4.6. Hydraulic connection
The boiler irrigation flow rate must be at least equal to Pinst/25 (Pinst =
instantaneous power in Th/h - 1 Th/h = 1.163 kW).
The circulation pump must be sized according to the maximum power
delivered.
In the main boiler, never exceed the flow rates specified in paragraph
3.4.
Figure 15 - Head losses
The boilers are equipped with the following elements:
•
a manual drain pipework,
•
a flow sensor.
It is imperative to fit the boiler and its installation with the following components:
•
isolating valves on the flow and return pipeworks,
•
an expansion tank,
•
an effective drain mechanism,
•
a filling mechanism (to be installed on the return pipework),
• a drain mechanism.
Loss of hydraulic head (mbar)
Loss of hydraulic head (mCE)
Flow rate (m
3
/h)