28
Operation
(1) This function is used to compensate for ambient
temperature. In the state of off, and the backlight is lit up,
long press FAN key for 5 seconds to enter temperature
compensation interface. You can adjust the parameters with
or key. After adjustment, you need to press MENU key to
confirm change.
(2) When it is Celsius, the range of parameter adjustment is -4
~ 4. When it is Fahrenheit, the range of parameter adjustment
is -8 ~ 8.
(3) This function is valid only during collecting ambient
temperature of wired controller.
Temperature compensation
(1) After controller is in cooling mode and is turned off, long
press ON/OFF key for 10 seconds to enter forced cooling
function. At this time, controller will be turned on, and “LL”
flashes in the middle area to indicate that the forced cooling
function is turned on.
(2) After controller is in heating mode and is turned off, long
press ON/OFF key for 10 seconds to enter forced heating
function. At this time, controller will be turned on, and “HH”
flashes in the middle area to indicate that the forced heating
function is turned on.
Forced Cooling/Heating