FOR MORE INFO REFERENCE OIM MANUAL P/N FSG–MNL–00210 

4.

 

SAM AUTO MODE 

The SAM system opens the tank-to-pump valve when the pump is engaged and automatically recirculates 

water as required to prevent pump overheating by opening or closing the tank fill valve. NOTE: The onboard 

water tank is active (TANK OPEN) before any intakes. (See Figure 9) If a quickset is activated, SAM will begin 

flowing water. It is important that an offboard intake be established before the onboard water supply is ex-

hausted if pumping begins prior to connecting the offboard intake. 

 

Figure 9. 

SAM Control Center – Auto Mode – Home Screen 

4.1

 

Selecting A Water Supply 

Determine the offboard water source and select pump method (DRAFT or HYDRANT, Figure 9), touch and 

drag to toggle. 
4.1.1

 

Pressurized Water Supply (Hydrant) 

To activate a hydrant, connect supply hose to intake and open hydrant. On the SAM Control Center, touch 

and drag corresponding intake balloon to the associated target. 
NOTE: If intake is NOT close to SAM Control Center pressing the button on the MIV-Auto 

(located at the intake) actives the intake as if swiping on the SAM Control Center. 

(See Figure 10). 
SAM then bleeds the air, opens the intake valve, closes the tank-to-pump valve, and 

fills the water tank as the water supply permits. All this can be done while flowing water 

or before the discharge is opened. 

Figure 10.  MIV-Auto 

NOTES 

The automatic functions are not available for an auxiliary intake (Pony). 
A status indicator shows the operator what is happening. 

4.1.2

 

Draft Water Supply 

See paragraph 4.5 (page 9), DRAFTING WITH SAM, for details pertaining to drafting water in Auto Mode. 

Содержание SAM GENERATION 2

Страница 1: ...3 3569 800 520 3473 FAX www haleproducts com NOTICES THIS GUIDE IS INTENDED FOR QUICK REFERENCE ONLY DO NOT USE IT TO REPLACE REQUIRED TRAINING STANDARD OPERATING GUIDELINES REQUIRED BY THE AUTHORITY...

Страница 2: ......

Страница 3: ...CATORS AND THE PUMP CONTROLLER ARE ON BEFORE AT TEMPTING TO OPERATE THE PUMP FOLLOW ALL SOG STANDARD OPERATING GUIDELINES FOR PARKING BRAKE PUMP ENGAGEMENT AND WHEEL CHOCKS SAM PROVIDES AUTOMATED CONT...

Страница 4: ...erwritten in 1 second by auto mode The ITL 40 provides continuous display of the onboard water level Additionally the SAM Control Center dis plays the onboard water level with color indications yellow...

Страница 5: ...3 Figure 3 Entering Manual Mode From Splash or Auto Mode Home Screen No matter which screen is displayed touch the MANUAL MODE button orange and then touch YES to con firm see Figure 4 to access SAM M...

Страница 6: ...ll and or tank to pump buttons to open and close the valves as desired The Tank Info indicators bottom of screen show valve statuses Figure 6 Pump Controller Tank Screen Touch the Home button to retur...

Страница 7: ...To active SAM Auto Mode touch the ACTIVATE SAM AUTOFLOW button then touch YES see Figure 4 Figure 8 Akron Navigator Pro 9327 Left And 9335 Right NOTES For tank to pump tank fill or pony intake valves...

Страница 8: ...DRANT Figure 9 touch and drag to toggle 4 1 1 Pressurized Water Supply Hydrant To activate a hydrant connect supply hose to intake and open hydrant On the SAM Control Center touch and drag correspondi...

Страница 9: ...p to six 6 discharges To add more discharges simply 1 Activate another quickset drag desired quickset but ton to the ADD LINE button target or 2 Touch the ADD LINE button target If the ADD LINE button...

Страница 10: ...OTE Touch NO to do nothing Also the preset or CLOSE LINE balloon activates automatically Figure 13 Changing Discharge Pressure Use Preset Stop Balloon or SET PRESSURE Widget 4 3 SAM Auto Mode Alerts L...

Страница 11: ...aft toggle SAM to DRAFT see Figure 9 page 6 and connect an appropriate supply hose to the desired master intake See NOTES below On the SAM Control Center the icons change to indicated drafting and the...

Страница 12: ...e desired screen using the buttons on the left hand side of the screen Figure 17 Pump Info And Engine Data Screens Additionally when flow is above 600 GPM the Pump Controller also calculates displays...

Отзывы: