HAMWORTHY HEATING LTD.                                                    APPENDIX 4                                                                               500001029/C

3

Unscrew the retaining screw securing the din
plug/s in place and carefully pull the plug/s
away from the valve or separate the plug and
socket in line connector near the control box.

Disconnect  the  flame  probe  and  electrode
leads by pulling off the ceramic cap from the
flame  probe  and  the  rubber  cap  from  the
spark electrode.

The  gas  train  assembly  is  secured  to  the
heater by two nuts on the front feet and screw
in  the  bottom  of  the  heater  casing  at  the
centre of the gas manifold.  Removal of these
enables the assembly to be withdrawn.

The  electrode  and  flame  probe  should  be
checked  for  cracked  ceramics  and  wear.
Replace as necessary and adjust to correct
gaps.  For servicing of the burners and the
internals  of  the  heater,  refer  to  the  main
installers guide, with the exception of the pilot
burner  which  is  not  fitted  to  the  automatic
version.

Reassemble  components  in  reverse  order,
taking care to replace the rubber sealing ring
in the union.

FAULT FINDING

1.    Heater  will  not  start,  controller  not
locked out:-

Check  continuity  across  control  thermostat
with  control  at  operating  temperature
position.

Check for high temperature limit thermostat
lockout.

2.    Heater  starts  but  controller  goes  to
lockout without ignition:-

Check gas valve operation (by pressure at
manifold test point during a start up attempt).

Check  ignition  electrode  connector  (wire  is
firmly screwed into ceramic connector) and
ignition transformer if no spark is produced.

3.  Heater starts, ignition occurs, controller
immediately goes to lockout:-

DR35-90L

Check flame probe connector (wire is firmly
screwed into ceramic connector).

Check flame probe position ie touching the
burner  bar  or  not  in  the  flame  will  cause  a
lockout (see Fig 5 for correct probe position).

DR70-90L

Reduce flame ignition time by adjusting the
main  valve  initial  opening.    Remove  the
protective cap from the top of the valve (see
Fig 4), reverse it and use to turn the spindle
exposed.    This  adjusts  the  rapid  initial
opening of the valve and thus the initial gas
pressure.    The  valve  is  initially  set  at  the
minimum  opening  position,  turn  counter-
clockwise to increase the opening.  Restart
the heater and replace protective cap.

Replace  control  box.   

NOTE! 

  To  remove

control box from its base, using a screwdriver
remove the retaining screw in the front of the
box and gently pull from the base.  Locate
and press home the new one and retighten
screw.

ADDITIONAL RECOMMENDED SPARES

Description

      Part Numbe

r

Control Valve 

3

/

4

 Dungs

533903013

Compact Gas Control Valve
23 mm in/out Honeywell
VR4601A (special)

531907008

Limit Thermostat

533901191

Controller

533901006

Ignition transformer

533901062

Electrode (ignition)

533805008

Probe (Flame Sensing)

533805007

Ceramic Cap (Probe)

533901060

Rubber Cap (Electrode)

533901255

Содержание DORCHESTER DR90L-CE

Страница 1: ...ST BE READ AND UNDERSTOOD BEFORE INSTALLING COMMISSIONING OPERATING OR SERVICING EQUIPMENT Installation Commissioning and Servicing Instructions supplement Dorchester DR35L CE to DR90L CE Hot Water St...

Страница 2: ...tive parts but does not include labour When the equipment is commissioned and routinely maintained by Hamworthy Heating under a Service Maintenance Agreement then the warranty terms will cover both pa...

Страница 3: ...CE TO DR90L CE HOT WATER STORAGE HEATERS INSTALLATION COMMISSIONING AND MAINTENANCE MANUAL FOR FULLY AUTOMATIC CONTROLS NOTE THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING OR COMMIS...

Страница 4: ...HAMWORTHY HEATING LTD APPENDIX 4 500001029 C ii This Page Left Intentionally Blank...

Страница 5: ...nual 500001001 The basic differences between the permanent pilot natural gas models and the fully automatic versions are as follows 1 The Honeywell V4410 softlite gas control valve is replaced by a Du...

Страница 6: ...ot light spark will continue for 5 seconds after which time the control box will lockout in a safe condition with the lockout button illuminated If this occurs switch off power supply wait 3 minutes c...

Страница 7: ...n by pressure at manifold test point during a start up attempt Check ignition electrode connector wire is firmly screwed into ceramic connector and ignition transformer if no spark is produced 3 Heate...

Страница 8: ...HAMWORTHY HEATING LTD APPENDIX 4 500001029 C 4...

Страница 9: ...HAMWORTHY HEATING LTD APPENDIX 4 500001029 C 5...

Страница 10: ...HAMWORTHY HEATING LTD APPENDIX 4 500001029 C 6...

Страница 11: ...HAMWORTHY HEATING LTD APPENDIX 4 500001029 C 7...

Страница 12: ...HAMWORTHY HEATING LTD APPENDIX 4 500001029 C 8...

Страница 13: ...218 New Chester Road 92 94 Dargan Crescent Birkenhead Duncrue Industrial Estate Merseyside L41 9BG Belfast BT3 9JP Tel 0151 666 1030 Tel 01232 777788 Fax 0151 647 8101 Fax 01232 776865 North East Eng...

Страница 14: ...liaise individual delivery arrangements SPARE PARTS 01202 662525 A comprehensive spare parts service is operated from our factory in Poole providing replacement parts for both current and discontinue...

Отзывы: