OPERATION

On/Off: Press ” to turn on, press ” again to turn off thermostat and its output.

Setting temperature: Press “

” to reduce set-point, press “

” to raise set-point, and 0.5

changed once.

Mode Selection: Press “ ” to change system working in cooling ”, heating ” or ventilation ” mode, the

related icon will flash ( The ventilation function is invalid for HL2023Y/YE)

Fan Speed Selection not for HL2023Y: Press

” to change fan speed among

(Hi)”,

(Med)”, “

(Low)” or “AUTO (Auto)”.

Under auto fan speed “AUTO”, the fan-speed will be changed automatically. Auto LOW-speed When the

difference between room-temperature and set-point is 1

; Auto MED-speed When difference is 2

; Auto Hi-speed

When difference is 3

.

Control Motorized-Damper (HL2023Y/YE): Under cooling (heating) mode, The damper will be open when the

room temperature is 1

higher than set-point in cooling, or room temperature is 1

lower than set-point in heating,

Otherwise the damper will be closed.

Control Motorized Valve under 2-pipe configuration (not for HL2023Y/YE): If the differential temperature between

room temperature and set-point exceed 1

, FCU valve will be open; if room temperature and set-point are equal,

HL2023DA/DAE/DA2/DA2E will close the FCU valve with the fan still running, HL2023DB/DBE/DB2/DB2E will close
both of valve and Fan.

Control FCU Valve under 4-pipe configuration (HL2023FCV2/FCV2E): In cooling, when the room temperature is

higher than set-point, the cooling Valve will be opened. Otherwise it will be closed. Heating valve is always closed. In
heating, When the room temperature is lower than set-point, the heating valve will be opened. Otherwise it will be closed.
Cooling valve is always closed

Keyboard Lock Function

Keypad Lock: its keypad would be automatically locked in 30 seconds in case that no one uses the thermostat,

so as to prohibit other persons from operating the thermostat.

Keypad ”for 5 seconds to unlock

In case that no one uses the thermostat, its keypad would be

automatically locked in 30 seconds

.

Low Temperature Protection Function

Turn off: When the room temperature is lower than 5

, the thermostat would automatically turn on the fan and

valve with

” showing, When the room temperature reaches to 7

, the thermostat will automatically close the

output.

Low Temperature Protection Setting

Turn off the thermostat, ” and hold for 3 seconds, it will display “OF” or “ON”, press “▲” or “▼” key to

adjust.

“OF” indicates low temperature protection invalid, “ON” indicates low temperature protection function valid. The default is
“OF”.

Temperature Adjustment

Temperature adjustment (±5

) can be done by following step:

Turn off the thermostat, press“▲”and “▼”hold for 3 seconds, it will display “XX

not displaying the thermostat

model

, press “▲”or “▼” to adjust the temperature value, it will be automatically confirmed after 6 second.