(automatic changeover between heat and cool). When disabled, AUTO 

icon does not appear when successive presses of MODE button are 

used to move between HEAT and COOL. Factory default is ON (AUTO 

mode enabled). 

TO ADJUST: 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 07.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 07 setting.

4. Use Up and Down buttons to move between the available Option 07

choices of ON or OF. Factory default is On.

5. Press Mode button again to return to Option 07. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 08

COOLING LOCKOUT 

"

 An outdoor air sensor is required for this function. In OF mode, 

cooling is available regardless of outdoor temperature. In ON mode, 

cooling will not be initiated if the outdoor air temperature is below 

55°F(12

). If the compressor is already operating and the outdoor air 

temperature drops below 55F, the compressor will continue to operate 

until the cooling cycle has completed. If the mode has been set to ON 

and the outdoor air sensor fails, E2 error will be displayed. 

TO ADJUST: 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 08.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 08 setting.

4. Use Up and Down buttons to move between the available Option 08

choices of ON or OF. Factory default is OF.

5. Press Mode button again to return to Option 08. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 09

KEYPAD LOCKOUT 

"

 In OF (off) mode, the keypad is not locked out and has full 

functionality. In ON mode, the keypad is locked out and press any 

key;”F1” will be displayed. To unlock the keypad, the user must press 

and hold the up and down buttons simultaneously for approximately 5 

seconds. The”F1” is turned off and the keypad will remain unlocked as 

long as the user presses a button at least every 30 seconds or for the 

entire duration of the installer test mode. If keypad remains idle for 

30seconds and the installer test mode is not in operation, the keypad 

will return to the locked state. 

TO ADJUST: 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 09.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 09 setting.

4. Use Up and Down buttons to move between the available Option 09

choices of ON or OF. Factory default is OF.

5. Press Mode button again to return to Option 09. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 10 – HEAT/ COOL SETPOINT(DESIRED TEMPRATURES)   

"

 A minimum difference of values is enforced between heating and 

cooling setpoints. For example, if 2 is selected, Heating setpoint is 23, 

Cooling minimum setpoint should be 25. Factory default is 2. 

TO ADJUST: 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 10.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 10 setting.

4. Use Up and Down buttons to move between the available Option 10

values 1 to 9. Factory default is 2.

5. Press Mode button again to return to Option 10. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode.

OPTION 11

O (REVERSING VALVE) ON WITH HEAT OR COOL 

SELECTION 

"

 This selection determines whether the reversing valve is energized in 

the heating or cooling mode. Factory default is C, energized in cooling. 

Use up and down buttons to change between H and C.   

TO ADJUST: 

1. Enter configuration mode (if not already there).

2. Use Up and Down n buttons to display Option 11.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 11 setting.

4. Use Up and Down buttons to move between the available Option 11

choices of C (Cooling) or H (Heating). Factory default is C.

5. Press Mode button again to return to Option 11. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 12 – COMPRESSOR PROTECTION 

"

 

In normal operation, when a stage turns on and then it turns off, it 

must keep off status at least for the setting time. This function avoids 

compressor or other equipment frequent turn on/off. Factory default is 

3 minutes. 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 12.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 12 setting.

4. Use Up and Down buttons to move between the available Option 12

values 0 to 12. Factory default is 3.

5. Press Mode button again to return to Option 12. The SET icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode.

OPTION 13 –MINIMUM ON TIME

"

 

In normal operation, when a stage turns off and then it turns on, it 

must keep on status at least for the setting time. This function avoids 

compressor or other equipment frequent turn on/off. Factory default is 

3 minutes. 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 13.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The display 

now shows Option 13 setting.

4. Use Up and Down buttons to move between the available Option 13

values 0 to 5. Factory default is 3.

5. Press Mode button again to return to Option 13. The SET icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 14 – AUTO MODE CONFIGURATION 

"

 

When the auto changeover mode is selected, a change from heat to 

cool (or vice versa) will not occur until an opposite mode demand has 

existed for the setting time. If the set point is changed, the setting time 

requirement is deleted. Auto mode may be disabled. Factory default is 

20 minutes. 

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 14.The “SET” icon should

be off.

3. Press Mode button once. The “SET” icon will be come on. The display 

now shows Option 14 setting.

4. Use up and down buttons to move between the available Option 14

values 0 to 20. Factory default is 3.

5. Press Mode button again to return to Option 14. The SET icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 15 – 

AUTO RECOVERY

 

"

 

Auto recovery feature means the thermostat will retain the previous 

status when power is back. This option can be used to choose whether 

auto recovery feature is enabled. 

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 15.The “SET” icon should

be off.

3. Press Mode button once. The “SET” icon will be come on. The display 

now shows Option 15 setting.

4. Use up and down buttons to move between the available Option 15

choices of 00(disable) or 01(enable). Factory default is 01.

5. Press Mode button again to return to Option 15. The SET icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 16 – 

AIR CONDITIONER OR HEAT PUMP SELECTION

 

"

 

To select between air conditioning and heat pump applications. A 

heat pump application uses a reversing valve. Set AC for air- 

conditioning applications (no reversing valve). Set HP for heat pump 

applications (O is used to energize the reversing valve). The factory 

setting is AC.

 

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 16.The “SET” icon should

be off.

3. Press Mode button once. The “SET” icon will be come on. The display 

now shows Option 16 setting.

4. Use up and down buttons to move between the available Option 16

choices of AC or HP. Factory default is AC.

5. Press Mode button again to return to Option 16. The SET icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode.

 

AIR CONDITIONER: 

HEAT PUMP: 

Installation

 

Thermostat Location 

Thermostat should be mounted: 

• Approximately 5 ft (1.5 m) from floor.

• Close to or in a frequently used room, preferably on an inside

partitioning wall.

• On a section of wall without pipes or duct work.

1.

Cut off the power, the mark of wire should be clear.

2. Take the main control panel

apart: put the screwdriver

(3.5mm wide) into 4mm of slot.

3. Push up by force, open the clip. 

4. Fix by the two screws in the

packing box. 

5. As per wiring drawing, connect

with terminals, fix it by 

screwdriver. 

6. Push the downside by force,

lock the up panel, and finish 

the installation. 

Wire Diagram

THERMOSTAT 

R(L) 

heating 

C(N)

Med

Low

Fan

O/W

Y

cooling 

AC24V  50/60Hz 

(

AC220V

±

10%

 50/60Hz

R(L)  C(N) 

Hi

THERMOSTAT 

R(L) 

Reversing val 

C(N)

Med

Low

Fan

o/w

Y

compressor 

Hi

AC24V  50/60Hz 

(

AC220V

±

10%

 50/60Hz

R(L)  C(N) 