Hampton H300 Cast Freestanding Woodstove
10
FLOOR PROTECTION
A combustible fl oor must be protected by non-combustible material (like tile, concrete board, or certifi ed to UL-1618 or as defi ned by local codes)
extending beneath the heater and a minimum of 6" from each side and minimum 18" from the front face of the stove and minimum 6" (or the rear
clearance to combustibles whichever is smaller) from the rear of the stove.
When installed with horizontal venting, non-combustible fl oor protection must beneath the fl ue pipe and extend 2" (51mm) beyond each side.
NOTE: In Canada, fl oor protection must
extend 18" (450mm) to the front
and 8" (200mm) to each side and
back of the stove.
Minimum Overall Depth (Y) of Floor Protector
Residential Residential Mobile Home Alcove
Unit "C" Vent Close Clearance Close Clearance
Y Z
Y
Z
Y Z
Y
Z
H300 (US)
44-1/2" 6" (152 mm) 44-1/2" 6" (152 mm) 44-1/2" 6" (152 mm) 44-1/2" 6" (152 mm)
(1130 mm)
(1130 mm) (1130 mm)
(1130 mm)
H300 (Canada)
46-1/2" 8" (203 mm) 46-1/2" 8" (203 mm) 46-1/2" 8" (203 mm) 46-1/2" 8" (203 mm)
(1181 mm)
(1181 mm) (1181 mm)
(1181 mm)
INSTALLATION
IF SIDE LOAD DOOR IS USED:
Floor protection must extend 18" (457mm)
from the side of the unit to the wall.
Floor protection must be a minimum of 3/8"
thick with a minimum k factor of 0.84.
Minimum Overall Width (X) of Floor Protector
for all installations:
H300
39"
(990
mm)
-
US
43"
(1092mm)
-
Canada