background image

 

Take the B-cover and place it on the wall on the decided location. Screw the B-
cover to the wall (use anchor with concrete wall or gypsum board. Place the 
batteries inside the A-cover. 

 

Take A-cover and identify the product by reading the QR code in the side of the 
A-cover. To identify the device over Thingsee API, please follow the link for 
further information: 

https://support.haltian.com/api/open-services-api/api-

sequences/

 

 

Attach the A-cover to the B-cover attached to the wall. (Make sure the Thingsee 
logo is right way). 

 

Note: Make sure the sensor is installed max. 20 meters form the next sensor or 
gateway. This is to ensure full coverage mesh network between the sensors and 
the gateway. 

Detection Capability 

• C

O

2

measurement range 400 

 5 000 ppm; extended range up to 10 000 ppm. 

Accuracy ±3% (In extended range ±10%)  

• TVOC measurement range 0 –

 600000 ppb. Resolution 1ppb at range 0ppb-

2008ppb, 6ppb at range 2008ppb 

 11110ppb, 32 ppb at range 11110ppb - 

60000ppb  

• Temperature 

-40 ºC to + 85 ºC. Please note recommended operation 

temperature -0º C to +50 ºC. Accuracy ±0,2C.  

• Relative humidity can be measured between 0

-

100% RH. Accuracy ±2%. • 

Barometric pressure can be measured between 300-1200hPa. Absolute accuracy 
is ±1hPa. Pressure sensor precision is ±0.002hPa in high precision mode.  

• Ambient light sensing between 0

-100k lux. Light level measurement not 

calibrated. Only for indicative purposes. 

 

Содержание Thingsee AIR TSAR01

Страница 1: ...powered wireless IoT sensor for your indoor air quality monitoring Together with CO2 TVOC temperature barometric pressure and humidity sensors it is a perfect device to provide extensive overlook to b...

Страница 2: ...rops at least once per day Possibility for manual baseline calibration CO sensor is a nondispersive infrared sensor NDIR TVOC Total volatile organic compounds Resolution is 1ppb at range 0ppb 2008ppb...

Страница 3: ...95mm Height 26 88mm Length 92 95mm Weight 100 g Environment info Environment Operating temperature 5 C 50 C Operating humidity 0 85 RH non condensing Storage temperature 5 C 25 C Storage humidity 45 8...

Страница 4: ...ure is 400 ppm There must be free of people moments with full ventilation in the space so the device works best in locations where there are no people 24h Note Thingsee AIR requires free of people mom...

Страница 5: ...ps with hot surface Nearby radio equipment like WiFi routers or any other similar high power RF transmitters Avoid installing the sensor in close proximity to a spot where there s people presence cons...

Страница 6: ...he next sensor or gateway This is to ensure full coverage mesh network between the sensors and the gateway Detection Capability CO2measurement range 400 5 000 ppm extended range up to 10 000 ppm Accur...

Страница 7: ...e change 0 5 C Humidity when absolute change 2 Barometric pressure when absolute change 20 hPa Ambient light when absolute change 10000 Time based reporting Reports all measurement values every 1 hour...

Страница 8: ...radiation exposure limits set forth for an uncontrolled environment This equipment should be installed and operated with minimum distance of 5 mm between the radiator and your body This transmitter m...

Страница 9: ...taking them to appropriate collection point When changing batteries replace both of them at the same time using identical brand and type Do not swallow batteries Do not throw batteries into water or f...

Страница 10: ...f life The purpose of this Directive is as a first priority the prevention of WEEE and in addition to promote the reuse recycling and other forms of recovery of such wastes so as to reduce disposal Th...

Отзывы: