pushbutton. The jumper wire connected to ERU connector box for raft 2 shall be 

removed. Leave the ERU connector box for ERU 1 without anything connected. Make 

sure that the ERU emulator now connected to ERU connector box for ERU 2 is flashing 

green. 

7.

 

Return to the ERRS CP2 control panel. The display shall now display RELEASE: RAFT 2. 

8.

 

Push the RELEASE pushbutton for 5 seconds. When the display reports RELEASING: 

RAFT 2 you can release the pushbutton. 

9.

 

Check that the ERU emulator connected to output 2 now is flashing red. If it is flashing 

red proceed to next step, if it still is flashing green check the wiring between the ERRS 

CP2 control panel and the ERU connector box.  

10.

 

Repeat step 6, 7, 8 and 9 for all outputs to ensure that all outputs activate ok. 

11.

 

When all outputs have been tested all jumper wires and the ERU emulator shall have 

been removed. 

12.

 

Return to the ERRS CP2 control panel and push the MAINTENANCE pushbutton to enter 

the maintenance menu. Use the scroll pushbuttons to scroll to menu item 5: RESET 

SYSTEM 

13.

 

Push the SELECT pushbutton. The control system will now be restarted and reset.  

14.

 

The H20ERU units in the system can now be connected and the covers for the ERU 

connector boxes can be closed. 

15.

 

Return to the ERRS CP2 control panel. The display shall now be dark without any 

message. 

16.

 

Remove the arrangement for securing the rafts in the racks. 

17.

 

The system is now operational and the test and verification is finished. 

If the system is configured for activation by activating the ERRS CP2 system inputs it shall be 

verified that the activation of the different inputs activates the correct outputs or sequence of 

outputs.  

 

Testing activation by the use of fuses 

 

Connect a fuse between the terminals in ERU connection box for the output to be tested. Connect 

jumper wires between the terminals in all other ERU connection boxes. Push the ON/OFF 

pushbutton on the ERRS2 control panel and use the scroll pushbuttons to select the output to be 

tested.  Have  someone to monitor the fuse and activate the output by pushing the RELEASE 

pushbutton. The fuse has to be monitored closely at the activation of the output in order to be 

able to visually verify that the activation current reaches the fuse. The fuse will give a very short 

flash of light at the activation if the output is ok but it does not always burn off. If the system is 

configured for activation by activating the ERRS CP2 system inputs it shall be verified that the 

activation of the different inputs activates the correct outputs or sequence of outputs.  

 

Final test of the ERRS system

 

 

The function of the installed ERRS CP2 system shall be verified by activating one or two outputs 

before the system is set to operate. The way to perform this test is to use a H20 ERU and activate 

it by means of the ERRS CP2 Control Panel. 

If more than one control panel is installed in a network it shall also be verified that the 

communication between the ERRS CP2  control panels is working correctly. Verify this by 

activating outputs connected to other ERRS CP2 control panels in the control panel network. See 

configuration specifications for the intended function of the system. 

 

IMPORTANT! 

In order to activate the guarantee for the HAMMAR ERRS SYSTEM the document: CHECKLIST 

FROM INSTALLATION AND TESTING OF HAMMAR ERRS CP2 SYSTEM has to be filled in and to be 

returned to CM HAMMAR AB by fax, e-mail or mail. 

Содержание ERRS CP2

Страница 1: ...and use of the ERRS system Note After the battery has been connected to the system it will automatically take over the power supply to the ERRS CP2 system if the ships emergency power supply is switc...

Страница 2: ...rder to avoid water or dirt to get inside the box When the installation is finished all holes in the ERRS CP2 enclosure shall have EMC cable glands or sealing plugs installed There shall be no opening...

Страница 3: ...tion so that it is ensured that the connection cable of the H20 ERU can be connected Mount the connector box with the cable glands in a horizontal position and in a protected position with respect to...

Страница 4: ...ERRS CP2 enclosure Only use the original type of cable glands Additional cable glands can be ordered from CM HAMMAR AB The Enclosure shall be connected to ships ground by the Ground connection device...

Страница 5: ...imum current consumption for the system is 0 5 A Internal fuses S1 1 0AF 5x20 mm glass tube fuse See wiring diagram for maximum cable length and area H20 ERU Cut the flexible cable of the H20 ERU to a...

Страница 6: ...ep 7 and 8 for all outputs to ensure that all outputs are connected to the right release unit 10 When all outputs have been checked push the MAINTENANCE pushbutton to exit the maintenance menu Activat...

Страница 7: ...inputs activates the correct outputs or sequence of outputs Testing activation by the use of fuses Connect a fuse between the terminals in ERU connection box for the output to be tested Connect jumpe...