HAMWORTHY HEATING LTD
55
FLEET H series
500001212/F
Figure C3.1 - Room sealed C53 twin duct flue system
Model
Flue
size
Ø
Equivalent
lengths
(m)
Max
L
45°
90°
cond.
Drain
40
80/125
29
0.75
1
0.5
50
80/125
19
0.75
1
0.5
60
80/125
12
1.5
2
0.5
70
80/125
8
1.5
2
0.5
85
80/125
3
2
3
0.5
100
80/125
1
3
4
0.75
Model
Flue
size
Ø
Equivalent
lengths
(m)
Max
L
45°
90°
cond.
Drain
40
100/150
59
0.5
0.75
0.5
50
100/150
39
0.5
0.75
0.5
60
100/150
29
0.75
1
0.5
70
100/150
19
0.75
1
0.5
85
100/150
14
0.75
1
0.5
100
100/150
9
1
1.5
0.75
125
100/150
6
1
1.5
0.75
150
100/150
3
1
1.5
0.75
Figure C2.1.1 - Individual Flue
equivalent lengths - refer to fig. C2.1
Standard
Ver cal
fl
ue
kit
80/125Ø
HHL
Part
no
562511081
Op ons:
80/125Ø
87°
Elbow
532511124
80/125Ø
45°
Elbow
532511123
80/125Ø
*
1m
532511139
80/125Ø
cond.drain
532511162
Standard
Ver cal
fl
ue
kit
100/150Ø
HHL
Part
no
562511082
Op ons:
100/150Ø
87°
Elbow
532511118
100/150Ø
45°
Elbow
532511116
100/150Ø
*
1m
532511132
30
0 m
in
11
4
0
m
in
1100 min
1000
Содержание F40H
Страница 2: ......
Страница 35: ...HAMWORTHY HEATING LTD 29 FLEET H series 500001212 F Figure 8 2 1 3 Operation and display philosophy...
Страница 44: ...HAMWORTHY HEATING LTD 38 FLEET H series 500001212 F Figure 8 3 11 Operating phases...
Страница 75: ...HAMWORTHY HEATING LTD 69 FLEET H series 500001212 F NOTES...
Страница 77: ...Please complete the information on the Registration Card cut out and return to Hamworthy Heating Ltd...
Страница 78: ......
Страница 79: ......