10.3.1 Thermistor or Related Abnormality
Indoor Display E1: Room temperature sensor failure
E2: Heat-exchange sensor failure
Outdoor display LED1 flash 10 times
:
Defrost temperature sensor failure
LED1 flash 11 times
:
Suction temperature sensor failure
LED1 flash 12 times
:
Ambient temperature sensor failure
LED1 flash 13 times
:
Discharge temperature sensor failure
Method of The temperatures detected by the thermistors are used to determine thermistor errors
Malfunction
Detection
Malfunction When the thermistor input is more than 4.92V or less than 0.08V during compressor
Decision operation.
Conditions
Note: The values vary slightly in some models
Supposed
■
Faulty connector connection
Causes
■
Faulty thermistor
■
Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Thermistor resistance check method:
Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester.The
relationship between normal temperature and resistance is shown in the value of indoor thermistor.
Thermistor resistance check
Is it normal?
Yes
NO
Yes
Is it normal?
NO
Check the connector connection.
Replace the thermistor
Replace the indoor unit PCB
Correct the connection
Содержание SUPER MATCH AS50S2SF1FA-WH
Страница 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 Expansion valve Expansion valve ...
Страница 14: ...Domestic air conditioner PCB 12 CN8 CN9 CN21 CN36 CN23 CN6 CN52 CN5 CN14 CN2 CN34 CN15 CN11 CN51 CN5 CN11 ...
Страница 15: ...Wiring Diagrams 13 Domestic air conditioner Wiring Diagrams ...
Страница 47: ...Wall Mounted Type DC Inverter ...