Inspections
According to the inspection criteria regular inspections are
required; after exceptional incidents additional inspections
are required. All inspections have to be documented in an
inspection record.
Regular inspections / inspection before application
The contractor or operator must ensure that the HALFEN
HLX Lift-Box system is inspected at regular intervals.
Before each use, it must be ensured that the last inspection
and confi rmation of usability were not carried out more
than 12 months ago.
Frequent use or environmental eff ects may require shorter
periods between inspections. The inspections must only be
executed by qualifi ed persons and have to be recorded in
the inspection record.
Additional inspections
After unusual incidents which may infl uence the load
capacity of the HALFEN HLX Lift-Box or after maintenance
work, the contractor or operator has to ensure that an
additional inspection is done by a suitably qualifi ed
person and documented in the inspection record.
Inspection criteria
• Good, undamaged condition of the HALFEN HLX Lift-
Box components — signs of corrosion, broken strands
in the cable and visible deformations are not allowed.
• Perfect condition of the concrete slab — visible cracks,
spalling in the concrete and signs of corrosion are not
allowed.
• Proper condition of the marking – the anchorage point is
not to be used if the marking is not legible or missing.
• Cable loops must be checked for the following defects:
–
kinking
–
breakage in a loop
–
loosening of the exterior wires in the length of
the cable
–
compressive deformation
–
crushing in the load area of the load loop with
more than 4 wire breaks
–
in strand-cables and more than 10 breaks in
wire-laid cables
–
signs of corrosion
–
damage or exaggerated wear in the cable or cable
ferrule
–
large number of broken wires
–
Slippage between the cable loop and the ferrule
Do not use HLX Lift Box
if the following number of broken
wires are visible:
Wire breaks
Cable type
Visible wire breaks over a cable length of
3d
6d
10d
strand
cable
4
6
16
Inspection record
Year of production:
Date of fi rst use:
Date of purchase:
Identifi cation no.
Inspection
Date
Reason for inspection
(maintenance work or
regular periodical check)
Detected defi ciencies and
required maintenance work
Name / signature
of inspector
Date of next
inspection due: