5-76
11. Allen-Bradley PLC
PLC-5 Series: Switch Setting
1785-KE
SW1 (Protocol)
SW2 (Port)
Set the port number of 1785-KE. (This port should not be duplicated in the network.)
SW3 (Network link communication speed)
Adjust to the settings of the network you are using.
SW4 (Spare)
No
Setting
Contents
1
ON
BCC, even, no
2
OFF
3
OFF
4
ON
Duplicated message unacceptable
5
OFF
Handshaking signal ignored
6
ON
Execution of diagnosis command
No
Setting
Contents
1
ON
1st digit (octal)
2
ON
3
ON/OFF
2nd digit (octal)
4
ON/OFF
5
ON/OFF
6
ON/OFF
3rd digit (octal)
7
ON/OFF
8
ON/OFF
No
Setting
Contents
1
ON
Data highway (57.6 kbps)
2
ON
3
ON
Link communication speed (19.2 kbps)
4
ON
5
ON
6
ON
Local/remote selection
No
Setting
Contents
1
OFF
For extension, always OFF
2
OFF
3
OFF
4
OFF