Hanbay MC-AS-1.05 Series Скачать руководство пользователя страница 4

 

User Manual MCx-xxxAS-1.05 

 

 

 

Page 4 of 18

                                                                                                                         

www.hanbayinc.com | 1 800 315 4461      

Rev.2021.8                                                                                                                                                                              [email protected] 

OPERATION 

 

 

DIP switches 

 

The DIP switches allow you to change the  
settings on your actuator. To flip a switch, 
gently use a small flat-head screwdriver. 
 
See the table below for DIP switch functionality. 

 
 
 
 

 

 

 

 

 

 

 

 

 
 
 

DIP 

Function 


Baud Rate:

 Choose the rate at which information is transferred. See p.4. 

– 8 

Actuator Address:

 See p.5. 

– 11 

Deactivated

 

12 
 

Direction/Calibration:

 Toggle while powered to re-calibrate actuator (find valve seat). Also sets 

direction in which the actuator will open and close. See p.13.  
 
Example: The RCM model actuator turns clockwise when the signal is decreased with DIP 12 in 
the OFF position. Putting DIP 12 in the ON position will cause counter-clockwise turning for a 
decrease in signal. For changes in DIP 12 position to take effect, the power to the actuator must 
be cycled. 

 
 
 
 

Set the communication parameters 

 
Data bits: 8 
 
Parity: None 
 
Stop bits: 1 
 
Baud Rate: The communication baud rate can be set by using the first two positions of the 

DIP switch 

selector

. Check the table below for settings. 

To change the baud rate, turn off the actuator, change the setting of DIP switches and power it up again. 
 

DIP 1 

DIP 2 

Baud rate 

OFF 

OFF 

2400 bps 

OFF 

ON 

4800 bps 

ON 

OFF 

9600 bps 

ON 

ON 

19200 bps 

 
Response time: The response time is between 8ms to 35ms. This means, after sending a frame, you have to 
wait at least 35ms for the answer coming back from the actuator. 
 

 

 

In this example DIPs 1, 2, 5 and 12 are on. 

Содержание MC-AS-1.05 Series

Страница 1: ...ignal and Feedback 3 Serial Port Connection 3 OPERATION 4 DIP switches 4 Set the communication parameters 4 Set the actuator address 5 Modbus Protocol 6 Speed and Torque Settings 7 Speed and Torque De...

Страница 2: ...standard with a Turck 6 position connector and a 20 cable with plug Cut the cable to the length required and then connect according to the following wire color schematic Pins indicate the connection...

Страница 3: ...Signal and Feedback Locate the correct connection terminals as shown in the picture on p 2 then connect your communication wires to PIN 3 and PIN 4 grey and pink wires as shown below Serial Port Conn...

Страница 4: ...n the signal is decreased with DIP 12 in the OFF position Putting DIP 12 in the ON position will cause counter clockwise turning for a decrease in signal For changes in DIP 12 position to take effect...

Страница 5: ...0 1 1 0 1 14 0 0 1 1 1 0 15 0 0 1 1 1 1 16 0 1 0 0 0 0 17 0 1 0 0 0 1 18 0 1 0 0 1 0 19 0 1 0 0 1 1 20 0 1 0 1 0 0 21 0 1 0 1 0 1 22 0 1 0 1 1 0 23 0 1 0 1 1 1 24 0 1 1 0 0 0 25 0 1 1 0 0 1 26 0 1 1...

Страница 6: ...e is not supported Actuator memory map Address DEC Address HEX Offset Register Name Type 0 0x0000 4001 MaximumSpeed Holding registers READ and WRITE 1 0x0001 4002 MaximumPower 2 0x0002 4003 NumberOfTu...

Страница 7: ...eed to 0 in actuator number 8 0x08 0x06 0x0000 0x0000 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes Possible values for the MaximumSpeed register are shown in the following table To see how these values re...

Страница 8: ...ess 0x0001 Seating Torque in lbs Operating torque is 100 12VDC 24VDC 0 23 0 17 35 1 11 1 30 60 2 7 2 55 115 3 4 3 70 145 NOTE If actuator is RCK xxxAS divide torque values by 3 To convert in lbs to Nm...

Страница 9: ...0x0B 0x06 0x0003 0x0000 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes The InputRangeLow register allows the user to set the lower limit of the input signal i e the value of the input signal at which the ac...

Страница 10: ...ing the valve completely This enables a new fully closed position to be established based on normal wear of the valve seat If the value in TargetPosition is the same as the value in InputRangeHigh the...

Страница 11: ...alLostPosition register The default value is 0xFFFF DEC 65535 The actuator will ignore the lost signal and simply remain in its current position If the value is between InputRangeLow and InputRangeHig...

Страница 12: ...lt Actuator address Function code Register address Qty of registers CRC StatusRegister 0x0015 N A N A N A Example Read the status register in actuator number 32 0x20 0x04 0x0015 0x0001 0x 1 byte 1 byt...

Страница 13: ...It will turn clockwise until the actuator has reached the fully closed position of the valve If the actuator is being controlled via Modbus protocol i e TargetFromRS485Flag register contains value 0...

Страница 14: ...s alone can solve basic problems See the Calibration section above for more details If the actuator does not move try following these steps 1 Re calibrate the actuator This will move the actuator rega...

Страница 15: ...User Manual MCx xxxAS 1 05 Page 15 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com ACTUATOR DIMENSIONS MCJ MCL MCM xxxAS models MCH xxxAS models...

Страница 16: ...User Manual MCx xxxAS 1 05 Page 16 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com MCF xxxAS models...

Страница 17: ...User Manual MCx xxxAS 1 05 Page 17 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com PART NUMBER BREAKDOWN Full Hanbay Part Number...

Страница 18: ...9 Px 10 3 Actuator Part Number Refer to part number breakdown for available options QR Code Scan this QR code for a direct link to the user manual for your unit Actuator Serial Number This serial numb...

Отзывы: