5.2  Mains Water Connections. 

 
It is a requirement of the Water Supply (Water Fittings) Regulations 1999 that the system is filled using an RPZ 
(Reduced Pressure Zone) valve with integral Type BA air gap. Information regarding the application, use and 
maintenance requirements for RPZ valves with Type BA air gap is available from WRAS. It is also advisable to 
contact the local water utility company to verify notification requirements for the use of these valves. 
 
With the electronic model of Chesil pressurisation unit it is not always necessary to use an RPZ valve for system 
filling as the units have a Fill function suitable for small systems to a maximum of 200 litres. Where this fill function 
is used it is not necessary to have a quick fill loop using an RPZ valve. 
 

5.3  Expansion Vessels. 

 
System expansion vessels must be constructed to BS4814 or BS6144. 
 
The required expansion vessel size is detailed in the contract documents. If in any doubt contact Hamworthy 
Heating Limited for comprehensive system sizing information. Hamworthy Heating Ltd supply the ‘Burstock’ range 
of suitable expansion vessels, details are shown below. A calculation sheet which can be used to determine a 
suitable volume for an expansion vessel can be found in the Appendix. 
 

Figure 7 - Hamworthy Heating Expansion Vessels—’Burstock’ 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Note: 

25 litre expansion vessels are supplied complete with wall mounting bracket 

 
 
 
 
5.4  Safety Relief Valve. 

 
Must comply with BS6759 part 1, and be sized and installed in accordance with BS6644 & BS7074. 

 

 

SALES REF NO. 

 

HAMWORTHY PART 

NO. 

 

TYPE 

 

TOTAL VOL.  

LITRES 

 

CONNECTION  

DETAILS 

 

WT  

kgs 

 

HOT WATER 

 APPLICATIONS - 

EPDM DIAPHRAGM  

(0-100°C MAX) 

 

 

 

 

 

PV25W (kit) 

563605641 

VERTICAL 

25 

G3/4” 

4.7 

 

PV60W 

 

5327120094 

 

VERTICAL 

 

60 

 

G1” 

 

14 

 

PV80W 

 

5327120095 

 

VERTICAL 

 

80 

 

G1” 

 

16 

 

PV100W 

 

532712096 

 

VERTICAL 

 

100 

 

G1” 

 

19 

 

PV200W 

 

532712088 

 

VERTICAL 

 

200 

 

G1 1/4” 

 

40 

 

PV300W 

 

532712089 

 

VERTICAL 

 

300 

 

G1 1/4” 

 

54 

 

PV400W 

 

532712090 

 

VERTICAL 

 

400 

 

G1 1/4” 

 

70 

 

PV500W 

 

532712091 

 

VERTICAL 

 

500 

 

G1 1/4” 

 

79 

 

PV800W 

 

532712092 

 

VERTICAL 

 

800 

 

G1 1/2” 

 

195 

 

PV1000W 

 

532712093 

 

VERTICAL 

 

1000 

 

G1 1/2” 

 

228 

Содержание 563216020

Страница 1: ...nt For Commercial Light Industrial Central Heating Installations Installation Commissioning and Servicing Instructions IMPORTANT NOTE THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING C...

Страница 2: ......

Страница 3: ...FOR USE ONLY IN COMMERCIAL LIGHT INDUSTRIAL APPLICATIONS THESE PRESSURISATION UNITS COMPLY WITH THE ESSENTIAL REQUIREMENTS OF THE MACHINERY DIRECTIVE 89 392 EEC AMENDED BY 91 368 EEC THE LOW VOLTAGE D...

Страница 4: ...Mechanical Installation 12 7 2 System Flushing 12 7 3 Electrical Installation 12 7 4 System Expansion Vessel 12 7 5 Initial Setting of Unit 13 7 6 Filling the Unit 13 7 7 Pump Spindle Access Hole 14 8...

Страница 5: ...15 Figure 18 Pump Removal 17 Figure 19 Pump Removal 17 Figure 20 Pump Removal 17 Figure 21 Pressure Sensor 18 Figure 22 Location Of Sensor 18 Figure 23 Control Box 18 Figure 24 Controller Terminals 18...

Страница 6: ...th a float valve to be connected to the water mains The pump draws the make up water pressurising the system from this tank In the wall mounted unit the user interface for the controller is accessed t...

Страница 7: ...6 To suit system conditions Maximum water flow temp C 82 Maximum static height m 16 5 Minimum system operating pressure bar 0 7 Maximum system operating pressure bar 7 0 Safety relief valve setting N...

Страница 8: ...d by the vessel When the system cools the pressure drops If there has been some fluid loss the pressurisation provides replacement 1 Diaphragm position at the cold fill charge pressure The vessel is e...

Страница 9: ...ing the system which should be filled with a suitable device such as an RPZ valve 5 0 GENERAL REQUIREMENTS 5 1 Related Documents Pressure Systems and Transportable Gas Containers Regulations 1989 It i...

Страница 10: ...l size is detailed in the contract documents If in any doubt contact Hamworthy Heating Limited for comprehensive system sizing information Hamworthy Heating Ltd supply the Burstock range of suitable e...

