background image

Operators Manual

Manual provides

Installation, Operation, and Maintenance Instructions

Models : KVE (SJ-SK) KVC (SJ-SK), KVW (SJ-SK),

KVR, KVO, KVL and KVM 

SWR / EO / DW / CH

SWS / SBS / SIR5

Содержание KVE (SJ-SK)

Страница 1: ...Operators Manual Manual provides Installation Operation and Maintenance Instructions Models KVE SJ SK KVC SJ SK KVW SJ SK KVR KVO KVL and KVM SWR EO DW CH SWS SBS SIR5...

Страница 2: ...im if needed GENERAL INSTALLATION It is the responsibility of the installing contractor to see that the system installation is completed in accordance with the project plans and specifications and tha...

Страница 3: ...gh the hanger brackets that are welded to the top of the hood Use of turnbuckles will make final adjustment easier Standard hanging height for canopy hoods ranges from 78 min to 84 max above the finis...

Страница 4: ...od or mounted in an electrical enclosure Information regarding the fan and speed controller see pg 12 2 Each Halton Capture Jet hood system will have a KSA filter remover model KFR The KFR will be pac...

Страница 5: ...e to wall screw head will not interfere with hood Screw backsplash to wall or attach with adhesive Halton canopy hoods should be installed from 78 min 84 max above the finished floor 1 Insulated Backs...

Страница 6: ...the turnbuckles will make final adjustments easier Hanging height of Canopy hoods should be per local building codes verify with Authority Having Jurisdiction for hanging height in your project locati...

Страница 7: ...collar with sheet metal screws or pop rivets and sealed with duct tape Screws or Rivets are not to interfere with the operation of the fire damper if equipped Recommended Exhaust Duct Installation Det...

Страница 8: ...screws for models with supply plenum Fig 1 Fig 2 U Channel For hood models that are placed back to back as shown in Fig 1 Slide the U Channel A up over the back of the hood systems and secure with she...

Страница 9: ...losure panel and vertical flange on top of hood should line up 2 Hammer clips C over the two vertical flanges 3 Attach panels B to wall using appropriate hardware D 4 Slide front panel A into place 5...

Страница 10: ...oks at point D close S hooks to secure 5 For final adjustment of fire damper tighten eye bolts at clips A B and C so that cable has no slack and assure maximum open position is obtained Access to fire...

Страница 11: ...to the hole located in the middle of the supply fire damper flange closing ends of the S hook to secure 3 On final adjustment of the supply fire damper tighten cable using eyebolts to assure maximum o...

Страница 12: ...CJOM 2009 rev2 EN 12 Standard Switch Panel Wiring For Hoods not equipped with Capture Jet By Electrician By Halton Wires Numbered as shown in junction box 5...

Страница 13: ...grated Capture Jet fan package as shown above T A B Ports KSA Filter Integrated Capture Jet fan Optional Standard Speed Controller 5 AMP Speed Controller wired on top of hood or located in the Control...

Страница 14: ...KVL 0 29 T A B Testing and Balancing Ports The Capture Jet and exhaust air flows are easily and accurately determined by measuring the pressure difference from the T A B Testing and Balancing ports m...

Страница 15: ...xhaust plenum the T A B Port reading AccuFlow installs in Capture Jet plenum for easy viewing and access The device shares an electrical circuit with the Capture Jet fan Photo 1 Halton AccuFlow Photo...

Страница 16: ...determined by Halton Research and Development personnel Bluetooth capability also allows an Authorized Service Agent to determine the airflow of an exhaust hood on site if an alarm is present This in...

Страница 17: ...roper electrical connections Verify or reconnect electrical connections Low airflow alarm Not reaching design airflow Plastic tubing disconnected from Accuflow device or TAB port Broken plastic tubing...

Страница 18: ...ntil filter slides out of plenum To install filter Place filter on KFR filter removal tool bracket raise filter into place inside exhaust plenum Slide upward until top lip of filter is locked into pla...

Страница 19: ...height Model KVR Round and Oval hoods can be shipped in pieces for field assembly If pieces are shipped loose parts will be marked for easy assembly and an Operation and Installation and Maintenance...

Страница 20: ...SA Filters Incandescent Lights Incandescent Lights Filters 78 84 A F F Standard Verify with Authority in project location for min hanging height Exhaust Air UL listed upblast fan for restaurant cookin...

Страница 21: ...1 Model CH Typical Installation Baffles Perimeter Gutter S S Drain CH w 2 baffles option Available with and without baffles 78 84 A F F Standard Verify with Authority in project location for hanging h...

Страница 22: ...le KSA Filters 78 84 A F F Standard Verify with Authority in project location for min hanging height 16 ga duct work all welded per code Optional Capture Jet intake location standard top mounted Captu...

Страница 23: ...Installation Filtered MUA unit on the roof 40 min 120 min 16 ga duct work all welded per code Stainless Steel KSA filters Capture Jet air 78 84 A F F 78 Std Make up airflow Verify with Authority in p...

Страница 24: ...estaurant cooking appliances 40 min 58 64 A F F Capture Jet fan Stainless Steel KSA filters 16 ga duct work all welded per code Note on Model KVL the Capture Jet fan is mounted on top of hood Capture...

Страница 25: ...restaurant cooking appliances 40 min 16 ga duct work all welded per code Capture Jet air Stainless Steel KSA filters Note on Model KVM the Capture Jet fan is integral Side Skirt Install NOTE Side Skir...

Страница 26: ...cooking appliances 78 84 A F F 78 Std Side view of typical install Integrated Capture Jet location 40 min S S KSA Filters Exhaust Air Incandescent lights T A B Ports Integrated Capture Jet fan Verify...

Страница 27: ...A filters Incandescent lighting T A B Ports Exhaust Air S S Perf Low Velocity Supply Air W 2 Perf Plenum Capture Jet Air W 1 Perf Plenum Supply Air Exhaust Air Supply Air Integrated Captur Jet fan Inc...

Страница 28: ...charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL APPLY ONLY to products that have been installed and maintained in accordance with the i...