![Haier MRV II AV08NMVERA Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/haier/mrv-ii-av08nmvera/mrv-ii-av08nmvera_startup-manual_3714587017.webp)
GRUPAd.o.o.
17
2.12 Confirm the outdoor pipe length switch on outdoor PCB
SW4-1
piping length selection
SW4-1
SW4-2
medium piping length, cooling suction pressure:8.01kgf/cm
2
,
heating discharging pressure:28.0kgf/cm
2
0
0
0
1
1
0
1
1
SW4-2
description
medium piping length
long piping length, cooling suction pressure:7.51kgf/cm
2
,
heating discharging pressure:30.0kgf/cm
2
short piping length, cooling suction pressure:8.53kgf/cm
2
,
heating discharging pressure:26.0kgf/cm
2
1: ON
0: OFF
SW4-1, SW4-2
2.13 Confirm the outdoor capacity over match switch setting on outdoor PCB
0
1
SW4-4
over-match capacity
setting
allowable
forbidden
1: ON
0: OFF
SW4-4
Содержание MRV II AV08NMVERA
Страница 6: ...G R U P A d o o 06 2 Wiring work...
Страница 40: ...G R U P A d o o 40...