Страница 11: ...are shown in fig 9 below 6 1 Location 6 2 Pipework Connections Shown in Figure 10 1 Mains water connection BSP Male The units have a type AF air gap to prevent backflow in accordance with Water Supply...

Страница 12: ...HAMWORTHY HEATING LTD 7 CHESIL ELECTRONIC 500001181 K Figure 10 Pipework Connections Wall Mounted Figure 11 Pipework Connections Floor Standing...

Страница 13: ...revert to this unless it is in alarm condition 6 6 Trouble Shooting In the event of the unit not coming on when mains is applied then please return the unit to HHL for full investigation Once powered...

Страница 14: ...ce pump ops was last reset By pressing the enter button this will be reset to 0000 PUMP1 HRS XX XX This is Pump 1 hours run since pump 1 hrs was last reset By pressing the enter button this will be re...

Страница 15: ...n stop and FILL will flash on the screen To return the unit back to normal operation the enter key needs to be pressed again Once any required modifications have been made under Maintenance Menu it is...

Страница 16: ...hat Pump 2 has not increased the pressure in the system within the allowed time Same remedy as for Pump 1 Timed Out alarm There are volt free relays on the unit to give audible visual or BMS signals t...

Страница 17: ...the expansion vessel charge pressure the lock shield valve between the Chesil unit and the vessel must be closed The drain cock fitted on the base of the expansion vessel must be open to allow any wa...

Страница 18: ...suitable isolation valve 5 Check that the mains lead has been connected to a suitably fused and switched isolator 6 The cold fill pressure on the units are factory set to the levels listed in figure 3...

Страница 19: ...factory set operating parameters can be made following the instructions detailed in the maintenance section 6 8 7 7 Pump Spindle Access hole A 20mm hole has been added to the right hand side panel of...

Страница 20: ...ge Pump cuts in and out rapidly hunting Value of cut in coldfill pressure set incorrectly Non return valve not sealing correctly System Leak Adjust values Clean valve seat or replace valve if necessar...

Страница 21: ...valve to initiate a leak Note Ensure that the drain valve is closed after this operation 9 2 12 Monthly 1 Check the ball float valve diaphragm seat for integrity and replace if necessary Also check t...

Страница 22: ...inside the unit MUST be quoted For service or spares contacts please refer to the inside front cover of this guide 10 2 Pump Removal part n 530905053 530905054 1 Isolate unit from electrical water su...

Страница 23: ...he screw at the base of the sheet metal front cover of the unit and lift off the cover from the unit 3 Unscrew the 4 screws shown in figure 23 and remove the lid of the box 4 Disconnect the terminal c...

Страница 24: ...mbling the nuts 6 Reconnect the wires to the correct terminal of the PCB as defined in the wiring schematic of Appendix A1 7 Reassemble the lid of the box and reconnect the power to the unit 10 6 Repl...

Страница 25: ...l supply to the unit 10 8 Replacement Of Low Water Level Switch Part No 531203006 The tank contains a water level switch for general alarm indication 1 Isolate the unit from the mains water electrical...

Страница 26: ...e fig 14 1 Isolate the unit from the water supply 2 Undo 1 2 BSP connection to remove supply pipe 3 Unscrew the lock nut from the inlet tube The valve and float are now free to be removed 4 On the sta...

Страница 27: ...it could be subjected to ambient temperatures approaching 0 C At a set temperature determined by the thermostat supplied a small heating element affixed to the baseplate of the unit will be activated...

Страница 28: ...2 Main Wiring Diagram 24 Figure A3 Heating System Calculation Sheet 25 Figure A1 Frost Protection Kit Wiring Diagram CONNECTOR CONNECTOR BLUE BROWN 6 5 4 3 2 1 4 3 2 1 THERMOSTAT GREEN YELLOW BLACK BL...

Страница 29: ...11 12 13 14 15 16 17 PUMP 2 PUMP 1 1 2 Black Black WATER LEVEL SWITCH LOW ALARM NO PU POWERED LOW ALARM NC PU POWERED LOW ALARM COMMON HIGH ALARM NC PU POWERED HIGH ALARM NO PU POWERED HIGH ALARM COMM...

Страница 30: ...Hi pressure alarm level 3 Cold Fill Pressure Switch Setting Calculation Pf Ph Pf 0 2 0 2 Pf bar 10 2 10 2 4 Safety Valve Lift Pressure Calculation Ps Actual fitted expansion vessel volume Vva Vva litr...

Страница 31: ...HAMWORTHY HEATING LTD 26 CHESIL ELECTRONIC 500001181 K NOTES...

Страница 32: ...HAMWORTHY HEATING LTD 27 CHESIL ELECTRONIC 500001181 K INSTALLER SITE ADDRESS USEFUL USER INFORMATION...

Страница 33: ......

Страница 34: ...Road Glasgow Scotland G33 4AG tel 0141 336 8795 fax 0141 771 9635 North East England Service Allison Heating Products 12 Sunnyside Lane Cleadon Village Sunderland SR6 7XB tel 0191 536 8833 fax 0191 53...

Отзывы: