background image

                                                                                         

HaiLin Controls

 

Beijing HaiLin Auto Controls Equipment Co., Ltd.         Page 1 of 3                         Tel: +86 10 52816666 
International Information Industry Basement, HuilongguanNorth, Changping District, Beijing            www.hailin.com

 

HL2023 Series Thermostat User Manual 

HL2023 Series Touch Pad fan coil unit thermostats are designed to control the room 

temperature in air-conditioning fan coil unit system or dust pipe channel system. HL2023 

series thermostats with microprocessor and big LCD display. It shows the following items: 

working status (cool, heat or ventilation), fan speed, room temperature, set-point 

temperature etc. Keys include on/off (

),mode ( ),fan speed (

) and temperature 

adjustment ( 

S

 

T

 ). 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASIC FEATURES

                                               

LCD Display 

 Room temperature setting 

 Manual or auto 3-speed changeover 

 Defrost (low temperature protection) 

 Blue back light ( -L, Optional ) 

 Key lock ( Optional ) 

 Auto-restart ( Optional ) 

 Working Status: Cooling 

, Heating  or Ventilation   

 Fan Speed

Low

Med

High

 or 

AUTO

 

 FCU valve status 

 

 Room temperature display 

 Temperature setting display 

SPECIFICATIONS 

 Sensing element:    NTC 

 Accuracy:                     

±

 1

 

 Set-point range:      5  to 35

 

 Display range:       0

55

 

 Operation environment: 0

45

 

Operating Humidity: 5

90%RH 

(non-condensing) 

 Key:    soft    touch                                       

 Power supply:    AC 85

260V, 50/60Hz   

 Wirings: Accepting 2 × 1.5 mm

2

 or 1 x 2.5mm

2

 wires

 

 Switch current rating: Resistive: 2 A, Inductive: 1 A 

 Housing: PC + ABS Fire Retardant   

 Dimensions: 90

×

88

×

15.5 mm ( W × H × D ) 

 Hole pitch: 60 mm ( Standard ) 

 Protection Class: IP30 

 Rated Power: 

<

 1W 

 

MODEL DESCRIPTION

 

HL2023     -    

L

    blue backlit. Blank is invalid. 

Y

      Control damper to open or close 

DA/DA2

DA: Control 2-wire valve; DA2: Control 3-wire valve, 

When the temperature reaches the set-point, it will 
close the valve with the fan still running. 

DB/DB2: DB:Control 2-wire valve; DB2: Control 3-wire 

valve ,When the temperature reaches the set-point, 

it will close both the valve and fan. 

FCV2

 Control 4 pipe fan coil units, Control heating and 

cooling valves and 3-speed fan, when the 

temperature reaches the set-point, it will close the 

valves with the fan still running   

E

  auto-restart (Restart the working status of 

last 6 seconds before power off). Blank is 

invalid. 

Отзывы: