User Manual MCx-B-xxxAx-8.09 

 

 

 

Page 5 of 13

                                                                                                                         

www.hanbayinc.com | 1 800 315 4461      

Rev.2021.7                                                                                                                                                                              [email protected] 

OPERATION 

 

DIP switches 

 

 
The DIP switches allow you to change the  
settings on your actuator. To flip a switch, 
gently use a small flat-head screwdriver. 
 
See chart on next page for DIP switch functionality. 

 
 
 
 

 

 
 
 

DIP

 

Function

 


Speed:

 Choose how quickly the actuator will turn the drive wheel. See p.7.  

For external gear stage (MCH) 

– not an option for battery fail-safe model 






 

Turns:

 The actuator usually ships from the factory with the recommended number of turns for the 

valve. However, this number can be changed. Turning on a switch will add a specific number of 
turns to the actuator’s movement. 
See p.6 for relation between positions of the DIP switches and number of turns.  
Example: Turning on DIP 6 adds four turns, turning on DIP 8 adds one turn. If both DIP 6 and 8 are 
on, then the total turns of the actuator would be five. 

Signal loss:

 See p.8. 

10 
11 

Seating Torque:

 Set how much torque the actuator exerts on the valve lever during the calibration 

(finding valve seat) procedure. See p.7. 

12 
 

Direction/Calibration:

 Toggle switch on and off while powered to re-calibrate actuator. Also sets 

direction in which the actuator will open and close. See p.8. 
 
Example: The MCM model actuator turns clockwise when the signal is decreased with DIP 12 in the 
OFF position. Putting DIP 12 in the ON position will cause counterclockwise turning for a decrease 
in signal. For changes in DIP 12 position to take effect, the power to the actuator must be cycled. 
 
When cycling the power, the power must be off for at least 2 minutes to ensure the battery has 
switched off. 
 

 

 
 
 
 

Controlling the Actuator 

 
The 4-20 mA (or 1-5 V / 1-10 V) input signal represents a total span of a number of turns. 
I.e.:  If you set the number of turns to 2, then a signal of 12 mA will set the actuator to exactly 1 turn from the 
fully closed position. 15 mA will give: (15-4)/16=0.6875  

   68.75% of 2 turns   

  1.375 turns from closed. 

 

 

 

In this example DIPs 1, 2, 5 and 12 are on. 

 

Содержание MC A 8.09 Series

Страница 1: ...g 2 Wiring 2 Power Supply and Current Draw 3 Control Signal and Feedback 4 OPERATION 5 DIP switches 5 Controlling the Actuator 5 Changing the number of turns 6 Torque Settings 7 Speed and Torque Detai...

Страница 2: ...bing is minimum dia stainless Wiring The actuator comes standard with a Turck 5 position connector and a 20 cable with plug Cut the cable to the length required and then connect according to the follo...

Страница 3: ...or draws approx 50 mA Pin Function 6 Already Connected to battery board Connect 24 VDC wire to loose red cable with crimp connector 5 Already Connected to battery board Connect power ground wire to lo...

Страница 4: ...ctuator 4 20 mA output is internally supplying the signal current and can drive sufficient voltage for any sensing resistor of up to 250 ohms The potential of the external GND after the sensing resist...

Страница 5: ...the actuator would be five 9 Signal loss See p 8 10 11 Seating Torque Set how much torque the actuator exerts on the valve lever during the calibration finding valve seat procedure See p 7 12 Directi...

Страница 6: ...0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 5 0 1 0 1 6 0 1 1 0 7 0 1 1 1 8 1 0 0 0 9 1 0 0 1 10 1 0 1 0 11 1 0 1 1 12 1 1 0 0 13 1 1 0 1 14 1 1 1 0 15 1 1 1 1 WARNING Be sure that the number of turns...

Страница 7: ...two positions of the DIP switch selector As a result of this setting the actuator will limit the maximum speed The tables below show the time required to complete one turn The seating torque depends...

Страница 8: ...que in lbs Operating torque is 100 OFF OFF 161 OFF OFF 230 OFF ON 77 OFF ON 380 ON OFF 49 ON OFF 720 ON ON 28 ON ON 915 To convert in lbs to Nm divide by 9 The MCH model is not available with battery...

Страница 9: ...sition The default signal position is an absolute actuator position i e not a signal value 3 Re zeroing the actuator and initiating calibration routine The actuator will re zero when the input signal...

Страница 10: ...ital potentiometer will monitor the position of the valve during this fail safe operation 2 Once the valve has reached its fail safe position and after about one minute the P1 processor will go into s...

Страница 11: ...User Manual MCx B xxxAx 8 09 Page 11 of 13 www hanbayinc com 1 800 315 4461 Rev 2021 7 hanbaysales hanbayinc com ACTUATOR DIMENSIONS MCJ MCL MCM B xxxAx models MCF B xxxAx models...

Страница 12: ...User Manual MCx B xxxAx 8 09 Page 12 of 13 www hanbayinc com 1 800 315 4461 Rev 2021 7 hanbaysales hanbayinc com PART NUMBER BREAKDOWN Full Hanbay Part Number...

Страница 13: ...19 Px 10 3 Actuator Part Number Refer to part number breakdown for available options QR Code Scan this QR code for a direct link to the user manual for your unit Actuator Serial Number This serial num...

Отзывы: