Service diagnosis
36
Domestic air conditioner
10.3.7 The communication fault between IPM and outdoor PCB
Outdoor display:
ƵƾƵ)
LED1 flash 4 times
Method of Communication is detected by checking the IPM module and the outdoor PCB
Malfunction
Detection
Malfunction
Ŷ
The outdoor PCB broken leads to communication fault
Decision
Ŷ
The IPM module broken leads to communication fault
Conditions
Supposed
Ŷ
The outdoor PCB is broken
Causes
Ŷ
The IPM module is broken
Ŷ
Communication wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
1) Check whether Terminal CN23 and CN24 on the outdoor mainboard
CN10 and CN11 on IPM module
2) Check whether the connected wire between IPM and outdoor
Are they good?
Electrify the machine again and turn it
on, Check whether the voltage between
1 and 2 of Terminal CN23 is about DC5V,
Check whether the voltage between2
and 3 of Terminal CN23 is about DC15V,
Replace the outdoor mainboard with a new one
Replace the outdoor IPM module
with a new one.
YES
NO
NO
YES
Malfunction unsolved
1) Pull out and reinsert the terminals.
2) Replace connected wire
Содержание JS035-D2
Страница 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 EEV EEV ...
Страница 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB 1 ...
Страница 27: ...Service diagnosis Domestic air conditioner 8 Dimensional drawings unit mm 9 Center of gravity unit mm 26 ...
Страница 46: ......
Страница 51: ...three 6 Removal Procedure 4 Domestic Air Conditioner Remove the casing 1 2 3 ...
Страница 55: ...Removal Procedure 8 Domestic Air Conditioner motor cover motor cover ...
Страница 56: ...Removal Procedure 9 Domestic Air Conditioner ...