Страница 7: ...eed to 0 in actuator number 8 0x08 0x06 0x0000 0x0000 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes Possible values for the MaximumSpeed register are shown in the following table To see how these values re...

Страница 8: ...ess 0x0001 Seating Torque in lbs Operating torque is 100 12VDC 24VDC 0 23 0 17 35 1 11 1 30 60 2 7 2 55 115 3 4 3 70 145 NOTE If actuator is RCK xxxAS divide torque values by 3 To convert in lbs to Nm...

Страница 9: ...0x0B 0x06 0x0003 0x0000 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes The InputRangeLow register allows the user to set the lower limit of the input signal i e the value of the input signal at which the ac...

Страница 10: ...ing the valve completely This enables a new fully closed position to be established based on normal wear of the valve seat If the value in TargetPosition is the same as the value in InputRangeHigh the...

Страница 11: ...alLostPosition register The default value is 0xFFFF DEC 65535 The actuator will ignore the lost signal and simply remain in its current position If the value is between InputRangeLow and InputRangeHig...

Страница 12: ...lt Actuator address Function code Register address Qty of registers CRC StatusRegister 0x0015 N A N A N A Example Read the status register in actuator number 32 0x20 0x04 0x0015 0x0001 0x 1 byte 1 byt...

Страница 13: ...It will turn clockwise until the actuator has reached the fully closed position of the valve If the actuator is being controlled via Modbus protocol i e TargetFromRS485Flag register contains value 0...

Страница 14: ...s alone can solve basic problems See the Calibration section above for more details If the actuator does not move try following these steps 1 Re calibrate the actuator This will move the actuator rega...

Страница 15: ...User Manual MCx xxxAS 1 05 Page 15 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com ACTUATOR DIMENSIONS MCJ MCL MCM xxxAS models MCH xxxAS models...

Страница 16: ...User Manual MCx xxxAS 1 05 Page 16 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com MCF xxxAS models...

Страница 17: ...User Manual MCx xxxAS 1 05 Page 17 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com PART NUMBER BREAKDOWN Full Hanbay Part Number...

Страница 18: ...9 Px 10 3 Actuator Part Number Refer to part number breakdown for available options QR Code Scan this QR code for a direct link to the user manual for your unit Actuator Serial Number This serial numb...

Отзывы: