background image

33

MM1 Series Hood Installation, Operation & Maintenance Manual  

OM032/0920

18/re

v6/EN

Wiring Diagram Detail – Oven Wiring Harness, 8 Pin Connector

Содержание MM1 Series

Страница 1: ...MM1 Series Hoods Model MM1 Form OM032_MM1_Series_Hoods Date 09 2018 Rev6 Operators Manual for MM1 Series Hood Manual provides Operation Maintenance and Service Instructions...

Страница 2: ...ve the hood to full design airflow is incorporated as well This switch should only be used if a problem occurs with the hoods control panel sensing the pizza oven s individual decks on off status Fiel...

Страница 3: ...ovens both gas and electric The hood can be used with single double or triple stack configurations at the design exhaust airflows shown on the submittal drawings in Appendix 1 Optional side skirts Mo...

Страница 4: ...4 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN PARTS IDENTIFICATION...

Страница 5: ...5 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN ITEMS SHIPPED INSIDE CONTROL PANEL...

Страница 6: ...ll thread rods at the hood For structural calculations assume the hood assembly weighs 500 lbs The fascia panels between the pods are removable to facilitate assembly Removing the front panel will all...

Страница 7: ...nd oven B Locate the control panel at the exhaust hood and wiring diagram for the system Review the wiring diagram and all instructions prior to beginning the process C Install current switches on blo...

Страница 8: ...ries Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Installation of Current Switch on 570 670 Alternate Installation of Current Switch on 570 670 wires routed into electrical acce...

Страница 9: ...owest oven deck E It will be necessary to drill holes as shown in the photos below to allow for harness routing Install grommets to avoid chafing of wires Holes should 7 8 diameter to allow grommet in...

Страница 10: ...10 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN 360G Harness Routing 2 Deck Example 360G Harness Installation Example...

Страница 11: ...11 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN 670 Harness Routing 3 Deck Example 670 Harness Installation Example...

Страница 12: ...to thermostat line Alternate 570 670 Install Example Avoid attaching adhesive pads directly to areas that get hot during cooking F The 8 pin connector should be positioned near the control panel loca...

Страница 13: ...e labeled to indicate appropriate oven deck Locate Deck 1 2 pin connection and connect to the current switch Ensure the all wires are safely installed using fastener mount cable holders and zip ties a...

Страница 14: ...the hood Tabs are provided along the side skirt flange which runs down the oven body which allows the side skirt to be attached to the oven at predetermined points These points are places where the e...

Страница 15: ...15 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Side Skirt Attachment Side Skirt Knobs Side Skirt Attachment Side Skirt Attachment...

Страница 16: ...16 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN...

Страница 17: ...compliant ductwork The hood is fabricated with a 14 X 14 exhaust collar When the hood is used with a triple stack oven the exhaust duct should be 14 X 14 to the exhaust fan When the hood is used with...

Страница 18: ...tions These instructions must be followed carefully and completely 7 Replace fascia panels if they have been removed 8 Complete Ansul installation page 26 Fire Suppression System if required A Locate...

Страница 19: ...upon makeup air unit configuration Please refer to site drawings to determine if required The field wiring from Terminal Strip contacts M98 and M99 to the make up air start stop contactor shall be 2...

Страница 20: ...20 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN RTC Solutions FSC Speed Controller...

Страница 21: ...21 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Exhaust Fan Control Greenheck Fan Controller...

Страница 22: ...22 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Wiring for S P fan with PerfectSpeed Controller PerfectSpeed Controller on Fan PerfectSpeed Controller Wiring...

Страница 23: ...g power source Connect a three wire 120V 15A circuit to terminals L Line N Neutral and G Ground in the Power Supply Box 10 Commission system starting on page 29 Make sure grease filters and grease cup...

Страница 24: ...r to be removed and installed from the end of the conveyor if the side skirts are installed Remove the crumb tray from its bracket Each bracket consists of two pieces that are assembled into the exist...

Страница 25: ...MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN For Installation and Control Wiring questions call EVS at 586 779 0996 Downloadable manuals may be found at www evsvent c...

Страница 26: ...n is required the local Ansul installer must also design and install the distribution piping and nozzles for this requirement This work must be performed by the Ansul system installer The side skirts...

Страница 27: ...27 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN MM1 Typical Fire Suppression System Isometric View...

Страница 28: ...28 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN MM1 Typical Fire Suppression System Schematic...

Страница 29: ...o off and exhaust fan will go to full speed 3 When the manual override is activated the exhaust fan will operate at full speed Commissioning 1 Ensure that the oven wiring harness is installed all fiel...

Страница 30: ...panel circuitry must be removed Remove the front cover of the control panel Remove the BLUE wire jumper between terminals 1 and 2 This will initiate an override setting that will change the default e...

Страница 31: ...led the makeup air unit is configured to be OFF in the event of a fire while the exhaust fan is to run at full design airflow 4 After the system has been placed into service and the balancing of airfl...

Страница 32: ...lton Part Number Filter 12 x 16 Aluminum Baffle 10163 Filter 12 x 20 Aluminum Baffle 10164 14 x 14 to 11 5 x 11 5 transition 57443 9 Duct Collar Extension 14PSW9 3AO Round Duct 11461 Collar Connector...

Страница 33: ...33 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Wiring Diagram Detail Oven Wiring Harness 8 Pin Connector...

Страница 34: ...34 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Wiring Diagram Detail Field wiring close up Airflow Jumper Detail Wiring close up...

Страница 35: ...35 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Wiring Diagram Detail Jumper wiring close up...

Страница 36: ...36 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Jumper Positions on MC8 Controller...

Страница 37: ...43 MM1 Series Hood Installation Operation Maintenance Manual OM032 092018 rev6 EN Appendix 2 Pre Fab Duct Installation...

Страница 38: ...ons and that it meets all specific requirements of lo cal code officials The local authority having jurisdiction could overrule some of the installation details written in this manual The installation...