Installations
Domestic air conditioner
32
Supposed
■
IPM protection dues to the compressor faulty
Causes
■
IPM protection dues to faulty PCB of IPM module
■
Compressor wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
NO
YES
Electrify the machine again and turn it on with
the rem ote controller ,If ma lfunctions are reported
before or upon the compressor being started up
.
IPM Mod ule is damaged
and needs replacing.
The compressor is started normally ,
but malfunctions are reported after it
has run for some time.
1
、
The system may have been over(like,capillary clogging or electronic expansion valve faulty ) or under
charged with gas, which can be judged through the pressure of the measuring system.
2
、
The shaft of compressor is seized and the compressor needs replacing.
Test IPM module resistance between P and U,V,W .
Then test IPM module resistance between N and U,V,W.
The resistances range are between 1M
Ω
with 10M
Ω
.and they
are similar.
NO
YES
10.3.6 Over-current of the compressor
Outdoor Display: LED1 flash 3 or 24 or 25 times
Method of The current of the compressor is too high
Malfunction
Detection
Malfunction when the IPM Module is damaged
Decision or the compressor is damaged.
Conditions power supply voltage is too low or too high
Supposed
■
Faulty IPM Module
Causes
■
Faulty compressor
■
Faulty power supply
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Содержание SUPER MATCH AS71S2SF1FA-CW
Страница 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 Expansion valve Expansion valve ...
Страница 14: ...Domestic air conditioner PCB 12 CN8 CN9 CN21 CN36 CN23 CN6 CN52 CN5 CN14 CN2 CN34 CN15 CN11 CN51 CN5 ...
Страница 47: ...Wall Mounted Type DC Inverter FREE MATCH N Series SERIES 70F ...