Hamworthy Heating Limited                         Wessex Modumax mk3                                                       500001309-A 

LIGHTING INSTRUCTIONS 

 

Carry out the following procedure for each boiler 

 

Ensure the electrical mains supply to the boiler module 
is switched on and that any external controls are  
calling for heat (Time clock, BMS etc.). 

 

Depress blue On/Off button (7) The button will 
illuminate and the screen will update data. When the 
update is complete the screen will enter normal boiler 
mode. 
 

To set Time and date 
 

Press 

OK

 – To enter 

PROG

 screen - Time of day and 

date will be highlighted on screen. 
Press 

OK

 – Hours/minutes will be shown on screen. 

Press 

OK

 – Hours will flash – Use rotary knob to enter 

the hours required – Press 

OK

 to enter 

Press 

OK

 – Minutes will flash – Use rotary knob to  

enter minutes required – Press 

OK

 to enter 

Turn rotary knob – Day/month will be shown on screen 
Press 

OK

 – Month will flash – Use rotary knob to enter 

month required – Press 

OK

 to enter 

Press 

OK

 – Day will flash – Use rotary knob to enter 

day required – Press 

OK

 to enter 

Turn rotary knob – Year will be shown on screen. 
Press 

OK 

– Year will flash – Use rotary knob to enter 

year required – Press 

OK

 to enter 

When finished press 

ESC

 to return to 

PROG

 screen – 

Press 

ESC

 to return to Main screen 

 

To set time programme for heating circuit

 
Press 

OK

 – to enter 

PROG

 screen – Turn rotary knob 

to highlight Time prog heating circuit 1 
Press 

OK

 – Turn rotary knob - 1st phase on will be 

shown on screen 
Press 

OK

 – Time will flash – use rotary knob to enter 

time required – Press 

OK

 to enter 

Turn  rotary knob – 1st phase off will be shown on 
screen. 
Press 

OK

 – Time will flash – use rotary knob to enter 

time required – Press 

OK

 to enter 

 
Repeat process for 2nd and 3rd phases. 
 
When finished press 

ESC

 to return to 

PROG 

screen – 

Press 

ESC

 to return to Main screen. 

 

To set boiler flow setpoint for heating circuit 1 
 

Press 

OK

 – to enter 

PROG

 screen – Hold 

INFO 

button 

for 5 seconds 
Use rotary knob to select 

ENGINEER 

-Press 

OK 

Use rotary knob to select 

Heating Circuit 1

- Press 

OK 

Use rotary knob to select line 

741

 

Press 

OK

 – Setpoint will flash – Use rotary knob to set 

value required – Press 

OK

 to enter 

When finished press 

ESC

 to return to 

PROG 

screen – 

Press 

ESC

 to return to Main screen. 

To light the boiler 
 

Use the mode button (3) to select the desired operating 
mode. The boiler should go through it’s sequence and 
light. 

 
If sequence does not begin, check all external    
controls and safety interlocks are correct. 
 
Lockouts 

 
Should a lockout occur, a code will be displayed on the 
screen. 
A red LED is displayed constantly when a non-blocking 
fault is detected (following correction of the fault, the 
LED goes off). 
The LED flashes when a blocking fault is detected (in 
this case, the LED goes off after the fault has been cor-
rected and the reset button on the interface 
has been pressed), 
 
 

Should a Overheat lockout occur, a code will be dis-
played on the screen. The overheat thermostat will 
automatically re-set after sufficient temperature 
drop. To reset an Overheat condition, the boiler 
must be allowed to cool down. The reset button (1) 
must be depressed to clear the lockout condition. 

If the problem persists, seek expert advice from your 
installer or Hamworthy Heating Ltd. 
 
 

Shutting Down the Boiler 

 
To shut the boiler off for short periods i.e. 2 to 3 days, 
carry out the following procedure for each module of the 
boiler - 
 
Push the Mode button (3) until the Standby mode is se-
lected 
Alternatively the boiler can be put into setback operation 
by selecting the ‘Reduced’ mode. 
 

Note

:- During periods of intense cold weather, do not 

switch off the boiler module electrical mains supply, this 
will permit the system frost thermostat to function and 
protect the system. 
 
To shut the boiler off for longer periods i.e. during sum-
mer periods, carry out the following procedure for each 
module of the boiler  - 
 
1)  Switch the boiler module off as described above. 
2)  Depress the blue On/Off button (7) 
3)  Turn the main gas service valve off. 
 

Note

:- During periods of intense cold weather and with 

the boiler shut down for prolonged periods, the com-
plete system should be drained (including the boiler). A 
notice should be placed on the boiler highlighting the 
fact that the system has been drained down. 
The gas service valve should not be used, except in 
emergencies, or for long periods of shutdown or during 
servicing. 