MAN2285-9
Page 12
This function is for display purposes only, and shows a value corresponding to the cur-rent airflow through the
detector.
4.29
Flow high limit
Flow monitoring tab
This value is the level above which airflow needs to increase to trigger a fault indication (which may indicate a
loose or damaged inlet pipe).
Flow low limit and Flow high limit are automatically set up on initial power-up.
4.30
Flow low limit
Flow monitoring tab
This value is the level below which airflow needs to be reduced to trigger a fault reading (which may indicate a
blocked pipe).
Flow low limit and Flow high limit are automatically set up on initial power-up.
4.31
Aspirator speed
Flow monitoring tab
This function has no current use on the FastSense 25 (reserved for future expansion).
4.32
Access code
Miscellaneous tab
This function has no current use on the FastSense 25 (reserved for future expansion).
4.33
Chart recording rate
Miscellaneous tab
This function controls how frequently the detector and alarm level or flow rates are stored in the FastSense
25’s internal chart recorder log. (see Section 5.3, ‘Chart recording’).
The chart log recording rates are as follows.
Setting
Type
Storage Interval
Time per Division on Chart Log
0
Detector output
1 second
10 seconds
1
Detector output
5 seconds
50 seconds
2
Detector output
12 seconds
2 minutes
3
Detector output
30 seconds
5 minutes
4
Detector output
1 minute
10 minutes
5
Detector output
2 minutes
20 minutes
6
Detector output
5 minutes
50 minutes
7
Detector output
10 minutes
100 minutes
8
Detector output
20 minutes
200 minutes
9
Detector output
50 minutes
500 minutes
10
flow recording
1 second
10 seconds
11
flow recording
5 seconds
50 seconds
12
flow recording
12 seconds
2 minutes
13
flow recording
30 seconds
5 minutes
14
flow recording
1 minute
10 minutes
15
flow recording
2 minutes
20 minutes
16
flow recording
5 minutes
50 minutes